Abstract: In this paper, we present a comparative assessment of
Space Vector Pulse Width Modulation (SVPWM) and Model
Predictive Control (MPC) for two-level three phase (2L-3P) Voltage
Source Inverter (VSI). VSI with associated system is subjected to
both control techniques and the results are compared.
Matlab/Simulink was used to model, simulate and validate the
control schemes. Findings of this study show that MPC is superior to
SVPWM in terms of total harmonic distortion (THD) and
implementation.
Abstract: This paper presents a hybrid three phase rectifier for
high power factor application. This rectifier is composed by zero
voltage transition (ZVT) and zero current transition (ZCT) boost
converter with three phase diode bridge rectifier, in parallel with a six
pulse three phase pulse width modulation (PWM) controlled rectifier.
The proposed topology is capable of high power factor with DC
output voltage regulation by providing sinusoidal input. Also, it
increases the overall efficiency of the new hybrid rectifier to 94.56%
and the total harmonic distortion of the hybrid structure varies from
0% to 16% at nominal output power. This topology was simulated in
MATLAB/SIMULINK environment and the output waveforms
presented with experimental result.
Abstract: Multilevel inverters such as flying capacitor, diodeclamped,
and cascaded H-bridge inverters are very popular
particularly in medium and high power applications. This paper
focuses on a cascaded H-bridge module using a single direct current
(DC) source in order to generate an 11-level output voltage. The
noble approach reduces the number of switches and gate drivers, in
comparison with a conventional method. The anticipated topology
produces more accurate result with an isolation transformer at high
switching frequency. Different modulation techniques can be used for
the multilevel inverter, but this work features modulation techniques
known as selective harmonic elimination (SHE).This modulation
approach reduces the number of carriers with reduction in Switching
Losses, Total Harmonic Distortion (THD), and thereby increasing
Power Quality (PQ). Based on the simulation result obtained, it
appears SHE has the ability to eliminate selected harmonics by
chopping off the fundamental output component. The performance
evaluation of the proposed cascaded multilevel inverter is performed
using PSIM simulation package and THD of 0.94% is obtained.
Abstract: Multilevel inverter is a promising inverter topology for high voltage and high power applications. This inverter synthesizes several different levels of DC voltages to produce a stepped AC output that approaches the pure sine waveform. The three different topologies, diode-clamped inverter, capacitor-clamped inverter and cascaded h-bridge multilevel inverter are widely used in these multilevel inverters. Among the three topologies, cascaded h-bridge multilevel inverter is more suitable for photovoltaic applications since each PV array can act as a separate dc source for each h-bridge module. This research especially focus on photovoltaic power source as input to the system and shows the potential of a Single Phase Cascaded H-bridge Eleven level inverter governed by the fuzzy logic controller to improve the power quality by reducing the total harmonic distortion at the output voltage. Hence the efficiency of the system will be improved. Simulation using MATLAB/SIMULINK has been done to verify the performance of cascaded h-bridge eleven level inverter using sinusoidal pulse width modulation technique. The simulated output shows very favorable result.
Abstract: Power quality in terms of power factor, THD and precisely regulated output voltage are the major key factors for efficient operation of power electronic converters. This paper presents an easy and effective active wave shaping control scheme for the pulsed input current drawn by the uncontrolled diode bridge rectifier thereby achieving power factor nearer to unity and also satisfying the THD specifications. It also regulates the output DC-bus voltage. CCM boost power factor correction with constant frequency operation features smaller inductor current ripple resulting in low RMS currents on inductor and switch thus leading to low electromagnetic interference. The objective of this work is to develop an active PFC control circuit using CCM boost converter implementing variable duty cycle control. The proposed scheme eliminates inductor current sensing requirements yet offering good performance and satisfactory results for maintaining the power quality. Simulation results have been presented which covers load changes also.
