Abstract: Thermal water hammer is a special type of water
hammer which rarely occurs in heat exchangers. In biphasic fluids, if
steam bubbles are surrounded by condensate, regarding lower
condensate temperature than steam, they will suddenly collapse. As a
result, the vacuum caused by an extreme change in volume lead to
movement of the condensates in all directions and their collision the
force produced by this collision leads to a severe stress in the pipe
wall. This phenomenon is a special type of water hammer. According
to fluid mechanics, this phenomenon is a particular type of transient
flows during which abrupt change of fluid leads to sudden pressure
change inside the tube. In this paper, the mechanism of abrupt failure
of 80 tubes of 481 tubes of a methanol heat exchanger is discussed.
Initially, due to excessive temperature differences between heat
transfer fluids and simultaneous failure of 80 tubes, thermal shock
was presupposed as the reason of failure. Deeper investigation on
cross-section of failed tubes showed that failure was, ductile type of
failure, so the first hypothesis was rejected. Further analysis and more
accurate experiments revealed that failure of tubes caused by thermal
water hammer. Finally, the causes of thermal water hammer and
various solutions to avoid such mechanism are discussed.
Abstract: Facing the concern of the population to its environment and to climatic change, city planners are now considering the urban climate in their choices of planning. The urban climate, representing different urban morphologies across central Bangkok metropolitan area (BMA), are used to investigates the effects of both the composition and configuration of variables of urban morphology indicators on the summer diurnal range of urban climate, using correlation analyses and multiple linear regressions. Results show first indicate that approximately 92.6% of the variation in the average maximum daytime near-surface air temperature (Ta) was explained jointly by the two composition variables of urban morphology indicators including open space ratio (OSR) and floor area ratio (FAR). It has been possible to determine the membership of sample areas to the local climate zones (LCZs) using these urban morphology descriptors automatically computed with GIS and remote sensed data. Finally result found the temperature differences among zones of large separation, such as the city center could be respectively from 35.48±1.04ºC (Mean±S.D.) warmer than the outskirt of Bangkok on average for maximum daytime near surface temperature to 28.27±0.21ºC for extreme event and, can exceed as 8ºC. A spatially disaggregation of urban thermal responsiveness map would be helpful for several reasons. First, it would localize urban areas concerned by different climate behavior over summer daytime and be a good indicator of urban climate variability. Second, when overlaid with a land cover map, this map may contribute to identify possible urban management strategies to reduce heat wave effects in BMA.
Abstract: The present work deals with thermodynamic analysis
of cascade refrigeration system using ozone friendly refrigerants pair
R507A and R23. R507A is azeotropic mixture composed of HFC
refrigerants R125/R143a (50%/50% wt.). R23 is a single component
HFC refrigerant used as replacement to CFC refrigerant R13 in low
temperature applications. These refrigerants have zero ozone
depletion potential and are non-flammable and as R507A an
azeotropic mixture there is no problem of temperature glide. This
study thermodynamically analyzed R507A-R23 cascade refrigeration
system to optimize the design and operating parameters of the
system. The design and operating parameters include: Condensing,
evaporating, subcooling and superheating temperatures in the high
temperature circuit, temperature difference in the cascade heat
exchanger, Condensing, evaporating, subcooling and superheating
temperatures in the low temperature circuit.
Abstract: This study investigated climatic factors associated
with influenza cases in Southern Thailand. The main aim for use
regression analysis to investigate possible causual relationship of
climatic factors and variability between the border of the Andaman
Sea and the Gulf of Thailand. Southern Thailand had the highest
Influenza incidences among four regions (i.e. north, northeast, central
and southern Thailand). In this study, there were 14 climatic factors:
mean relative humidity, maximum relative humidity, minimum
relative humidity, rainfall, rainy days, daily maximum rainfall,
pressure, maximum wind speed, mean wind speed, sunshine duration,
mean temperature, maximum temperature, minimum temperature,
and temperature difference (i.e. maximum – minimum temperature).
Multiple stepwise regression technique was used to fit the statistical
model. The results indicated that the mean wind speed and the
minimum relative humidity were positively associated with the
number of influenza cases on the Andaman Sea side. The maximum
wind speed was positively associated with the number of influenza
cases on the Gulf of Thailand side.