Abstract: Current transformers are an integral part of power
system because it provides a proportional safe amount of current for
protection and measurement applications. However, when the power
system experiences an abnormal situation leading to huge current
flow, then this huge current is proportionally injected to the
protection and metering circuit. Since the protection and metering
equipment’s are designed to withstand only certain amount of current
with respect to time, these high currents pose a risk to man and
equipment. Therefore, during such instances, the CT saturation
characteristics have a huge influence on the safety of both man and
equipment and on the reliability of the protection and metering
system. This paper shows the effect of burden on the Accuracy Limiting
factor/ Instrument security factor of current transformers and the
change in saturation characteristics of the CT’s. The response of the
CT to varying levels of overcurrent at different connected burden will
be captured using the data acquisition software LabVIEW. Analysis
is done on the real time data gathered using LabVIEW. Variation of
current transformer saturation characteristics with changes in burden
will be discussed.
Abstract: In insulation and cooling of power transformers
various liquids are used. Mineral oils have wide availability and low
cost. However, they have a poor biodegradability potential and lower
fire point in comparison with other insulating liquids. Use of a liquid
having high biodegradability is important due to environmental
consideration. This paper investigates edible corn oil as an alternative
to mineral oil. Various properties of mineral and corn oil like
breakdown voltage, dissipation factor, relative dielectric constant,
power loss and resistivity were measured according to different
standards.
Abstract: Efficient use of energy, the increase in demand of
energy and also with the reduction of natural energy sources, has
improved its importance in recent years. Most of the losses in the
system from electricity produced until the point of consumption is
mostly composed by the energy distribution system. In this study,
analysis of the resulting loss in power distribution transformer and
distribution power cable is realized which are most of the losses in
the distribution system. Transformer losses in the real distribution
system are analyzed by CYME Power Engineering Software
program. These losses are disclosed for different voltage levels and
different loading conditions.
Abstract: In this paper, influence of harmonics on medium
voltage distribution system of Bogazici Electricity Distribution Inc.
(BEDAS) which takes place at Istanbul/Turkey is investigated. A ring
network consisting of residential loads is taken into account for this
study. Real system parameters and measurement results are used for
simulations. Also, probable working conditions of the system are
analyzed for 50%, 75%, and 100% loading of transformers with
similar harmonic contents. Results of the study are exhibited the
influence of nonlinear loads on %THDV, P.F. and technical losses of
the medium voltage distribution system.
Abstract: This paper presents an application of Artificial Neural
Network (ANN) algorithm for improving power system voltage
stability. The training data is obtained by solving several normal and
abnormal conditions using the Linear Programming technique. The
selected objective function gives minimum deviation of the reactive
power control variables, which leads to the maximization of
minimum Eigen value of load flow Jacobian. The considered reactive
power control variables are switchable VAR compensators, OLTC
transformers and excitation of generators. The method has been
implemented on a modified IEEE 30-bus test system. The results
obtain from the test clearly show that the trained neural network is
capable of improving the voltage stability in power system with a
high level of precision and speed.
Abstract: The coaxial transformer-coupled push-pull circuitry
has been used widely in HF and VHF amplifiers for many decades
without significant changes in the topology of the transformers. Basic
changes over the years concerned the construction and turns ratio of
the transformers as has been imposed upon the newer technologies
active devices demands. The balun transmission line transformers
applied in push-pull amplifiers enable input/output impedance
transformation, but are mainly used to convert the balanced output
into unbalanced and the input unbalanced into balanced. A simple
and affordable alternative solution over the traditional coaxial
transformer is the coreless planar balun. A key advantage over the
traditional approach lies in the high specifications repeatability;
simplifying the amplifier construction requirements as the planar
balun constitutes an integrated part of the PCB copper layout. This
paper presents the performance analysis of a planar LDMOS
MRFE6VP5600 Push-Pull amplifier that enables robust operation in
Band III, DVB-T, DVB-T2 standards but functions equally well in
Band II, for DRM+ new generation transmitters.
Abstract: The power converter that feeds high-frequency, highvoltage
transformers must be carefully designed due to parasitic
components, mainly the secondary winding capacitance and the
leakage inductance, that introduces resonances in relatively lowfrequency
range, next to the switching frequency. This paper
considers applications in which the load (resistive) has an
unpredictable behavior, changing from open to short-circuit condition
faster than the output voltage control loop could react. In this context,
to avoid overvoltage and over current situations, that could damage
the converter, the transformer or the load, it is necessary to find an
operation point that assure the desired output voltage in spite of the
load condition. This can done adjusting the frequency response of the
transformer adding an external inductance, together with selecting the
switching frequency to get stable output voltage independently of the
load.