Abstract: This paper is based on the bridgeless single-phase Ac–Dc Power Factor Correction (PFC) converters with Fuzzy Logic Controller. High frequency isolated Cuk converters are used as a modular dc-dc converter in Discontinuous Conduction Mode (DCM) of operation of Power Factor Correction. The aim of this paper is to simplify the program complexity of the controller by reducing the number of fuzzy sets of the Membership Functions (MFs) and to improve the efficiency and to eliminate the power quality problems. The output of Fuzzy controller is compared with High frequency triangular wave to generate PWM gating signals of Cuk converter. The proposed topologies are designed to work in Discontinuous Conduction Mode (DCM) to achieve a unity power factor and low total harmonic distortion of the input current. The Fuzzy Logic Controller gives additional advantages such as accurate result, uncertainty and imprecision and automatic control circuitry. Performance comparisons between the proposed and conventional controllers and circuits are performed based on circuit simulations.
Abstract: Distributed Generation (DG) systems are considered an integral part in future distribution system planning. Appropriate size and location of distributed generation plays a significant role in minimizing power losses in distribution systems. Among the benefits of distributed generation is the reduction in active power losses, which can improve the system performance, reliability and power quality. In this paper, Artificial Bee Colony (ABC) algorithm is proposed to determine the optimal DG-unit size and location by loss sensitivity index in order to minimize the real power loss, total harmonic distortion (THD) and voltage sag index improvement. Simulation study is conducted on 69-bus radial test system to verify the efficacy of the proposed method.
Abstract: The aim of this paper is to identify an optimum
control strategy of three-phase shunt active filters to minimize the total harmonic distortion factor of the supply current. A classical PIPI cascade control solution of the output current of the active filterand the voltage across the DC capacitor based on Modulus–Optimum
criterion is taken into consideration. The control system operation
has been simulated using Matlab-Simulink environment and the results agree with the theoretical expectation. It is shown that there is
an optimum value of the DC-bus voltage which minimizes the supply current harmonic distortion factor. It corresponds to the equality of the apparent power at the output of the active filter and the apparent power across the capacitor. Finally, predicted results are verified experimentally on a MaxSine active power filter.
Abstract: The perfect operation of common Active Filters is depended on accuracy of identification system distortion. Also, using a suitable method in current injection and reactive power compensation, leads to increased filter performance. Due to this fact, this paper presents a method based on predictive current control theory in shunt active filter applications. The harmonics of the load current is identified by using o–d–q reference frame on load current and eliminating the DC part of d–q components. Then, the rest of these components deliver to predictive current controller as a Threephase reference current by using Park inverse transformation. System is modeled in discreet time domain. The proposed method has been tested using MATLAB model for a nonlinear load (with Total Harmonic Distortion=20%). The simulation results indicate that the proposed filter leads to flowing a sinusoidal current (THD=0.15%) through the source. In addition, the results show that the filter tracks the reference current accurately.
Abstract: This paper proposes a feed-forward control in
resonant dc link inverter. The feed-forward control configuration is
based on synchronous sigma-delta modulation. The simulation
results showing the proposed technique can reject non-ideal dc bus
improving the total harmonic distortion.
Abstract: This paper presents a low-voltage low-power differential linear transconductor with near rail-to-rail input swing. Based on the current-mirror OTA topology, the proposed transconductor combines the Flipped Voltage Follower (FVF) technique to linearize the transconductor behavior that leads to class- AB linear operation and the virtual transistor technique to lower the effective threshold voltages of the transistors which offers an advantage in terms of low supply requirement. Design of the OTA has been discussed. It operates at supply voltages of about ±0.8V. Simulation results for 0.18μm TSMC CMOS technology show a good input range of 1Vpp with a high DC gain of 81.53dB and a total harmonic distortion of -40dB at 1MHz for an input of 1Vpp. The main aim of this paper is to present and compare new OTA design with high transconductance, which has a potential to be used in low voltage applications.
