Abstract: The Gravity Recovery and Climate Experiment (GRACE) has been a very successful project in determining math redistribution within the Earth system. Large deformations caused by earthquakes are in the high frequency band. Unfortunately, GRACE is only capable to provide reliable estimate at the low-to-medium frequency band for the gravitational changes. In this study, we computed the gravity changes after the 2012 Mw8.6 Indian Ocean earthquake off-Sumatra using the GRACE Level-2 monthly spherical harmonic (SH) solutions released by the University of Texas Center for Space Research (UTCSR). Moreover, we calculated gravity changes using different fault models derived from teleseismic data. The model predictions showed non-negligible discrepancies in gravity changes. However, after removing high-frequency signals, using Gaussian filtering 350 km commensurable GRACE spatial resolution, the discrepancies vanished, and the spatial patterns of total gravity changes predicted from all slip models became similar at the spatial resolution attainable by GRACE observations, and predicted-gravity changes were consistent with the GRACE-detected gravity changes. Nevertheless, the fault models, in which give different slip amplitudes, proportionally lead to different amplitude in the predicted gravity changes.
Abstract: This paper presents the impact study of apparent
reactance injected by series Flexible AC Transmission System
(FACTS) i.e. Thyristor Controlled Series Reactor (TCSR) on the
measured impedance of a 400 kV single electrical transmission line
in the presence of phase to earth fault with fault resistance. The study
deals with an electrical transmission line of Eastern Algerian
transmission networks at Group Sonelgaz (Algerian Company of
Electrical and Gas) compensated by TCSR connected at midpoint of
the line. This compensator used to inject active and reactive powers
is controlled by three TCSR-s. The simulations results investigate the
impacts of the TCSR on the parameters of short circuit calculation
and parameters of measured impedance by distance relay in the
presence of earth fault for three cases study.