Abstract: Voltage sags are the most common power quality
disturbance in the distribution system. It occurs due to the fault in the
electrical network or by the starting of a large induction motor and
this can be solved by using the custom power devices such as
Dynamic Voltage Restorer (DVR). In this paper DVR is proposed to
compensate voltage sags on critical loads dynamically. The DVR
consists of VSC, injection transformers, passive filters and energy
storage (lead acid battery). By injecting an appropriate voltage, the
DVR restores a voltage waveform and ensures constant load voltage.
The simulation and experimental results of a DVR using MATLAB
software shows clearly the performance of the DVR in mitigating
voltage sags.
Abstract: Current transformers (CTs) are used to transform large primary currents to a small secondary current. Since most standard equipment’s are not designed to handle large primary currents the CTs have an important part in any electrical system for the purpose of Metering and Protection both of which are integral in Power system. Now a days due to advancement in solid state technology, the operation times of the protective relays have come to a few cycles from few seconds. Thus, in such a scenario it becomes important to study the transient response of the current transformers as it will play a vital role in the operating of the protective devices.
This paper shows the steady state and transient behavior of current transformers and how it changes with change in connected burden. The transient and steady state response will be captured using the data acquisition software LabVIEW. Analysis is done on the real time data gathered using LabVIEW. Variation of current transformer characteristics with changes in burden will be discussed.
Abstract: Time base maintenance (TBM) is conventionally applied by the power utilities to maintain circuit breakers (CBs), transformers, bus bars and cables, which may result in under maintenance or over maintenance. As information and communication technology (ICT) industry develops, the maintenance policies of many power utilities have gradually changed from TBM to condition base maintenance (CBM) to improve system operating efficiency, operation cost and power supply reliability. This paper discusses the feasibility of using intelligent electronic devices (IEDs) to construct a CB CBM management platform. CBs in power substations can be monitored using IEDs with additional logic configuration and wire connections. The CB monitoring data can be sent through intranet to a control center and be analyzed and integrated by the Elipse Power Studio software. Finally, a human-machine interface (HMI) of supervisory control and data acquisition (SCADA) system can be designed to construct a CBM management platform to provide maintenance decision information for the maintenance personnel, management personnel and CB manufacturers.
Abstract: Non-synchronous breakage or line failure in power
systems with light or no loads can lead to core saturation in
transformers or potential transformers. This can cause component and
capacitance matching resulting in the formation of resonant circuits,
which trigger ferroresonance. This study employed a wavelet
transform for the detection of ferroresonance. Simulation results
demonstrate the efficacy of the proposed method.
Abstract: This paper presents a nonparametric method to obtain the hazard rate “Bathtub curve” for power system components. The model is a mixture of the three known phases of a component life, the decreasing failure rate (DFR), the constant failure rate (CFR) and the increasing failure rate (IFR) represented by three parametric Weibull models. The parameters are obtained from a simultaneous fitting process of the model to the Kernel nonparametric hazard rate curve. From the Weibull parameters and failure rate curves the useful lifetime and the characteristic lifetime were defined. To demonstrate the model the historic time-to-failure of distribution transformers were used as an example. The resulted “Bathtub curve” shows the failure rate for the equipment lifetime which can be applied in economic and replacement decision models.
Abstract: This paper investigates the impact on operating time delay and relay maloperation when 1st,2nd and 3rd order analog antialiasing filters are used in numerical distance protection. RC filter with cut-off frequency 90 Hz is used. Simulations are carried out for different SIR (Source to line Impedance Ratio), load, fault type and fault conditions using SIMULINK, where the voltage and current signals are fed online to the developed numerical distance relay model. Matlab is used for plotting the impedance trajectory. Investigation results shows that, about 75 % of the simulated cases, numerical distance relay operating time is not increased even-though there is a time delay when higher order filters are used. Relay maloperation (selectivity) also reduces (increases) when higher order filters are used in numerical distance protection.
