Abstract: The gases generated in oil filled transformers can be
used for qualitative determination of incipient faults. The Dissolved
Gas Analysis has been widely used by utilities throughout the world
as the primarily diagnostic tool for transformer maintenance. In this
paper, various Artificial Intelligence Techniques that have been used
by the researchers in the past have been reviewed, some conclusions
have been drawn and a sequential hybrid system has been proposed.
The synergy of ANN and FIS can be a good solution for reliable
results for predicting faults because one should not rely on a single
technology when dealing with real–life applications.
Abstract: Optimization and control of reactive power
distribution in the power systems leads to the better operation of the
reactive power resources. Reactive power control reduces
considerably the power losses and effective loads and improves the
power factor of the power systems. Another important reason of the
reactive power control is improving the voltage profile of the power
system. In this paper, voltage and reactive power control using
Neural Network techniques have been applied to the 33 shines-
Tehran Electric Company. In this suggested ANN, the voltages of PQ
shines have been considered as the input of the ANN. Also, the
generators voltages, tap transformers and shunt compensators have
been considered as the output of ANN. Results of this techniques
have been compared with the Linear Programming. Minimization of
the transmission line power losses has been considered as the
objective function of the linear programming technique. The
comparison of the results of the ANN technique with the LP shows
that the ANN technique improves the precision and reduces the
computation time. ANN technique also has a simple structure and
this causes to use the operator experience.
Abstract: In this paper, the transformers over-load problem of Shiraz substation in Fars Regional Electric Company (FREC) is investigated for a period of three years plan. So the suggestions for using phase shifting transformer (PST) and unified power flow controller (UPFC) in order to solve this problem are examined in details and finally, some economical and practical designs will be given in order to solve the related problems. Practical consideration and using the basic and fundamental concept of powers in transmission lines in order to find the economical design are the main advantages of this research. The simulation results of the integrated overall system with different designs compare them base on economical and practical aspects to solve the over-load and loss-reduction.
Abstract: This paper describes interconnection between
technical and economical making decision. The reason of this dealing
could be different: poor technical condition, change of substation
(electrical network) regime, power transformer owner budget deficit
and increasing of tariff on electricity. Establishing of recommended
practice as well as to give general advice and guidance in economical
sector, testing, diagnostic power transformers to establish its
conditions, identify problems and provide potential remedies.
Abstract: The winding hot-spot temperature is one of the most
critical parameters that affect the useful life of the power
transformers. The winding hot-spot temperature can be calculated as
function of the top-oil temperature that can estimated by using the
ambient temperature and transformer loading measured data. This
paper proposes the estimation of the top-oil temperature by using a
method based on Least Squares Support Vector Machines approach.
The estimated top-oil temperature is compared with measured data of
a power transformer in operation. The results are also compared with
methods based on the IEEE Standard C57.91-1995/2000 and
Artificial Neural Networks. It is shown that the Least Squares
Support Vector Machines approach presents better performance than
the methods based in the IEEE Standard C57.91-1995/2000 and
artificial neural networks.
Abstract: Bond graph models of an electrical transformer including
the nonlinear saturation are presented. The transformer
using electrical and magnetic circuits are modelled. These models
determine the relation between self and mutual inductances, and
the leakage and magnetizing inductances of power transformers
with two windings using the properties of a bond graph. The
equivalence between electrical and magnetic variables is given.
The modelling and analysis using this methodology to three phase
power transformers can be extended.
Abstract: Ferroresonance is an electrical phenomenon in
nonlinear character, which frequently occurs in power system due to
transmission line faults and single or more-phase switching on the
lines as well as usage of the saturable transformers. In this study, the
ferroresonance phenomena are investigated under the modeling of the
West Anatolian Electric Power Network of 380 kV in Turkey. The
ferroresonance event is observed as a result of removing the loads at
the end of the lines. In this sense, two different cases are considered.
At first, the switching is applied at 2nd second and the ferroresonance
affects are observed between 2nd and 4th seconds in the voltage
variations of the phase-R. Hence the ferroresonance and nonferroresonance
parts of the overall data are compared with each
others using the Fourier transform techniques to show the
ferroresonance affects.
Abstract: One of the problems in fault diagnosis of transformer
based on dissolved gas, is lack of matching the result of fault
diagnosis of different standards with the real world. In this paper, the
result of the different standards is analyzed using fuzzy and the result
is compared with the empirical test. The comparison between the
suggested method and existing methods indicate the capability of the
suggested method in on-line fault diagnosis of the transformers. In
addition, in some cases the existing standards are not able to
diagnose the fault. In theses cases, the presented method has the
potential of diagnosing the fault. The information of three
transformers is used to the show the capability of the suggested
method in diagnosing the fault. The results validate the capability of
the presented method in fault diagnosis of the transformer.
