Abstract: The proper selection of the AC-side passive filter
interconnecting the voltage source converter to the power supply is
essential to obtain satisfactory performances of an active power filter
system. The use of the LCL-type filter has the advantage of
eliminating the high frequency switching harmonics in the current
injected into the power supply. This paper is mainly focused on
analyzing the influence of the interface filter parameters on the active
filtering performances. Some design aspects are pointed out. Thus,
the design of the AC interface filter starts from transfer functions by
imposing the filter performance which refers to the significant current
attenuation of the switching harmonics without affecting the
harmonics to be compensated. A Matlab/Simulink model of the entire
active filtering system including a concrete nonlinear load has been
developed to examine the system performances. It is shown that a
gamma LC filter could accomplish the attenuation requirement of the
current provided by converter. Moreover, the existence of an optimal
value of the grid-side inductance which minimizes the total harmonic
distortion factor of the power supply current is pointed out.
Nevertheless, a small converter-side inductance and a damping
resistance in series with the filter capacitance are absolutely needed
in order to keep the ripple and oscillations of the current at the
converter side within acceptable limits. The effect of change in the
LCL-filter parameters is evaluated. It is concluded that good active
filtering performances can be achieved with small values of the
capacitance and converter-side inductance.
Abstract: This paper present a MATLAB-SIMULINK model of a single phase 2.5 KVA, 240V RMS controlled PV VSI (Photovoltaic Voltage Source Inverter) inverter using IGBTs (Insulated Gate Bipolar Transistor). The behavior of output voltage, output current, and the total harmonic distortion (THD), with the variation in input dc blocking capacitor (Cdc), for linear and non-linear load has been analyzed. The values of Cdc as suggested by the other authors in their papers are not clearly defined and it poses difficulty in selecting the proper value. As the dc power stored in Cdc, (generally placed parallel with battery) is used as input to the VSI inverter. The simulation results shows the variation in the output voltage and current with different values of Cdc for linear and non-linear load connected at the output side of PV VSI inverter and suggest the selection of suitable value of Cdc.