Abstract: In this paper, various methods of providing restricted
earth fault protection are discussed. The proper operation of high and
low impedance Restricted Earth Fault (REF) protection for various
applications has been discussed. The maloperation of a relay due to
improper placement of CTs has been identified and a simple/unique
solution has been proposed in this work with a case study. Moreover,
it is found that the proper placement of CT in high impedance method
will provide the same result with reduced CT. This methodology has
been successfully implemented in Al Takreer refinery for a 2000
KVA transformer. The outcome of the paper may be included in
IEEEC37.91 standard to give the proper guidance for protection
engineers to sort out the issues related to mal functioning of REF
relays.
Abstract: This paper investigates the impact on operating time delay and relay maloperation when 1st,2nd and 3rd order analog antialiasing filters are used in numerical distance protection. RC filter with cut-off frequency 90 Hz is used. Simulations are carried out for different SIR (Source to line Impedance Ratio), load, fault type and fault conditions using SIMULINK, where the voltage and current signals are fed online to the developed numerical distance relay model. Matlab is used for plotting the impedance trajectory. Investigation results shows that, about 75 % of the simulated cases, numerical distance relay operating time is not increased even-though there is a time delay when higher order filters are used. Relay maloperation (selectivity) also reduces (increases) when higher order filters are used in numerical distance protection.