Abstract: The application of ESS (Energy Storage Systems) in
the future grids has been the solution of the microgrid. However, high
investment costs necessitate accurate modeling and control strategy of
ESS to justify its economic viability and further underutilization.
Therefore, the reasonable control strategy for ESS which is subjected
to generator and usage helps to curtail the cost of investment and
operation costs. The rated frequency in power system is decreased
when the load is increasing unexpectedly; hence the thermal power is
operated at the capacity of only its 95% for the Governor Free (GF) to
adjust the frequency as reserve (5%) in practice. The ESS can be
utilized with governor at the same time for the frequency response due
to characteristic of its fast response speed and moreover, the cost of
ESS is declined rapidly to the reasonable price. This paper presents the
ESS control strategy to extend usage of the ESS taken account into
governor’s ramp rate and reduce the governor’s intervention as well.
All results in this paper are simulated by MATLAB.
Abstract: Increasingly complex modern power systems require
stability, especially for transient and small disturbances. Transient
stability plays a major role in stability during fault and large
disturbance. This paper compares a power system stabilizer (PSS)
and static Var compensator (SVC) to improve damping oscillation
and enhance transient stability. The effectiveness of a PSS connected
to the exciter and/or governor in damping electromechanical
oscillations of isolated synchronous generator was tested. The SVC
device is a member of the shunt FACTS (flexible alternating current
transmission system) family, utilized in power transmission systems.
The designed model was tested with a multi-machine system
consisting of four machines six bus, using MATLAB/SIMULINK
software. The results obtained indicate that SVC solutions are better
than PSS.
Abstract: The growth in the demand of electrical energy is
leading to load on the Power system which increases the occurrence
of frequent oscillations in the system. The reason for the oscillations
is due to the lack of damping torque which is required to dominate
the disturbances of Power system. By using FACT devices, such as
Unified Power Flow Controller (UPFC) can control power flow,
reduce sub-synchronous resonances and increase transient stability.
Hence, UPFC is used to damp the oscillations occurred in Power
system. This research focuses on adapting the neuro fuzzy controller
for the UPFC design by connecting the infinite bus (SMIB - Single
machine Infinite Bus) to a linearized model of synchronous machine
(Heffron-Phillips) in the power system. This model gains the
capability to improve the transient stability and to damp the
oscillations of the system.
Abstract: The subject of this paper is to review, comparative
analysis and simulation of selected components of power electronic
systems (PES), consistent with the concept of a more electric aircraft
(MEA). Comparative analysis and simulation in software
environment MATLAB / Simulink were carried out on the base of a
group of representatives of civil aircraft (B-787, A-380) and military
(F-22 Raptor, F-35) in the context of multi-pulse converters used in
them (6- and 12-pulse, and 18- and 24-pulse), which are key
components of high-tech electronics on-board power systems of
autonomous power systems (ASE) of modern aircraft (airplanes of
the future).
Abstract: The energy need is growing rapidly due to the
population growth and the large new usage of power. Several works
put considerable efforts to make the electricity grid more intelligent
to reduce essentially energy consumption and provide efficiency and
reliability of power systems. The Smart Grid is a complex
architecture that covers critical devices and systems vulnerable to
significant attacks. Hence, security is a crucial factor for the success
and the wide deployment of Smart Grids. In this paper, we present
security issues of the Smart Grid architecture and we highlight open
issues that will make the Smart Grid security a challenging research
area in the future.
Abstract: In recent years, the power system has been changed
and a flexible power pricing system such as demand response has been
sought in Japan. The demand response system works simply in the
household sector and the owner as the decision-maker, can benefit
from power saving. On the other hand, the execution of demand
response in the office building is more complex than in the household
because various people such as owners, building administrators and
occupants are involved in the decision-making process. While the
owners benefit from demand saving, the occupants are exposed to
restricted benefits of a demand-saved environment. One of the reasons
is that building systems are usually under centralized management and
each occupant cannot choose freely whether to participate in demand
response or not. In addition, it is unclear whether incentives give
occupants the motivation to participate. However, the recent
development of IT and building systems enables the personalized
control of the office environment where each occupant can control the
lighting level or temperature individually. Therefore, it can be possible
to have a system which each occupant can make a decision of whether
or not to participate in demand response in the office building. This study investigates personal responses to demand response
requests, under the condition where each occupant can adjust their
brightness individually in their workspace. Once workers participate
in the demand response, their desk-lights are automatically turned off.
