Abstract: Operation enhancement in an air cooler depends on
rate of heat transfer, and pressure drop. In this paper for a given heat
duty, study of the effects of FPI (Fin Per Inch) and fin type (circular
and hexagonal fins) on heat transfer, and pressure drop in an air
cooler in Iran, Arvand petrochemical. A program in EES
(Engineering Equations Solver) software moreover, Aspen B-JAC
and HTFS+ softwares are used for this purpose to solve governing
equations. At first the simulated results obtained from this program is
compared to the experimental data for two cases of FPI. The effects
of FPI from 3 to 15 over heat transfer (Q) to pressure drop ratio
(Q/Δp ratio). This ratio is one of the main parameters in design, and
simulation heat exchangers. The results show that heat transfer (Q)
and pressure drop increase with increasing FPI steadily, and the Q/Δp
ratio increases to FPI=12 and then decreased gradually to FPI=15,
and Q/Δp ratio is maximum at FPI=12. The FPI value selection
between 8 and 12 obtained as a result to optimum heat transfer to
pressure drop ratio. Also by contrast, between circular and hexagonal
fins results, the Q/Δp ratio of hexagonal fins more than Q/Δp ratio of
circular fins for FPI between 8 and 12 (optimum FPI)
Abstract: The main focus of the work was concerned with hydrodynamic and thermal analysis of the plate heat exchanger channel with corrugation patterns suggested to be triangular, sinusoidal, and square corrugation. This study was to numerically model and validate the triangular corrugated channel with dimensions/parameters taken from open literature, and then model/analyze both sinusoidal, and square corrugated channel referred to the triangular model. Initially, 2D modeling with local extensive analysis for triangular corrugated channel was carried out. By that, all local pressure drop, wall shear stress, friction factor, static temperature, heat flux, Nusselt number, and surface heat coefficient, were analyzed to interpret the hydrodynamic and thermal phenomena occurred in the flow. Furthermore, in order to facilitate confidence in this model, a comparison between the values predicted, and experimental results taken from literature for almost the same case, was done. Moreover, a holistic numerical study for sinusoidal and square channels together with global comparisons with triangular corrugation under the same condition, were handled. Later, a comparison between electric, and fluid cooling through varying the boundary condition was achieved. The constant wall temperature and constant wall heat flux boundary conditions were employed, and the different resulted Nusselt numbers as a consequence were justified. The results obtained can be used to come up with an optimal design, a 'compromise' between heat transfer and pressure drop.