Abstract: This paper presents a grid synchronization technique based on adaptive notch filter for SPV (Solar Photovoltaic) system along with MPPT (Maximum Power Point Tracking) techniques. An efficient grid synchronization technique offers proficient detection of various components of grid signal like phase and frequency. It also acts as a barrier for harmonics and other disturbances in grid signal. A reference phase signal synchronized with the grid voltage is provided by the grid synchronization technique to standardize the system with grid codes and power quality standards. Hence, grid synchronization unit plays important role for grid connected SPV systems. As the output of the PV array is fluctuating in nature with the meteorological parameters like irradiance, temperature, wind etc. In order to maintain a constant DC voltage at VSC (Voltage Source Converter) input, MPPT control is required to track the maximum power point from PV array. In this work, a variable step size P & O (Perturb and Observe) MPPT technique with DC/DC boost converter has been used at first stage of the system. This algorithm divides the dPpv/dVpv curve of PV panel into three separate zones i.e. zone 0, zone 1 and zone 2. A fine value of tracking step size is used in zone 0 while zone 1 and zone 2 requires a large value of step size in order to obtain a high tracking speed. Further, adaptive notch filter based control technique is proposed for VSC in PV generation system. Adaptive notch filter (ANF) approach is used to synchronize the interfaced PV system with grid to maintain the amplitude, phase and frequency parameters as well as power quality improvement. This technique offers the compensation of harmonics current and reactive power with both linear and nonlinear loads. To maintain constant DC link voltage a PI controller is also implemented and presented in this paper. The complete system has been designed, developed and simulated using SimPower System and Simulink toolbox of MATLAB. The performance analysis of three phase grid connected solar photovoltaic system has been carried out on the basis of various parameters like PV output power, PV voltage, PV current, DC link voltage, PCC (Point of Common Coupling) voltage, grid voltage, grid current, voltage source converter current, power supplied by the voltage source converter etc. The results obtained from the proposed system are found satisfactory.
Abstract: Among various active filters, shunt active filter is a
viable solution for reactive power and harmonics compensation. In
this paper, the SRF plan is used to generate current reference for
compensation and conventional PI controllers were used as the
controller to compensate the reactive power. The design of the closed
loop controllers is reserved simple by modeling them as first order
systems. Computationally uncomplicated and efficient SVM system
is used in the present work for better utilization of dc bus voltage.
The rating of shunt active filter has been finalized based on the
reactive power demand of the selected reactive load. The proposed
control and SVM technique are validated by simulating in MATLAB
software.
Abstract: A Space Vector based Pulse Width Modulation
control technique for the three-phase PWM converter is proposed in
this paper. The proposed control scheme is based on a synchronous
reference frame model. High performance and efficiency is obtained
with regards to the DC bus voltage and the power factor
considerations of the PWM rectifier thus leading to low losses.
MATLAB/SIMULINK are used as a platform for the simulations and
a SIMULINK model is presented in the paper. The results show that
the proposed model demonstrates better performance and properties
compared to the traditional SPWM method and the method improves
the dynamic performance of the closed loop drastically.
For the Space Vector based Pulse Width Modulation, Sine signal
is the reference waveform and triangle waveform is the carrier
waveform. When the value sine signal is large than triangle signal,
the pulse will start produce to high. And then when the triangular
signals higher than sine signal, the pulse will come to low. SPWM
output will changed by changing the value of the modulation index
and frequency used in this system to produce more pulse width. The
more pulse width produced, the output voltage will have lower
harmonics contents and the resolution increase.
Abstract: This paper presents a method for obtaining the
desired reference current for Voltage Source Converter (VSC) of the Shunt Active Power Filter (SAPF) using Synchronous Reference Frame Theory. The method relies on the performance of the Proportional-Integral (PI) controller for
obtaining the best control performance of the SAPF. To
improve the performance of the PI controller, the feedback
path to the integral term is introduced to compensate the
winding up phenomenon due to integrator. Using Reference
Frame Transformation, reference signals are transformed from
a - b - c stationery frame to 0 - d - q rotating frame.
Using the PI controller, the reference signals in the 0 - d - q rotating frame are controlled to get the desired reference signals for the Pulse Width Modulation. The synchronizer, the Phase Locked Loop (PLL) with PI filter is used for
synchronization, with much emphasis on minimizing delays. The system performance is examined with Shunt Active Power Filter simulation model.
Abstract: Back-to-back static synchronous compensator (BtBSTATCOM) consists of two back-to-back voltage-source converters (VSC) with a common DC link in a substation. This configuration extends the capabilities of conventional STATCOM that bidirectional active power transfer from one bus to another is possible. In this paper, VSCs are designed in quasi multi-pulse form in which GTOs are triggered only once per cycle in PSCAD/EMTDC. The design details of VSCs as well as gate switching circuits and controllers are fully represented. Regulation modes of BtBSTATCOM are verified and tested on a multi-machine power system through different simulation cases. The results presented in the form of typical time responses show that practical PI controllers are almost robust and stable in case of start-up, set-point change, and line faults.
Abstract: This paper proposes a new optimal feedback controller
for voltage source converters VSC's, for current regulated voltage
source converters, which allows compensate the harmonics of current
produced by nonlinear loads and load reactive power. The aim of the
present paper is to describe a novel switching signal generation
technique called optimal controller which guarantees that the injected
currents follow the reference currents determined by the
compensation strategy, with the smallest possible tracking error and
fixed switching frequency. It is compared with well-known
hysteresis current controller HCC. The validity of presented method
and its comparison with HCC is studied through simulation results.
