Abstract: This paper presents the experimental results on
artificial ageing test of 22 kV XLPE cable for distribution system
application in Thailand. XLPE insulating material of 22 kV cable
was sliced to 60-70 μm in thick and was subjected to ac high voltage
at 23
Ôùª
C, 60
Ôùª
C and 75
Ôùª
C. Testing voltage was constantly applied to
the specimen until breakdown. Breakdown voltage and time to
breakdown were used to evaluate life time of insulating material.
Furthermore, the physical model by J. P. Crine for predicts life time
of XLPE insulating material was adopted as life time model and was
calculated in order to compare the experimental results. Acceptable
life time results were obtained from Crine-s model comparing with
the experimental result. In addition, fourier transform infrared
spectroscopy (FTIR) for chemical analysis and scanning electron
microscope (SEM) for physical analysis were conducted on tested
specimens.
Abstract: The paper presents dynamic programming based model as a planning tool for the maintenance of electric power systems. Every distribution component has an exponential age depending reliability function to model the fault risk. In the moment of time when the fault costs exceed the investment costs of the new component the reinvestment of the component should be made. However, in some cases the overhauling of the old component may be more economical than the reinvestment. The comparison between overhauling and reinvestment is made by optimisation process. The goal of the optimisation process is to find the cost minimising maintenance program for electric power distribution system.
Abstract: This paper presents a novel control strategy of a threephase
four-wire Unified Power Quality (UPQC) for an improvement
in power quality. The UPQC is realized by integration of series and
shunt active power filters (APFs) sharing a common dc bus capacitor.
The shunt APF is realized using a thee-phase, four leg voltage source
inverter (VSI) and the series APF is realized using a three-phase,
three leg VSI. A control technique based on unit vector template
technique (UTT) is used to get the reference signals for series APF,
while instantaneous sequence component theory (ISCT) is used for
the control of Shunt APF. The performance of the implemented
control algorithm is evaluated in terms of power-factor correction,
load balancing, neutral source current mitigation and mitigation of
voltage and current harmonics, voltage sag and swell in a three-phase
four-wire distribution system for different combination of linear and
non-linear loads. In this proposed control scheme of UPQC, the
current/voltage control is applied over the fundamental supply
currents/voltages instead of fast changing APFs currents/voltages,
there by reducing the computational delay and the required sensors.
MATLAB/Simulink based simulations are obtained, which support
the functionality of the UPQC. MATLAB/Simulink based
simulations are obtained, which support the functionality of the
UPQC.
Abstract: Distributed Generation (DG) in the form of renewable
power generation systems is currently preferred for clean power
generation. It has a significant impact on the distribution systems.
This impact may be either positively or negatively depending on the
distribution system, distributed generator and load characteristics. In
this works, an overview of DG is briefly introduced. The technology
of DG is also listed while the technical impacts and economic
impacts are explained.