Abstract: This investigation develops a revisable method for estimating the estimate value of equivalent 10 Hz voltage flicker (DV10) of a DC Electric Arc Furnace (EAF). This study also discusses three 161kV DC EAFs by field measurement, with those results indicating that the estimated DV10 value is significantly smaller than the survey value. The key point is that the conventional means of estimating DV10 is inappropriate. There is a main cause as the assumed Qmax is too small.
Although DC EAF is regularly operated in a constant MVA mode, the reactive power variation in the Main Transformer (MT) is more significant than that in the Furnace Transformer (FT). A substantial difference exists between estimated maximum reactive power fluctuation (DQmax) and the survey value from actual DC EAF operations. However, this study proposes a revisable method that can obtain a more accurate DV10 estimate than the conventional method.
Abstract: One of the most important power quality issues is voltage flicker. Nowadays this issue also impacts the power system all over the world. The fact of the matter is that the more and the larger capacity of wind generator has been installed. Under unstable wind power situation, the variation of output current and voltage have caused trouble to voltage flicker. Hence, the major purpose of this study is to analyze the impact of wind generator on voltage flicker of power system. First of all, digital simulation and analysis are carried out based on wind generator operating under various system short circuit capacity, impedance angle, loading, and power factor of load. The simulation results have been confirmed by field measurements.
Abstract: Voltage flicker problems have long existed in several
of the distribution areas served by the Taiwan Power Company. In
the past, those research results indicating that the estimated ΔV10
value based on the conventional method is significantly smaller than
the survey value. This paper is used to study the relationship between
the voltage flicker problems and harmonic power variation for the
power system with electric arc furnaces. This investigation discussed
thought the effect of harmonic power fluctuation with flicker
estimate value. The method of field measurement, statistics and
simulation is used. The survey results demonstrate that 10 ΔV
estimate must account for the effect of harmonic power variation.
Abstract: Voltage flicker is a disturbance in electrical power
systems. The reason for this disturbance is mainly the large nonlinear
loads such as electric arc furnaces. Synchronous static
compensator (STATCOM) is considered as a proper technique to
mitigate the voltage flicker. Application of more suitable and precise
power electronic converter leads to a more precise performance of the
compensator. In this paper a three-level 12-pulse voltage source
inverter (VSI) with a 12-terminal transformer connected to the ac
system is studied and the obtained results are compared with the
performance of a STATCOM using a simple two-level VSI and an
optimal and more precise performance of the proposed scheme is
achieved.