Abstract: This paper presents the impact study of apparent
reactance injected by series Flexible AC Transmission System
(FACTS) i.e. Thyristor Controlled Series Reactor (TCSR) on the
measured impedance of a 400 kV single electrical transmission line
in the presence of phase to earth fault with fault resistance. The study
deals with an electrical transmission line of Eastern Algerian
transmission networks at Group Sonelgaz (Algerian Company of
Electrical and Gas) compensated by TCSR connected at midpoint of
the line. This compensator used to inject active and reactive powers
is controlled by three TCSR-s. The simulations results investigate the
impacts of the TCSR on the parameters of short circuit calculation
and parameters of measured impedance by distance relay in the
presence of earth fault for three cases study.