Abstract: This paper presents the mathematical model and
control strategy on DQ frame of shunt active power filter. The
structure of the shunt active power filter is the voltage source inverter
(VSI). The pulse width modulation (PWM) with PI controller is used
in the paper. The concept of DQ frame to apply with the shunt active
power filter is described. Moreover, the detail of the PI controller
design for two current loops and one voltage loop are fully explained.
The DQ axis with Fourier (DQF) method is applied to calculate the
reference currents on DQ frame. The simulation results show that the
control strategy and the design method presented in the paper can
provide the good performance of the shunt active power filter.
Moreover, the %THD of the source currents after compensation can
follow the IEEE Std.519-1992.
Abstract: The paper deals with the comparison study of
harmonic detection methods for a shunt active power filter. The
%THD and the power factor value at the PCC point after
compensation are considered for the comparison. There are three
harmonic detection methods used in the paper that are synchronous
reference frame method, synchronous detection method, and DQ axis
with Fourier method. In addition, the ideal current source is used to
represent the active power filter by assuming an infinitely fast
controller action of the active power filter. The simulation results
show that the DQ axis with Fourier method provides the minimum
%THD after compensation compared with other methods. However,
the power factor value at the PCC point after compensation is slightly
lower than that of synchronous detection method.