Abstract: Power Factor (PF) is one of the most important parameters in the electrical systems, especially in the water pumping station. The low power factor value of the water pumping stations causes penalty for the electrical bill. There are many methods use for power factor improvement. Each one of them uses a capacitor on the electrical power network. The position of the capacitors is varied depends on many factors such as; voltage level and capacitors rating. Adding capacitors on the motor terminals increase the supply power factor from 0.8 to more than 0.9 but these capacitors cause some problems for the electrical grid network, such as increasing the harmonic contents of the grid line voltage. In this paper the effects of using capacitors in the water pumping stations to improve the power factor value on the harmonic contents of the electrical grid network are studied. One of large water pumping stations in Kafr El-Shikh Governorate in Egypt was used, as a case study. The effect of capacitors on the line voltage harmonic contents is measured. The station uses capacitors to improve the PF values at the 1 lkv grid network. The power supply harmonics values are measured by a power quality analyzer at different loading conditions. The results showed that; the capacitors improved the power factor value of the feeder and its value increased than 0.9. But the THD values are increased by adding these capacitors. The harmonic analysis showed that; the 13th, 17th, and 19th harmonics orders are increased also by adding the capacitors.
Abstract: Active power filter continues to be a powerful tool to control harmonics in power systems thereby enhancing the power quality. This paper presents a fuzzy tuned PID controller based shunt active filter to diminish the harmonics caused by non linear loads like thyristor bridge rectifiers and imbalanced loads. Here Fuzzy controller provides the tuning of PID, based on firing of thyristor bridge rectifiers and variations in input rms current. The shunt APF system is implemented with three phase current controlled Voltage Source Inverter (VSI) and is connected at the point of common coupling for compensating the current harmonics by injecting equal but opposite filter currents. These controllers are capable of controlling dc-side capacitor voltage and estimating reference currents. Hysteresis Current Controller (HCC) is used to generate switching signals for the voltage source inverter. Simulation studies are carried out with non linear loads like thyristor bridge rectifier along with unbalanced loads and the results proved that the APF along with fuzzy tuned PID controller work flawlessly for different firing angles of non linear load.
Abstract: This paper presents a pulse doubling technique in a 12-pulse ac-dc converter which supplies direct torque controlled motor drives (DTCIMD-s) in order to have better power quality conditions at the point of common coupling. The proposed technique increases the number of rectification pulses without significant changes in the installations and yields in harmonic reduction in both ac and dc sides. The 12-pulse rectified output voltage is accomplished via two paralleled six-pulse ac-dc converters each of them consisting of three-phase diode bridge rectifier. An autotransformer is designed to supply the rectifiers. The design procedure of magnetics is in a way such that makes it suitable for retrofit applications where a six-pulse diode bridge rectifier is being utilized. Independent operation of paralleled diode-bridge rectifiers, i.e. dc-ripple re-injection methodology, requires a Zero Sequence Blocking Transformer (ZSBT). Finally, a tapped interphase reactor is connected at the output of ZSBT to double the pulse numbers of output voltage up to 24 pulses. The aforementioned structure improves power quality criteria at ac mains and makes them consistent with the IEEE-519 standard requirements for varying loads. Furthermore, near unity power factor is obtained for a wide range of DTCIMD operation. A comparison is made between 6- pulse, 12-pulse, and proposed converters from view point of power quality indices. Results show that input current total harmonic distortion (THD) is less than 5% for the proposed topology at various loads.
Abstract: A new low-voltage floating gate MOSFET (FGMOS)
based squarer using square law characteristic of the FGMOS is
proposed in this paper. The major advantages of the squarer are simplicity,
rail-to-rail input dynamic range, low total harmonic distortion,
and low power consumption. The proposed circuit is biased without
body effect. The circuit is designed and simulated using SPICE in
0.25μm CMOS technology. The squarer is operated at the supply
voltages of ±0.75V . The total harmonic distortion (THD) for the
input signal 0.75Vpp at 25 KHz, and maximum power consumption
were found to be less than 1% and 319μW respectively.
Abstract: This paper present the harmonic elimination of hybrid
multilevel inverters (HMI) which could be increase the number of
output voltage level. Total Harmonic Distortion (THD) is one of the
most important requirements concerning performance indices.
