Abstract: This paper considers the design of Dual Proportional-
Integral (DPI) Load Frequency Control (LFC), using gravitational
search algorithm (GSA). The design is carried out for nonlinear
hydrothermal power system where generation rate constraint (GRC)
and governor dead band are considered. Furthermore, time delays
imposed by governor-turbine, thermodynamic process, and
communication channels are investigated. GSA is utilized to search
for optimal controller parameters by minimizing a time-domain based
objective function. GSA-based DPI has been compared to Ziegler-
Nichols based PI, and Genetic Algorithm (GA) based PI controllers
in order to demonstrate the superior efficiency of the proposed
design. Simulation results are carried for a wide range of operating
conditions and system parameters variations.