Abstract: In this paper, monitoring and control of tap changer
mechanism of a transformer implementation in an Intelligent
Electronic Device (IED) is discussed. It has been a custom for
decades to provide a separate panel for on load tap changer control
for monitoring the tap position. However, this facility cannot either
record or transfer the information to remote control centers. As there
is a technology shift towards the smart grid protection and control
standards, the need for implementing remote control and monitoring
has necessitated the implementation of this feature in numerical
relays. This paper deals with the programming, settings and logic
implementation which is applicable to both IEC 61850 compatible
and non-compatible IEDs thereby eliminating the need for separate
tap changer control equipment. The monitoring mechanism has been
implemented in a 28MVA, 110 /6.9kV transformer with 16 tap
position with GE make T60 IED at Ultratech cement limited
Gulbarga, Karnataka and is in successful service.
Abstract: Non-synchronous breakage or line failure in power
systems with light or no loads can lead to core saturation in
transformers or potential transformers. This can cause component and
capacitance matching resulting in the formation of resonant circuits,
which trigger ferroresonance. This study employed a wavelet
transform for the detection of ferroresonance. Simulation results
demonstrate the efficacy of the proposed method.