Abstract: In this paper, monitoring and control of tap changer
mechanism of a transformer implementation in an Intelligent
Electronic Device (IED) is discussed. It has been a custom for
decades to provide a separate panel for on load tap changer control
for monitoring the tap position. However, this facility cannot either
record or transfer the information to remote control centers. As there
is a technology shift towards the smart grid protection and control
standards, the need for implementing remote control and monitoring
has necessitated the implementation of this feature in numerical
relays. This paper deals with the programming, settings and logic
implementation which is applicable to both IEC 61850 compatible
and non-compatible IEDs thereby eliminating the need for separate
tap changer control equipment. The monitoring mechanism has been
implemented in a 28MVA, 110 /6.9kV transformer with 16 tap
position with GE make T60 IED at Ultratech cement limited
Gulbarga, Karnataka and is in successful service.
Abstract: This paper discusses the implementation of a fuzzy logic based coordinated voltage control for a distribution system connected with distributed generations (DGs). The connection of DGs has created a challenge for the distribution network operators to keep the voltage in the system within its acceptable limits. Intelligent centralized or coordinated voltage control schemes have proven to be more reliable due to its ability to provide more control and coordination with the communication with other network devices. In this work, voltage control using fuzzy logic by coordinating three methods of control, power factor control, on load tap changer and generation curtailment is implemented on a distribution network test system. The results show that the fuzzy logic based coordination is able to keep the voltage within its allowable limits.