Abstract: The most important parameter in transformers life
expectancy is the hot-spot temperature level which accelerates the
rate of aging of the insulation. The aim of this paper is to present
thermal models for transformers loaded at prefabricated MV/LV
transformer substations and outdoor situations. The hot-spot
temperature of transformers is studied using their top-oil temperature
rise models. The thermal models proposed for hot-spot and top-oil
temperatures of different operating situations are compared. Since the
thermal transfer is different for indoor and outdoor transformers
considering their operating conditions, their hot-spot thermal models
differ from each other. The proposed thermal models are verified by
the results obtained from the experiments carried out on a typical
1600 kVA, 30 /0.4 kV, ONAN transformer for both indoor and
outdoor situations.