Abstract: Electricity market activities and a growing demand for electricity have led to heavily stressed power systems. This requires operation of the networks closer to their stability limits. Power system operation is affected by stability related problems, leading to unpredictable system behavior. Voltage stability refers to the ability of a power system to sustain appropriate voltage levels through large and small disturbances. Steady-state voltage stability is concerned with limits on the existence of steady-state operating points for the network. FACTS devices can be utilized to increase the transmission capacity, the stability margin and dynamic behavior or serve to ensure improved power quality. Their main capabilities are reactive power compensation, voltage control and power flow control. Among the FACTS controllers, Static Var Compensator (SVC) provides fast acting dynamic reactive compensation for voltage support during contingency events. In this paper, voltage stability assessment with appropriate representations of tap-changer transformers and SVC is investigated. Integrating both of these devices is the main topic of this paper. Effect of the presence of tap-changing transformers on static VAR compensator controller parameters and ratings necessary to stabilize load voltages at certain values are highlighted. The interrelation between transformer off nominal tap ratios and the SVC controller gains and droop slopes and the SVC rating are found. P-V curves are constructed to calculate loadability margins.
Abstract: Power systems and transformer are intrinsic apparatus, therefore its reliability and safe operation is important to determine their operation conditions, and the industry uses quality control tests in the insulation design of oil filled transformers. Hence the service period effect on AC dielectric strength is significant. The effect of aging on transformer oil physical, chemical and electrical properties was studied using the international testing methods for the evaluation of transformer oil quality. The study was carried out on six transformers operate in the field and for monitoring periods over twenty years. The properties which are strongly time dependent were specified and those which have a great impact on the transformer oil acidity, breakdown voltage and dissolved gas analysis were defined. Several tests on the transformers oil were studied to know the time of purifying or changing it, moreover prediction of the characteristics of it under different operation conditions.
Abstract: Bond graph models of an electrical transformer
including the nonlinear saturation are presented. These models
determine the relation between self and mutual inductances, and
the leakage and magnetizing inductances of power transformers
with two and three windings using the properties of a bond
graph. The modelling and analysis using this methodology to
three phase power transformers or transformers with internal
incipient faults can be extended.
Abstract: The present paper deals with the analysis and development of noise-reduction transformer that has a filter function for conductive noise transmission. Two types of prototype noise-reduction transformers with two different output voltages are proposed. To determine an optimum design for the noise-reduction transformer, noise attenuation characteristics are discussed based on the experiments and the equivalent circuit analysis. The analysis gives a relation between the circuit parameters and the noise attenuation. High performance step-down noise-reduction transformer for direct power supply to electronics equipment is developed. The input voltage of the transformer is 100 V and the output voltage is 5 V. Frequency characteristics of noise attenuation are discussed, and prevention of pulse noise transmission is demonstrated. Normal mode noise attenuation of this transformer is –80 dB, and common mode exceeds –90 dB. The step-down noise-reduction transformer eliminates pulse noise efficiently.
Abstract: Design of Converter transformer insulation is a major
challenge. The insulation of these transformers is stressed by both
AC and DC voltages. Particle contamination is one of the major
problems in insulation structures, as they generate partial discharges
leading it to major failure of insulation. Similarly corona discharges
occur in transformer insulation. This partial discharge due to particle
movement / corona formation in insulation structure under different
voltage wave shapes, are different. In the present study, UHF
technique is adopted to understand the discharge activity and could
be realized that the characteristics of UHF signal generated under
low and high fields are different. In the case of corona generated
signal, the frequency content of the UHF sensor output lies in the
range 0.3-1.2 GHz and is not much varied except for its increase in
magnitude of discharge with the increase in applied voltage. It is
realized that the current signal injected due to partial
discharges/corona is about 4ns duration measured for first one half
cycle. Wavelet technique is adopted in the present study. It allows
one to identify the frequency content present in the signal at different
instant of time. The STD-MRA analysis helps one to identify the
frequency band in which the energy content of the UHF signal is
maximum.
Abstract: This paper proposes a set of quasi-static mathematical
model of magnetic fields caused by high voltage conductors of
distribution transformer by using a set of second-order partial
differential equation. The modification for complex magnetic field
analysis and time-harmonic simulation are also utilized. In this
research, transformers were study in both balanced and unbalanced
loading conditions. Computer-based simulation utilizing the threedimensional
finite element method (3-D FEM) is exploited as a tool
for visualizing magnetic fields distribution volume a distribution
transformer. Finite Element Method (FEM) is one among popular
numerical methods that is able to handle problem complexity in
various forms. At present, the FEM has been widely applied in most
engineering fields. Even for problems of magnetic field distribution,
the FEM is able to estimate solutions of Maxwell-s equations
governing the power transmission systems. The computer simulation
based on the use of the FEM has been developed in MATLAB
programming environment.
