Abstract: Anaerobic treatment has many advantages over other
biological method particularly when used to treat complex
wastewater such as petroleum refinery wastewater. In this study two
Up-flow Anaerobic Sludge Blanket (UASB) reactors were operated
in parallel to treat six volumetric organic loads (0.58, 1.21, 0.89,
2.34, 1.47 and 4.14 kg COD/m3·d) to evaluate the chemical oxygen
demand (COD) removal efficiency. The reactors were continuously
adapting to the changing of operation condition with increase in the
removal efficiency or slight decrease until the last load which was
more than two times the load, at which the reactor stressed and the
removal efficiency decreased to 75% with effluent concentration of
1746 mg COD/L. Other parameters were also monitored such as pH,
alkalinity, volatile fatty acid and gas production rate. The UASB
reactor was suitable to treat petroleum refinery wastewater and the
highest COD removal rate was 83% at 1215 kg/m3·d with COD
concentration about 356 mg/L in the effluent.
Abstract: An experimental study of anaerobic treatment was performed by hybrid upflow anaerobic sludge blanket (HUASB) reactor to treat produced water (PW) of an onshore crude oil terminal (COD: 1597 mg/L, NH3-N: 14.7 mg/L, phenol: 13.8 mg/L, BOD5: 862 mg/L, sodium: 6240 mg/L and chloride 9530 mg/L). The produced water with high salinity and other toxic substances will inhibit the methanogens performance if there is no adaptation on biomass before anaerobic digestion. COD removal from produced water was investigated at five different dilutions of produced water and tap water (TW) without any nutrient addition and pre-treatment. The dilution ratios were 1PW:4TW, 2PW:3TW, 3PW:2TW, 4PW:1TW and 5PW:0TW. The reactor was evaluated at mesophilic operating condition (35 ± 2 °C) at 5 days of HRT for 250 days continuous feed. The average COD removals for 1PW:4TW, 2PW:3TW, 3PW:2TW, 4PW:1TW and 5PW:0TW were found to be approximately 76.1%, 73.8%, 70.3%, 46.3% and 61.82% respectively, with final average effluent COD of 123.7 mg/L, 240 mg/L, 294 mg/L, 589 mg/L and 738 mg/L, respectively.
Abstract: Water hyacinth has been used in aquatic systems for
wastewater purification in many years worldwide. The role of water
hyacinth (Eichhornia crassipes) species in polishing nitrate and
phosphorus concentration from municipal wastewater treatment plant
effluent by phytoremediation method was evaluated. The objective
of this project is to determine the removal efficiency of water
hyacinth in polishing nitrate and phosphorus, as well as chemical
oxygen demand (COD) and ammonia. Water hyacinth is considered
as the most efficient aquatic plant used in removing vast range of
pollutants such as organic matters, nutrients and heavy metals. Water
hyacinth, also referred as macrophytes, were cultivated in the
treatment house in a reactor tank of approximately 90(L) x 40(W) x
25(H) in dimension and built with three compartments. Three water
hyacinths were placed in each compartments and water sample in
each compartment were collected in every two days. The plant
observation was conducted by weight measurement, plant uptake and
new young shoot development. Water hyacinth effectively removed
approximately 49% of COD, 81% of ammonia, 67% of phosphorus
and 92% of nitrate. It also showed significant growth rate at starting
from day 6 with 0.33 shoot/day and they kept developing up to 0.38
shoot/day at the end of day 24. From the studies conducted, it was
proved that water hyacinth is capable of polishing the effluent of
municipal wastewater which contains undesirable amount of nitrate
and phosphorus concentration.