The participation rates in the demand response events are compared
among four groups, which are divided by different motivation, the
presence, or absence of incentives and the method of participation. The
result shows that there are significant differences of participation rates
in demand response event between four groups. The method of
participation has a large effect on the participation rate. The “Opt-out”
groups where the occupants are automatically enrolled in a demand
response event if they do not express non-participation have the
highest participation rate in the four groups. Incentives also have an
effect on the participation rate. This study also reports on the impact of low illumination office
environment on the occupants, such as stress or fatigue. The
electrocardiogram and the questionnaire are used to investigate the
autonomic nervous activity and subjective fatigue symptoms of the
occupants. There is no big difference between dim workspace during
demand response event and bright workspace in autonomic nervous
activity and fatigue.
Abstract: This paper presents a grid synchronization technique based on adaptive notch filter for SPV (Solar Photovoltaic) system along with MPPT (Maximum Power Point Tracking) techniques. An efficient grid synchronization technique offers proficient detection of various components of grid signal like phase and frequency. It also acts as a barrier for harmonics and other disturbances in grid signal. A reference phase signal synchronized with the grid voltage is provided by the grid synchronization technique to standardize the system with grid codes and power quality standards. Hence, grid synchronization unit plays important role for grid connected SPV systems. As the output of the PV array is fluctuating in nature with the meteorological parameters like irradiance, temperature, wind etc. In order to maintain a constant DC voltage at VSC (Voltage Source Converter) input, MPPT control is required to track the maximum power point from PV array. In this work, a variable step size P & O (Perturb and Observe) MPPT technique with DC/DC boost converter has been used at first stage of the system. This algorithm divides the dPpv/dVpv curve of PV panel into three separate zones i.e. zone 0, zone 1 and zone 2. A fine value of tracking step size is used in zone 0 while zone 1 and zone 2 requires a large value of step size in order to obtain a high tracking speed. Further, adaptive notch filter based control technique is proposed for VSC in PV generation system. Adaptive notch filter (ANF) approach is used to synchronize the interfaced PV system with grid to maintain the amplitude, phase and frequency parameters as well as power quality improvement. This technique offers the compensation of harmonics current and reactive power with both linear and nonlinear loads. To maintain constant DC link voltage a PI controller is also implemented and presented in this paper. The complete system has been designed, developed and simulated using SimPower System and Simulink toolbox of MATLAB. The performance analysis of three phase grid connected solar photovoltaic system has been carried out on the basis of various parameters like PV output power, PV voltage, PV current, DC link voltage, PCC (Point of Common Coupling) voltage, grid voltage, grid current, voltage source converter current, power supplied by the voltage source converter etc. The results obtained from the proposed system are found satisfactory.
Abstract: This paper considers the design of Dual Proportional-
Integral (DPI) Load Frequency Control (LFC), using gravitational
search algorithm (GSA). The design is carried out for nonlinear
hydrothermal power system where generation rate constraint (GRC)
and governor dead band are considered. Furthermore, time delays
imposed by governor-turbine, thermodynamic process, and
communication channels are investigated. GSA is utilized to search
for optimal controller parameters by minimizing a time-domain based
objective function. GSA-based DPI has been compared to Ziegler-
Nichols based PI, and Genetic Algorithm (GA) based PI controllers
in order to demonstrate the superior efficiency of the proposed
design. Simulation results are carried for a wide range of operating
conditions and system parameters variations.
Abstract: There are a number of Distributed Generations (DGs)
installed in microgrid, which may have diverse path and direction of
power flow or fault current. The overcurrent protection scheme for the
traditional radial type distribution system will no longer meet the
needs of microgrid protection. Integrating the Intelligent Electronic
Device (IED) and a Supervisory Control and Data Acquisition
(SCADA) with IEC 61850 communication protocol, the paper
proposes a Microgrid Protection Management System (MPMS) to
protect power system from the fault. In the proposed method, the
MPMS performs logic programming of each IED to coordinate their
tripping sequence. The GOOSE message defined in IEC 61850 is used
as the transmission information medium among IEDs. Moreover, to
cope with the difference in fault current of microgrid between
grid-connected mode and islanded mode, the proposed MPMS applies
the group setting feature of IED to protect system and robust
adaptability. Once the microgrid topology varies, the MPMS will
recalculate the fault current and update the group setting of IED.
Provided there is a fault, IEDs will isolate the fault at once. Finally, the
Matlab/Simulink and Elipse Power Studio software are used to
simulate and demonstrate the feasibility of the proposed method.
Abstract: As per the statistical data, the Doubly-fed Induction
Generator (DFIG) based wind turbine with variable speed and
variable pitch control is the most common wind turbine in the
growing wind market. This machine is usually used on the grid
connected wind energy conversion system to satisfy grid code
requirements such as grid stability, Fault Ride Through (FRT), power
quality improvement, grid synchronization and power control etc.