Abstract: The behavior of three phase five leg transformer under voltage sag is studied in this paper. This paper proposes a simple, practical model of a three phase-five leg, saturated transformer with accurate performance. Transformer saturation is produced when the voltage sag is recovered and it causes inrush current in transformer. Effects of voltage sag depth, duration and initial point on wave have been analyzed in this paper. Initial point on wave can produce maximum inrush current in five leg transformers while comparing with three leg transformers. The magnetic circuit symmetry of five leg transformer produces the more symmetrical shape of inrush current curves versus initial point on wave and sag duration than three leg transformer. The simulations show that current peak has a periodical dependence on sag duration and linear dependence on sag depth. Inrush current that is produced in three phase five leg transformer is higher than three phase three leg transformer.
Abstract: In this paper, multilayered coreless printed circuit
board (PCB) step-down power transformers for DC-DC converter
applications have been designed, manufactured and evaluated. A set
of two different circular spiral step-down transformers were
fabricated in the four layered PCB. These transformers have been
modelled with the assistance of high frequency equivalent circuit and
characterized with both sinusoidal and square wave excitation. This
paper provides the comparative results of these two different
transformers in terms of their resistances, self, leakage, mutual
inductances, coupling coefficient and also their energy efficiencies.
The operating regions for optimal performance of these transformers
for power transfer applications are determined. These transformers
were tested for the output power levels of about 30 Watts within the
input voltage range of 12-50 Vrms. The energy efficiency for these
step down transformers is observed to be in the range of 90%-97% in
MHz frequency region.
Abstract: Temperature rise in a transformer depends on variety
of parameters such as ambient temperature, output current and type
of the core. Considering these parameters, temperature rise estimation
is still complicated procedure. In this paper, we present a new model
based on simple electrical equivalent circuit. This method avoids the
complication associated to accurate estimation and is in very good
agreement with practice.
Abstract: With Power system movement toward restructuring along with factors such as life environment pollution, problems of transmission expansion and with advancement in construction technology of small generation units, it is expected that small units like wind turbines, fuel cells, photovoltaic, ... that most of the time connect to the distribution networks play a very essential role in electric power industry. With increase in developing usage of small generation units, management of distribution networks should be reviewed. The target of this paper is to present a new method for optimal management of active and reactive power in distribution networks with regard to costs pertaining to various types of dispersed generations, capacitors and cost of electric energy achieved from network. In other words, in this method it-s endeavored to select optimal sources of active and reactive power generation and controlling equipments such as dispersed generations, capacitors, under load tapchanger transformers and substations in a way that firstly costs in relation to them are minimized and secondly technical and physical constraints are regarded. Because the optimal management of distribution networks is an optimization problem with continuous and discrete variables, the new evolutionary method based on Ant Colony Algorithm has been applied. The simulation results of the method tested on two cases containing 23 and 34 buses exist and will be shown at later sections.
Abstract: This paper presents the results of a comprehensive
investigation of five blackouts that occurred on 28 August to 8
September 2011 due to bushing failures of the 132/33 kV, 125 MVA
transformers at JBB Ali Grid station. The investigation aims to
explore the root causes of the bushing failures and come up with
recommendations that help in rectifying the problem and avoiding the
reoccurrence of similar type of incidents. The incident reports about
the failed bushings and the SCADA reports at this grid station were
examined and analyzed. Moreover, comprehensive power quality
field measurements at ten 33/11 kV substations (S/Ss) in JBB Ali
area were conducted, and frequency scans were performed to verify
any harmonic resonance frequencies due to power factor correction
capacitors. Furthermore, the daily operations of the on-load tap
changers (OLTCs) of both the 125 MVA and 20 MVA transformers
at JBB Ali Grid station have been analyzed. The investigation
showed that the five bushing failures were due to a local problem, i.e.
internal degradation of the bushing insulation. This has been
confirmed by analyzing the time interval between successive OLTC
operations of the faulty grid transformers. It was also found that
monitoring the number of OLTC operations can help in predicting
bushing failure.
Abstract: Since large power transformers are the most
expensive and strategically important components of any power
generator and transmission system, their reliability is crucially
important for the energy system operation. Also, Circuit breakers are
very important elements in the power transmission line so monitoring
the events gives a knowledgebase to determine time to the next
maintenance. This paper deals with the introduction of the
comparative method of the state estimation of transformers and
Circuit breakers using continuous monitoring of voltage, current.
This paper gives details a new method based on wavelet to apparatus
insulation monitoring. In this paper to insulation monitoring of
transformer, a new method based on wavelet transformation and
neutral point analysis is proposed. Using the EMTP tools, fault in
transformer winding and the detailed transformer winding model
were simulated. The current of neutral point of winding was analyzed
by wavelet transformation. It is shown that the neutral current of the
transformer winding has useful information about fault in insulation
of the transformer.