Abstract: This paper presents the experimental results on
artificial ageing test of 22 kV XLPE cable for distribution system
application in Thailand. XLPE insulating material of 22 kV cable
was sliced to 60-70 μm in thick and was subjected to ac high voltage
at 23
Ôùª
C, 60
Ôùª
C and 75
Ôùª
C. Testing voltage was constantly applied to
the specimen until breakdown. Breakdown voltage and time to
breakdown were used to evaluate life time of insulating material.
Furthermore, the physical model by J. P. Crine for predicts life time
of XLPE insulating material was adopted as life time model and was
calculated in order to compare the experimental results. Acceptable
life time results were obtained from Crine-s model comparing with
the experimental result. In addition, fourier transform infrared
spectroscopy (FTIR) for chemical analysis and scanning electron
microscope (SEM) for physical analysis were conducted on tested
specimens.
Abstract: When a high DC voltage is applied to a capacitor with
strongly asymmetrical electrodes, it generates a mechanical force that
affects the whole capacitor. This is caused by the motion of ions generated around the smaller of the two electrodes and their subsequent interaction with the surrounding medium. If one of the electrodes is heated, it changes the conditions around the capacitor
and influences the process of ionisation, thus changing the value of the generated force. This paper describes these changes and gives
reasons behind them. Further the experimental results are given as proof of the ionic mechanism of the phenomenon.
Abstract: The prologue of new High Voltage (HV) transmission
mains into the community necessitates earthing design to ensure
safety compliance of the system. Conductive structures such as steel
or concrete poles are widely used in HV transmission mains. The
earth potential rise (EPR) generated by a fault on these structures
could result to an unsafe condition. This paper discusses information
on the input impedance of the over head earth wire (OHEW) system
for finite and infinite transmission mains. The definition of finite and
infinite system is discussed, maximum EPR due to pole fault. The
simplified equations for EPR assessments are introduced and
discussed for the finite and infinite conditions. A case study is also
shown.