Though the requirements are not fulfilled directly by the machine, the
control strategy is used in both the stator as well as rotor side along
with power electronic converters to fulfil the requirements stated
above. To satisfy the grid code requirements of wind turbine, usually
grid side converter is playing a major role. So in order to improve the
operation capacity of wind turbine under critical situation, the
intensive study of both machine side converter control and grid side
converter control is necessary In this paper DFIG is modeled using
power components as variables and the performance of the DFIG
system is analysed under grid voltage fluctuations. The voltage
fluctuations are made by lowering and raising the voltage values in
the utility grid intentionally for the purpose of simulation keeping in
view of different grid disturbances.
Abstract: The use of Flexible AC Transmission System
(FACTS) devices in a power system can potentially overcome
limitations of the present mechanically controlled transmission
system. Also, the advance of technology makes possible to include
new energy storage devices in the electrical power system. The
integration of Superconducting Magnetic Energy Storage (SMES)
into Static Synchronous Compensator (STATCOM) can lead to
increase their flexibility in improvement of power system dynamic
behaviour by exchanging both active and reactive powers with power
grids. This paper describes structure and behaviour of SMES,
specifications and performance principles of the STATCOM/SMES
compensator. Moreover, the benefits and effectiveness of integrated
SMES with STATCOM in power systems is presented. Also, the
performance of the STATCOM/SMES compensator is evaluated
using an IEEE 3-bus system through the dynamic simulation by
PSCAD/EMTDC software.
Abstract: High Voltage Direct Current (HVDC) power
transmission is employed to move large amounts of electric power.
There are several possibilities to enhance the transient stability in a
power system. One adequate option is by using the high
controllability of the HVDC if HVDC is available in the system. This
paper presents a control technique for HVDC to enhance the transient
stability. The strategy controls the power through the HVDC to help
make the system more transient stable during disturbances. Loss of
synchronism is prevented by quickly producing sufficient
decelerating energy to counteract accelerating energy gained during.
In this study, the power flow in the HVDC link is modulated with the
addition of an auxiliary signal to the current reference of the rectifier
firing angle controller. This modulation control signal is derived from
speed deviation signal of the generator utilizing a PD controller; the
utilization of a PD controller is suitable because it has the property of
fast response. The effectiveness of the proposed controller is
demonstrated with a SMIB test system.
Abstract: This paper presents an application of Artificial Neural
Network (ANN) algorithm for improving power system voltage
stability. The training data is obtained by solving several normal and
abnormal conditions using the Linear Programming technique. The
selected objective function gives minimum deviation of the reactive
power control variables, which leads to the maximization of
minimum Eigen value of load flow Jacobian. The considered reactive
power control variables are switchable VAR compensators, OLTC
transformers and excitation of generators. The method has been
implemented on a modified IEEE 30-bus test system. The results
obtain from the test clearly show that the trained neural network is
capable of improving the voltage stability in power system with a
high level of precision and speed.
Abstract: The use of hydroelectric pump-storage system at large
scale, MW-size systems, is already widespread around the world.
Designed for large scale applications, pump-storage station can be
scaled-down for small, remote residential applications. Given the cost
and complexity associated with installing a substation further than
100 miles from the main transmission lines, a remote, independent
and self-sufficient system is by far the most feasible solution. This
article is aiming at the design of wind and solar power generating
system, by means of pumped-storage to replace the wind and /or solar
power systems with a battery bank energy storage. Wind and solar
pumped-storage power generating system can reduce the cost of
power generation system, according to the user's electricity load and
resource condition and also can ensure system reliability of power
supply. Wind and solar pumped-storage power generation system is
well suited for remote residential applications with intermittent wind
and/or solar energy. This type of power systems, installed in these
locations, could be a very good alternative, with economic benefits
and positive social effects. The advantage of pumped storage power
system, where wind power regulation is calculated, shows that a
significant smoothing of the produced power is obtained, resulting in
a power-on-demand system’s capability, concomitant to extra
economic benefits.
Abstract: Implementation of advanced technologies requires
sophisticated instruments that deal with the operation, control,
restoration and protection of rapidly growing power system network
under normal and abnormal conditions. Presently, the applications of
Phasor Measurement Unit (PMU) are widely found in real time
operation, monitoring, controlling and analysis of power system
network as it eliminates the various limitations of supervisory control
and data acquisition system (SCADA) conventionally used in power
system. The use of PMU data is very rapidly increasing its
importance for online and offline analysis. Wide area measurement
system (WAMS) is developed as new technology by use of multiple
PMUs in power system. The present paper proposes a model of
Matlab based PMU using Discrete Fourier Transform (DFT)
algorithm and evaluation of its operation under different
contingencies. In this paper, PMU based two bus system having
WAMS network is presented as a case study.