Because of many numbers output levels of HMI, it had numerous
unknown variables of eliminate undesired individual harmonic and
THD nonlinear equations set. Optimized harmonic stepped waveform
(OHSW) is solving switching angles conventional method, but most
complicated for solving as added level. The artificial intelligent
techniques are deliberation to solve this problem. This paper presents
the Particle Swarm Optimization (PSO) technique for solving
switching angles to get minimum THD and eliminate undesired
individual harmonics of 15-levels hybrid multilevel inverters.
Consequently it had many variables and could eliminate numerous
harmonics. Both advantages including high level of inverter and
Particle Swarm Optimization (PSO) are used as powerful tools for
harmonics elimination.
Abstract: Properly sized capacitor banks are connected across induction motors for several reasons including power factor correction, reducing distortions, increasing capacity, etc. Total harmonic distortion (THD) and power factor (PF) are used in such cases to quantify the improvements obtained through connection of the external capacitor banks. On the other hand, one of the methods for assessing the motor internal condition is by the use of Park-s pattern analysis. In spite of taking adequate precautionary measures, the capacitor banks may sometimes malfunction. Such a minor fault in the capacitor bank is often not apparently discernible. This may however, give rise to substantial degradation of power factor correction performance and may also damage the supply profile. The case is more severe with the fact that the Park-s pattern gets distorted due to such external capacitor faults, and can give anomalous results about motor internal fault analyses. The aim of this paper is to present simulation and hardware laboratory test results to have an understanding of the anomalies in harmonic distortion and Park-s pattern analyses in induction motors due to capacitor bank defects.
Abstract: Multi-level voltage source inverters offer several
advantages such as; derivation of a refined output voltage with
reduced total harmonic distortion (THD), reduction of voltage ratings
of the power semiconductor switching devices and also the reduced
electro-magnetic-interference problems etc. In this paper, new
carrier-overlapped phase-disposition or sub-harmonic sinusoidal
pulse width modulation (CO-PD-SPWM) and also the carrieroverlapped
phase-disposition space vector modulation (CO-PDSVPWM)
schemes for a six-level diode-clamped inverter topology
are proposed. The principle of the proposed PWM schemes is similar
to the conventional PD-PWM with a little deviation from it in the
sense that the triangular carriers are all overlapped. The overlapping
of the triangular carriers on one hand results in an increased number
of switchings, on the other hand this facilitates an improved spectral
performance of the output voltage. It is demonstrated through
simulation studies that the six-level diode-clamped inverter with the
use of CO-PD-SPWM and CO-PD-SVPWM proposed in this paper is
capable of generating multiple levels in its output voltage. The
advantages of the proposed PWM schemes can be derived to benefit,
especially at lower modulation indices of the inverter and hence this
aspect of the proposed PWM schemes can be well exploited in high
power applications requiring low speeds of operation of the drive.
Abstract: Active Power Filters (APFs) are today the most
widely used systems to eliminate harmonics compensate power
factor and correct unbalanced problems in industrial power plants.
We propose to improve the performances of conventional APFs by
using artificial neural networks (ANNs) for harmonics estimation.
This new method combines both the strategies for extracting the
three-phase reference currents for active power filters and DC link
voltage control method. The ANNs learning capabilities to
adaptively choose the power system parameters for both to compute
the reference currents and to recharge the capacitor value requested
by VDC voltage in order to ensure suitable transit of powers to
supply the inverter. To investigate the performance of this
identification method, the study has been accomplished using
simulation with the MATLAB Simulink Power System Toolbox. The
simulation study results of the new (SAPF) identification technique
compared to other similar methods are found quite satisfactory by
assuring good filtering characteristics and high system stability.
Abstract: This paper presents a novel sinusoidal modulation
scheme that features least correlated noise and high linearity. The
modulation circuit, which is composed of a quantizer, a resonator, and
a comparator, is capable of eliminating correlated modulation noise
while doing modulation. The proposed modulation scheme combined
with the linear quadratic optimal control is applied to a single-phase
voltage source inverter and validated with the experiment results. The
experiments show that the inverter supplies stable 60Hz 110V AC
power with a total harmonic distortion of less than 1%, under the DC
input variation from 190 V to 300 V and the output power variation
from 0 to 600 W.