Abstract: This paper aims to give a full study of the dynamic
behavior of a mono-phase active power filter. First, the principle of
the parallel active power filter will be introduced. Then, a
dimensioning procedure for all its components will be explained in
detail, such as the input filter, the current and voltage controllers.
This active power filter is simulated using OrCAD program showing
the validity of the theoretical study.
Abstract: In this paper the reference current for Voltage Source
Converter (VSC) of the Shunt Active Power Filter (SAPF) is
generated using Synchronous Reference Frame method,
incorporating the PI controller with anti-windup scheme. The
proposed method improves the harmonic filtering by compensating
the winding up phenomenon caused by the integral term of the PI
controller.
Using Reference Frame Transformation, the current is transformed
from om a - b - c stationery frame to rotating 0 - d - q frame. Using
the PI controller, the current in the 0 - d - q frame is controlled to
get the desired reference signal. A controller with integral action
combined with an actuator that becomes saturated can give some
undesirable effects. If the control error is so large that the integrator
saturates the actuator, the feedback path becomes ineffective because
the actuator will remain saturated even if the process output changes.
The integrator being an unstable system may then integrate to a very
large value, the phenomenon known as integrator windup.
Implementing the integrator anti-windup circuit turns off the
integrator action when the actuator saturates, hence improving the
performance of the SAPF and dynamically compensating harmonics
in the power network. In this paper the system performance is
examined with Shunt Active Power Filter simulation model.
Abstract: This paper aims to present the reviews of the
application of neural network in shunt active power filter (SAPF).
From the review, three out of four components of SAPF structure,
which are harmonic detection component, compensating current
control, and DC bus voltage control, have been adopted some of
neural network architecture as part of its component or even
substitution. The objectives of most papers in using neural network in
SAPF are to increase the efficiency, stability, accuracy, robustness,
tracking ability of the systems of each component. Moreover,
minimizing unneeded signal due to the distortion is the ultimate goal
in applying neural network to the SAPF. The most famous
architecture of neural network in SAPF applications are ADALINE
and Backpropagation (BP).
Abstract: This paper presents the mathematical model and
control strategy on DQ frame of shunt active power filter. The
structure of the shunt active power filter is the voltage source inverter
(VSI). The pulse width modulation (PWM) with PI controller is used
in the paper. The concept of DQ frame to apply with the shunt active
power filter is described. Moreover, the detail of the PI controller
design for two current loops and one voltage loop are fully explained.
The DQ axis with Fourier (DQF) method is applied to calculate the
reference currents on DQ frame. The simulation results show that the
control strategy and the design method presented in the paper can
provide the good performance of the shunt active power filter.
Moreover, the %THD of the source currents after compensation can
follow the IEEE Std.519-1992.
Abstract: This paper proposes a three-phase four-wire currentcontrolled
Voltage Source Inverter (CC-VSI) for both power quality
improvement and PV energy extraction. For power quality
improvement, the CC-VSI works as a grid current-controlling shunt
active power filter to compensate for harmonic and reactive power of
loads. Then, the PV array is coupled to the DC bus of the CC-VSI
and supplies active power to the grid. The MPPT controller employs
the particle swarm optimization technique. The output of the MPPT
controller is a DC voltage that determines the DC-bus voltage
according to PV maximum power. The PSO method is simple and
effective especially for a partially shaded PV array. From computer
simulation results, it proves that grid currents are sinusoidal and inphase
with grid voltages, while the PV maximum active power is
delivered to loads.
Abstract: The paper deals with the comparison study of
harmonic detection methods for a shunt active power filter. The
%THD and the power factor value at the PCC point after
compensation are considered for the comparison. There are three
harmonic detection methods used in the paper that are synchronous
reference frame method, synchronous detection method, and DQ axis
with Fourier method. In addition, the ideal current source is used to
represent the active power filter by assuming an infinitely fast
controller action of the active power filter. The simulation results
show that the DQ axis with Fourier method provides the minimum
%THD after compensation compared with other methods. However,
the power factor value at the PCC point after compensation is slightly
lower than that of synchronous detection method.
Abstract: The proper selection of the AC-side passive filter
interconnecting the voltage source converter to the power supply is
essential to obtain satisfactory performances of an active power filter
system. The use of the LCL-type filter has the advantage of
eliminating the high frequency switching harmonics in the current
injected into the power supply. This paper is mainly focused on
analyzing the influence of the interface filter parameters on the active
filtering performances. Some design aspects are pointed out. Thus,
the design of the AC interface filter starts from transfer functions by
imposing the filter performance which refers to the significant current
attenuation of the switching harmonics without affecting the
harmonics to be compensated. A Matlab/Simulink model of the entire
active filtering system including a concrete nonlinear load has been
developed to examine the system performances. It is shown that a
gamma LC filter could accomplish the attenuation requirement of the
current provided by converter. Moreover, the existence of an optimal
value of the grid-side inductance which minimizes the total harmonic
distortion factor of the power supply current is pointed out.
Nevertheless, a small converter-side inductance and a damping
resistance in series with the filter capacitance are absolutely needed
in order to keep the ripple and oscillations of the current at the
converter side within acceptable limits. The effect of change in the
LCL-filter parameters is evaluated. It is concluded that good active
filtering performances can be achieved with small values of the
capacitance and converter-side inductance.
Abstract: This paper presents a novel control strategy of a threephase
four-wire Unified Power Quality (UPQC) for an improvement
in power quality. The UPQC is realized by integration of series and
shunt active power filters (APFs) sharing a common dc bus capacitor.
The shunt APF is realized using a thee-phase, four leg voltage source
inverter (VSI) and the series APF is realized using a three-phase,
three leg VSI. A control technique based on unit vector template
technique (UTT) is used to get the reference signals for series APF,
while instantaneous sequence component theory (ISCT) is used for
the control of Shunt APF. The performance of the implemented
control algorithm is evaluated in terms of power-factor correction,
load balancing, neutral source current mitigation and mitigation of
voltage and current harmonics, voltage sag and swell in a three-phase
four-wire distribution system for different combination of linear and
non-linear loads. In this proposed control scheme of UPQC, the
current/voltage control is applied over the fundamental supply
currents/voltages instead of fast changing APFs currents/voltages,
there by reducing the computational delay and the required sensors.
MATLAB/Simulink based simulations are obtained, which support
the functionality of the UPQC. MATLAB/Simulink based
simulations are obtained, which support the functionality of the
UPQC.