Abstract: The reliability of the power grid depends on the successful operation of thousands of protective relays. The failure of one relay to operate as intended may lead the entire power grid to blackout. In fact, major power system failures during transient disturbances may be caused by unnecessary protective relay tripping rather than by the failure of a relay to operate. Adequate relay testing provides a first defense against false trips of the relay and hence improves power grid stability and prevents catastrophic bulk power system failures. The goal of this research project is to design and enhance the relay tester using a technology such as Field Programmable Gate Array (FPGA) card NI 7851. A PC based tester framework has been developed using Simulink power system model for generating signals under different conditions (faults or transient disturbances) and LabVIEW for developing the graphical user interface and configuring the FPGA. Besides, the interface system has been developed for outputting and amplifying the signals without distortion. These signals should be like the generated ones by the real power system and large enough for testing the relay’s functionality. The signals generated that have been displayed on the scope are satisfactory. Furthermore, the proposed testing system can be used for improving the performance of protective relay.
Abstract: Current transformers (CTs) are used to transform large primary currents to a small secondary current. Since most standard equipment’s are not designed to handle large primary currents the CTs have an important part in any electrical system for the purpose of Metering and Protection both of which are integral in Power system. Now a days due to advancement in solid state technology, the operation times of the protective relays have come to a few cycles from few seconds. Thus, in such a scenario it becomes important to study the transient response of the current transformers as it will play a vital role in the operating of the protective devices.
This paper shows the steady state and transient behavior of current transformers and how it changes with change in connected burden. The transient and steady state response will be captured using the data acquisition software LabVIEW. Analysis is done on the real time data gathered using LabVIEW. Variation of current transformer characteristics with changes in burden will be discussed.
Abstract: In power systems, protective relays must filter their
inputs to remove undesirable quantities and retain signal quantities of
interest. This job must be performed accurate and fast. A new
method for filtering the undesirable components such as DC and
harmonic components associated with the fundamental system
signals. The method is s based on a dynamic filtering algorithm. The
filtering algorithm has many advantages over some other classical
methods. It can be used as dynamic on-line filter without the need of
parameters readjusting as in the case of classic filters. The proposed
filter is tested using different signals. Effects of number of samples
and sampling window size are discussed. Results obtained are
presented and discussed to show the algorithm capabilities.
Abstract: Protective relays are components of a protection system
in a power system domain that provides decision making element for
correct protection and fault clearing operations. Failure of the
protection devices may reduce the integrity and reliability of the power
system protection that will impact the overall performance of the
power system. Hence it is imperative for power utilities to assess the
reliability of protective relays to assure it will perform its intended
function without failure. This paper will discuss the application of
reliability analysis using statistical method called Life Data Analysis
in Tenaga Nasional Berhad (TNB), a government linked power utility
company in Malaysia, namely Transmission Division, to assess and
evaluate the reliability of numerical overcurrent protective relays from
two different manufacturers.
Abstract: Directional over current relays (DOCR) are commonly used in power system protection as a primary protection in distribution and sub-transmission electrical systems and as a secondary protection in transmission systems. Coordination of protective relays is necessary to obtain selective tripping. In this paper, an approach for efficiency reduction of DOCRs nonlinear optimum coordination (OC) is proposed. This was achieved by modifying the objective function and relaxing several constraints depending on the four constraints classification, non-valid, redundant, pre-obtained and valid constraints. According to this classification, the far end fault effect on the objective function and constraints, and in consequently on relay operating time, was studied. The study was carried out, firstly by taking into account the near-end and far-end faults in DOCRs coordination problem formulation; and then faults very close to the primary relays (nearend faults). The optimal coordination (OC) was achieved by simultaneously optimizing all variables (TDS and Ip) in nonlinear environment by using of Genetic algorithm nonlinear programming techniques. The results application of the above two approaches on 6-bus and 26-bus system verify that the far-end faults consideration on OC problem formulation don-t lose the optimality.