Abstract: In this paper, we propose the Modified Synchronous Detection (MSD) Method for determining the reference compensating currents of the shunt active power filter under non sinusoidal voltages conditions. For controlling the inverter switching we used the PI regulator. The numerical simulation results, using Power System Blockset Toolbox PSB of Matlab, from a complete structure, are presented and discussed.
Abstract: In recent years the large scale use of the power electronic equipment has led to an increase of harmonics in the power system. The harmonics results into a poor power quality and have great adverse economical impact on the utilities and customers. Current harmonics are one of the most common power quality problems and are usually resolved by using shunt active filter (SHAF). The main objective of this work is to develop PI and Fuzzy logic controllers (FLC) to analyze the performance of Shunt Active Filter for mitigating current harmonics under balanced and unbalanced sinusoidal source voltage conditions for normal load and increased load. When the supply voltages are ideal (balanced), both PI and FLC are converging to the same compensation characteristics. However, the supply voltages are non-ideal (unbalanced), FLC offers outstanding results. Simulation results validate the superiority of FLC with triangular membership function over the PI controller.
Abstract: The proper selection of the AC-side passive filter
interconnecting the voltage source converter to the power supply is
essential to obtain satisfactory performances of an active power filter
system. The use of the LCL-type filter has the advantage of
eliminating the high frequency switching harmonics in the current
injected into the power supply. This paper is mainly focused on
analyzing the influence of the interface filter parameters on the active
filtering performances. Some design aspects are pointed out. Thus,
the design of the AC interface filter starts from transfer functions by
imposing the filter performance which refers to the significant current
attenuation of the switching harmonics without affecting the
harmonics to be compensated. A Matlab/Simulink model of the entire
active filtering system including a concrete nonlinear load has been
developed to examine the system performances. It is shown that a
gamma LC filter could accomplish the attenuation requirement of the
current provided by converter. Moreover, the existence of an optimal
value of the grid-side inductance which minimizes the total harmonic
distortion factor of the power supply current is pointed out.
Nevertheless, a small converter-side inductance and a damping
resistance in series with the filter capacitance are absolutely needed
in order to keep the ripple and oscillations of the current at the
converter side within acceptable limits. The effect of change in the
LCL-filter parameters is evaluated. It is concluded that good active
filtering performances can be achieved with small values of the
capacitance and converter-side inductance.