Abstract: Nowadays, the use of renewable energy sources has been increasingly great because of the cost increase and public demand for clean energy sources. One of the fastest growing sources is wind energy. In this paper, Wind Diesel Hybrid System (WDHS) comprising a Diesel Generator (DG), a Wind Turbine Generator (WTG), the Consumer Load, a Battery-based Energy Storage System (BESS), and a Dump Load (DL) is used. Voltage is controlled by Diesel Generator; the frequency is controlled by BESS and DL. The BESS elimination is an efficient way to reduce maintenance cost and increase the dynamic response. Simulation results with graphs for the frequency of Power System, active power, and the battery power are presented for load changes. The controlling parameters are optimized by using Imperialist Competitive Algorithm (ICA). The simulation results for the BESS/no BESS cases are compared. Results show that in no BESS case, the frequency control is more optimal than the BESS case by using ICA.
Abstract: In a practical power system, the power plants are not
located at the same distance from the center of loads and their fuel
costs are different. Also, under normal operating conditions, the
generation capacity is more than the total load demand and losses.
Thus, there are many options for scheduling generation. In an
interconnected power system, the objective is to find the real and
reactive power scheduling of each power plant in such a way as to
minimize the operating cost. This means that the generator’s real and
reactive powers are allowed to vary within certain limits so as to meet
a particular load demand with minimum fuel cost. This is called
optimal power flow problem. In this paper, Economic Load Dispatch
(ELD) of real power generation is considered. Economic Load
Dispatch (ELD) is the scheduling of generators to minimize total
operating cost of generator units subjected to equality constraint of
power balance within the minimum and maximum operating limits of
the generating units. In this paper, genetic algorithms are considered.
ELD solutions are found by solving the conventional load flow
equations while at the same time minimizing the fuel costs.
Abstract: Due to the continuous increment of the load demand,
identification of weaker buses, improvement of voltage profile and
power losses in the context of the voltage stability problems has
become one of the major concerns for the larger, complex,
interconnected power systems. The objective of this paper is to
review the impact of Flexible AC Transmission System (FACTS)
controller in Wind generators connected electrical network for
maintaining voltage stability. Wind energy could be the growing
renewable energy due to several advantages. The influence of wind
generators on power quality is a significant issue; non uniform power
production causes variations in system voltage and frequency.
Therefore, wind farm requires high reactive power compensation; the
advances in high power semiconducting devices have led to the
development of FACTS. The FACTS devices such as for example
SVC inject reactive power into the system which helps in maintaining
a better voltage profile. The performance is evaluated on an IEEE 14
bus system, two wind generators are connected at low voltage buses
to meet the increased load demand and SVC devices are integrated at
the buses with wind generators to keep voltage stability. Power
flows, nodal voltage magnitudes and angles of the power network are
obtained by iterative solutions using MIPOWER.
Abstract: One of the key aspects of power quality improvement
in power system is the mitigation of voltage sags/swells and flicker.
Custom power devices have been known as the best tools for voltage
disturbances mitigation as well as reactive power compensation.
Dynamic Voltage Restorer (DVR) which is the most efficient and
effective modern custom power device can provide the most
commercial solution to solve several problems of power quality in
distribution networks. This paper deals with analysis and simulation
technique of DVR based on instantaneous power theory which is a
quick control to detect signals. The main purpose of this work is to
remove three important disturbances including voltage sags/swells
and flicker. Simulation of the proposed method was carried out on
two sample systems by using Matlab software environment and the
results of simulation show that the proposed method is able to
provide desirable power quality in the presence of wide range of
disturbances.
Abstract: Transmission system performance analysis is vital to
proper planning and operations of power systems in the presence of
deregulation. Key performance indicators (KPIs) are often used as
measure of degree of performance. This paper gives a novel method
to determine the transmission efficiency by evaluating the ratio of
real power losses incurred from a specified transfer direction.
Available Transmission Transfer Efficiency (ATTE) expresses the
percentage of real power received resulting from inter-area available
power transfer. The Tie line (Rated system path) performance is seen
to differ from system wide (Network response) performance and
ATTE values obtained are transfer direction specific. The required
sending end quantities with specified receiving end ATC and the
receiving end power circle diagram are obtained for the tie line
analysis. The amount of real power loss load relative to the available
transfer capability gives a measure of the transmission grid
efficiency.