Abstract: This paper deals with design of walking beam pendel
axle suspension system. This axles and suspension systems are
mainly required for transportation of heavy duty and Over Dimension
Consignment (ODC) cargo, which is exceeding legal limit in terms of
length, width and height. Presently, in Indian transportation industry,
ODC movement growth rate has increased in transportation of bridge
sections (pre-cast beams), transformers, heavy machineries, boilers,
gas turbines, windmill blades etc. However, current Indian standard
road transport vehicles are facing lot of service and maintenance
issues due to non availability of suitable axle and suspension to carry
the ODC cargoes. This in turn will lead to increased number of road
accidents, bridge collapse and delayed deliveries, which finally result
in higher operating cost. Understanding these requirements, this work
was carried out. These axles and suspensions are designed for
optimum self – weight with maximum payload carrying capacity with
better road stability.
Abstract: Dissolved gas analysis has been accepted as a sensitive, informative and reliable technique for incipient faults detection in power transformers and is widely used. In the last few years this method, which has been recommended by IEEE Power & Energy society, has been applied for fault detection in load tap changers. Regarding the critical role of load tap changers in electrical network and essential of catastrophic failures prevention, it is necessary to choose "condition based preventative maintenance strategy" which leads to reduction in costs, the number of unnecessary visits as well as the probability of interruptions and also increment in equipment reliability. In current work, considering the condition based preventative maintenance strategy, condition assessment of an Elin tap changer was carried out using dissolved gas analysis.
Abstract: Power transformers are among the most important and
expensive equipments in the electric power systems. Consequently
the transformer protection is an essential part of the system
protection. This paper presents a new method for locating
transformer winding faults such as turn-to-turn, turn-to-core, turn-totransformer
body, turn-to-earth, and high voltage winding to low
voltage winding. In this study the current and voltage signals of input
and output terminals of the transformer are measured, which the
Fourier transform of measured signals and harmonic analysis
determine the fault's location.
Abstract: This paper deals with the effect of a power transformer’s vector group on the basic voltage sag characteristics during unbalanced faults at a meshed or radial power network. Specifically, the propagation of voltage sags through a power transformer is studied with advanced short-circuit analysis. A smart method to incorporate this effect on analytical mathematical expressions is proposed. Based on this methodology, the positive effect of transformers of certain vector groups on the mitigation of the expected number of voltage sags per year (sag frequency) at the terminals of critical industrial customers can be estimated.
Abstract: In this paper a three dimensional thermal model of a
power toroidal transformer is proposed for both steady-state or
transient conditions. The influence of electric current and ambient
temperature on the temperature distribution, has been investigated.
To validate the three dimensional thermal model, some experimental
tests have been done. There is a good correlation between
experimental and simulation results.
Abstract: Diagnostic goal of transformers in service is to detect the winding or the core in fault. Transformers are valuable equipment which makes a major contribution to the supply security of a power system. Consequently, it is of great importance to minimize the frequency and duration of unwanted outages of power transformers. So, Frequency Response Analysis (FRA) is found to be a useful tool for reliable detection of incipient mechanical fault in a transformer, by finding winding or core defects. The authors propose as first part of this article, the coupled circuits method, because, it gives most possible exhaustive modelling of transformers. And as second part of this work, the application of FRA in low frequency in order to improve and simplify the response reading. This study can be useful as a base data for the other transformers of the same categories intended for distribution grid.
Abstract: Insulation used in transformer is mostly oil pressboard insulation. Insulation failure is one of the major causes of catastrophic failure of transformers. It is established that partial discharges (PD) cause insulation degradation and premature failure of insulation. Online monitoring of PDs can reduce the risk of catastrophic failure of transformers. There are different techniques of partial discharge measurement like, electrical, optical, acoustic, opto-acoustic and ultra high frequency (UHF). Being non invasive and non interference prone, acoustic emission technique is advantageous for online PD measurement. Acoustic detection of p.d. is based on the retrieval and analysis of mechanical or pressure signals produced by partial discharges. Partial discharges are classified according to the origin of discharges. Their effects on insulation deterioration are different for different types. This paper reports experimental results and analysis for classification of partial discharges using acoustic emission signal of laboratory simulated partial discharges in oil pressboard insulation system using three different electrode systems. Acoustic emission signal produced by PD are detected by sensors mounted on the experimental tank surface, stored on an oscilloscope and fed to computer for further analysis. The measured AE signals are analyzed using discrete wavelet transform analysis and wavelet packet analysis. Energy distribution in different frequency bands of discrete wavelet decomposed signal and wavelet packet decomposed signal is calculated. These analyses show a distinct feature useful for PD classification. Wavelet packet analysis can sort out any misclassification arising out of DWT in most cases.