Abstract: Increasingly complex modern power systems require
stability, especially for transient and small disturbances. Transient
stability plays a major role in stability during fault and large
disturbance. This paper compares a power system stabilizer (PSS)
and static Var compensator (SVC) to improve damping oscillation
and enhance transient stability. The effectiveness of a PSS connected
to the exciter and/or governor in damping electromechanical
oscillations of isolated synchronous generator was tested. The SVC
device is a member of the shunt FACTS (flexible alternating current
transmission system) family, utilized in power transmission systems.
The designed model was tested with a multi-machine system
consisting of four machines six bus, using MATLAB/SIMULINK
software. The results obtained indicate that SVC solutions are better
than PSS.
Abstract: The growth in the demand of electrical energy is
leading to load on the Power system which increases the occurrence
of frequent oscillations in the system. The reason for the oscillations
is due to the lack of damping torque which is required to dominate
the disturbances of Power system. By using FACT devices, such as
Unified Power Flow Controller (UPFC) can control power flow,
reduce sub-synchronous resonances and increase transient stability.
Hence, UPFC is used to damp the oscillations occurred in Power
system. This research focuses on adapting the neuro fuzzy controller
for the UPFC design by connecting the infinite bus (SMIB - Single
machine Infinite Bus) to a linearized model of synchronous machine
(Heffron-Phillips) in the power system. This model gains the
capability to improve the transient stability and to damp the
oscillations of the system.
Abstract: This paper presents a procedure for modeling and tuning the parameters of Thyristor Controlled Series Compensation (TCSC) controller in a multi-machine power system to improve transient stability. First a simple transfer function model of TCSC controller for stability improvement is developed and the parameters of the proposed controller are optimally tuned. Genetic algorithm (GA) is employed for the optimization of the parameter-constrained nonlinear optimization problem implemented in a simulation environment. By minimizing an objective function in which the oscillatory rotor angle deviations of the generators are involved, transient stability performance of the system is improved. The proposed TCSC controller is tested on a multi-machine system and the simulation results are presented. The nonlinear simulation results validate the effectiveness of proposed approach for transient stability improvement in a multimachine power system installed with a TCSC. The simulation results also show that the proposed TCSC controller is also effective in damping low frequency oscillations.