Abstract: In this paper, based on steady-state models of Flexible
AC Transmission System (FACTS) devices, the sizing of static
synchronous series compensator (SSSC) controllers in transmission
network is formed as an optimization problem. The objective of this
problem is to reduce the transmission losses in the network. The
optimization problem is solved using particle swarm optimization
(PSO) technique. The Newton-Raphson load flow algorithm is
modified to consider the insertion of the SSSC devices in the
network. A numerical example, illustrating the effectiveness of the
proposed algorithm, is introduced. In addition, a novel model of a 3-
phase voltage source converter (VSC) that is suitable for series
connected FACTS a controller is introduced. The model is verified
by simulation using Power System Blockset (PSB) and Simulink
software.
Abstract: A generalized unified power quality conditioner
(GUPQC) by using three single-phase three-level voltage source
converters (VSCs) connected back-to-back through a common dc
link is proposed in this paper as a new custom power device for a
three-feeder distribution system. One of the converters is connected
in shunt with one feeder for mitigation of current harmonics and
reactive power compensation, while the other two VSCs are
connected in series with the other two feeders to maintain the load
voltage sinusoidal and at constant level. A new control scheme based
on synchronous reference frame is proposed for series converters.
The simulation analysis on compensation performance of GUPQC
based on PSCAD/EMTDC is reported.
Abstract: In a wind power generator using doubly fed induction
generator (DFIG), the three-phase pulse width modulation (PWM)
voltage source converter (VSC) is used as grid side converter (GSC)
and rotor side converter (RSC). The standard linear control laws
proposed for GSC provides not only instablity against comparatively
large-signal disturbances, but also the problem of stability due to
uncertainty of load and variations in parameters. In this paper, a
nonlinear controller is designed for grid side converter (GSC) of a
DFIG for wind power application. The nonlinear controller is
designed based on the input-output feedback linearization control
method. The resulting closed-loop system ensures a sufficient
stability region, make robust to variations in circuit parameters and
also exhibits good transient response. Computer simulations and
experimental results are presented to confirm the effectiveness of the
proposed control strategy.
Abstract: Static synchronous compensator (STATCOM) is a shunt connected voltage source converter (VSC), which can affect rapid control of reactive flow in the transmission line by controlling the generated a.c. voltage. The main aim of the paper is to design a power system installed with a Static synchronous compensator (STATCOM) and demonstrates the application of the linearised Phillips-heffron model in analyzing the damping effect of the STATCOM to improve power system oscillation stability. The proposed PI controller is designed to coordinate two control inputs: Voltage of the injection bus and capacitor voltage of the STATCOM, to improve the Dynamic stability of a SMIB system .The power oscillations damping (POD) control and power system stabilizer (PSS) and their coordinated action with proposed controllers are tested. The simulation result shows that the proposed damping controllers provide satisfactory performance in terms of improvements of dynamic stability of the system.
Abstract: In this paper, investigation of subsynchronous
resonance (SSR) characteristics of a hybrid series compensated
system and the design of voltage controller for three level 24-pulse
Voltage Source Converter based Static Synchronous Series
Compensator (SSSC) is presented. Hybrid compensation consists of
series fixed capacitor and SSSC which is a active series FACTS
controller. The design of voltage controller for SSSC is based on
damping torque analysis, and Genetic Algorithm (GA) is adopted for
tuning the controller parameters. The SSR Characteristics of SSSC
with constant reactive voltage control modes has been investigated.
The results show that the constant reactive voltage control of SSSC
has the effect of reducing the electrical resonance frequency, which
detunes the SSR.The analysis of SSR with SSSC is carried out based
on frequency domain method, eigenvalue analysis and transient
simulation. While the eigenvalue and damping torque analysis are
based on D-Q model of SSSC, the transient simulation considers both
D-Q and detailed three phase nonlinear system model using
switching functions.
Abstract: The proper selection of the AC-side passive filter
interconnecting the voltage source converter to the power supply is
essential to obtain satisfactory performances of an active power filter
system. The use of the LCL-type filter has the advantage of
eliminating the high frequency switching harmonics in the current
injected into the power supply. This paper is mainly focused on
analyzing the influence of the interface filter parameters on the active
filtering performances. Some design aspects are pointed out. Thus,
the design of the AC interface filter starts from transfer functions by
imposing the filter performance which refers to the significant current
attenuation of the switching harmonics without affecting the
harmonics to be compensated. A Matlab/Simulink model of the entire
active filtering system including a concrete nonlinear load has been
developed to examine the system performances. It is shown that a
gamma LC filter could accomplish the attenuation requirement of the
current provided by converter. Moreover, the existence of an optimal
value of the grid-side inductance which minimizes the total harmonic
distortion factor of the power supply current is pointed out.
Nevertheless, a small converter-side inductance and a damping
resistance in series with the filter capacitance are absolutely needed
in order to keep the ripple and oscillations of the current at the
converter side within acceptable limits. The effect of change in the
LCL-filter parameters is evaluated. It is concluded that good active
filtering performances can be achieved with small values of the
capacitance and converter-side inductance.