Abstract: The Indian subcontinent is facing a massive challenge with regards to energy security in its member countries; to provide reliable electricity to facilitate development across various sectors of the economy and consequently achieve the developmental targets. The instability of the current precarious situation is observable in the frequent system failures and blackouts.
The deployment of interconnected electricity ‘Supergrid’ designed to carry huge quanta of power across the Indian sub-continent is proposed in this paper. Not only enabling energy security in the subcontinent it will also provide a platform for Renewable Energy Sources (RES) integration. This paper assesses the need and conditions for a Supergrid deployment and consequently proposes a meshed topology based on Voltage Source High Voltage Direct Current (VSC- HVDC) converters for the Supergrid modeling. Various control schemes for the control of voltage and power are utilized for the regulation of the network parameters. A 3 terminal Multi Terminal Direct Current (MTDC) network is used for the simulations.
Abstract: The Indian subcontinent is facing a massive challenge with regards to the energy security in member countries, i.e. providing a reliable source of electricity to facilitate development across various sectors of the economy and thereby achieve the developmental targets it has set for itself. A highly precarious situation exists in the subcontinent which is observed in the series of system failures which most of the times leads to system collapses-blackouts. To mitigate the issues related with energy security as well as keep in check the increasing supply demand gap, a possible solution that stands in front of the subcontinent is the deployment of an interconnected electricity ‘Supergrid’ designed to carry huge quanta of power across the sub continent as well as provide the infra structure for RES integration. This paper assesses the need and conditions for a Supergrid deployment and consequently proposes a meshed topology based on VSC HVDC converters for the Supergrid modeling.
Abstract: There is a variety of inconsistencies in the differences
in alcohol use and related problems between male and female
genders. This study was aimed at analyzing the gender differences in
alcohol use and related problems among university students in
Minsk, Belarus. A total of 465 male (average age of 21) and 1030
female (average age of 20.5) students from four major universities in
Minsk, Belarus were administered WHO recommended standardized
screening instruments – AUDIT, MAST, CAGE questionnaire, as
well as other alcohol related questions. The male to female ratio for
the prevalence of alcohol problems according to the AUDIT was
3.34, while the ratio for alcohol users was 0.97. There are a wide
gender differences in the pattern of alcohol use and preference for
different alcoholic beverages, cause for drinking, and other alcohol
related problems like injuries and blackouts.
Abstract: In this paper an analysis of blackouts in electric power
transmission systems is implemented using a model and studied in
simple networks with a regular topology. The proposed model
describes load demand and network improvements evolving on a
slow timescale as well as the fast dynamics of cascading overloads
and outages.
Abstract: Voltage collapse is instability of heavily loaded electric
power systems that cause to declining voltages and blackout. Power
systems are predicated to become more heavily loaded in the future
decade as the demand for electric power rises while economic and
environmental concerns limit the construction of new transmission
and generation capacity. Heavily loaded power systems are closer to
their stability limits and voltage collapse blackouts will occur if
suitable monitoring and control measures are not taken. To control
transmission lines, it can be used from FACTS devices.
In this paper Harmony search algorithm (HSA) and Genetic
Algorithm (GA) have applied to determine optimal location of
FACTS devices in a power system to improve power system stability.
Three types of FACTS devices (TCPAT, UPFS, and SVC) have been
introduced. Bus under voltage has been solved by controlling reactive
power of shunt compensator. Also a combined series-shunt
compensators has been also used to control transmission power flow
and bus voltage simultaneously.
Different scenarios have been considered. First TCPAT, UPFS, and
SVC are placed solely in transmission lines and indices have been
calculated. Then two types of above controller try to improve
parameters randomly. The last scenario tries to make better voltage
stability index and losses by implementation of three types controller
simultaneously. These scenarios are executed on typical 34-bus test
system and yields efficiency in improvement of voltage profile and
reduction of power losses; it also may permit an increase in power
transfer capacity, maximum loading, and voltage stability margin.
Abstract: This paper introduces a temporal epistemic logic
CBCTL that updates agent-s belief states through communications
in them, based on computational tree logic (CTL). In practical
environments, communication channels between agents may not be
secure, and in bad cases agents might suffer blackouts. In this study,
we provide inform* protocol based on ACL of FIPA, and declare the
presence of secure channels between two agents, dependent on time.
Thus, the belief state of each agent is updated along with the progress
of time. We show a prover, that is a reasoning system for a given
formula in a given a situation of an agent ; if it is directly provable
or if it could be validated through the chains of communications, the
system returns the proof.
Abstract: This paper presents the results of a comprehensive
investigation of five blackouts that occurred on 28 August to 8
September 2011 due to bushing failures of the 132/33 kV, 125 MVA
transformers at JBB Ali Grid station. The investigation aims to
explore the root causes of the bushing failures and come up with
recommendations that help in rectifying the problem and avoiding the
reoccurrence of similar type of incidents. The incident reports about
the failed bushings and the SCADA reports at this grid station were
examined and analyzed. Moreover, comprehensive power quality
field measurements at ten 33/11 kV substations (S/Ss) in JBB Ali
area were conducted, and frequency scans were performed to verify
any harmonic resonance frequencies due to power factor correction
capacitors. Furthermore, the daily operations of the on-load tap
changers (OLTCs) of both the 125 MVA and 20 MVA transformers
at JBB Ali Grid station have been analyzed. The investigation
showed that the five bushing failures were due to a local problem, i.e.
internal degradation of the bushing insulation. This has been
confirmed by analyzing the time interval between successive OLTC
operations of the faulty grid transformers. It was also found that
monitoring the number of OLTC operations can help in predicting
bushing failure.
Abstract: This paper proposes a methodology for mitigating the occurrence of cascading failure in stressed power systems. The methodology is essentially based on predicting voltage instability in the power system using a voltage stability index and then devising a corrective action in order to increase the voltage stability margin. The paper starts with a brief description of the cascading failure mechanism which is probable root cause of severe blackouts. Then, the voltage instability indices are introduced in order to evaluate stability limit. The aim of the analysis is to assure that the coordination of protection, by adopting load shedding scheme, capable of enhancing performance of the system after the major location of instability is determined. Finally, the proposed method to generate instability prediction is introduced.