Real-Time Measurement Approach for Tracking the ΔV10 Estimate Value of DC EAF

This investigation develops a revisable method for estimating the estimate value of equivalent 10 Hz voltage flicker (DV10) of a DC Electric Arc Furnace (EAF). This study also discusses three 161kV DC EAFs by field measurement, with those results indicating that the estimated DV10 value is significantly smaller than the survey value. The key point is that the conventional means of estimating DV10 is inappropriate. There is a main cause as the assumed Qmax is too small. Although DC EAF is regularly operated in a constant MVA mode, the reactive power variation in the Main Transformer (MT) is more significant than that in the Furnace Transformer (FT). A substantial difference exists between estimated maximum reactive power fluctuation (DQmax) and the survey value from actual DC EAF operations. However, this study proposes a revisable method that can obtain a more accurate DV10 estimate than the conventional method.

The Influence of Voltage Flicker for the Wind Generator upon Distribution System

One of the most important power quality issues is voltage flicker. Nowadays this issue also impacts the power system all over the world. The fact of the matter is that the more and the larger capacity of wind generator has been installed. Under unstable wind power situation, the variation of output current and voltage have caused trouble to voltage flicker. Hence, the major purpose of this study is to analyze the impact of wind generator on voltage flicker of power system. First of all, digital simulation and analysis are carried out based on wind generator operating under various system short circuit capacity, impedance angle, loading, and power factor of load. The simulation results have been confirmed by field measurements.

The Effect of Harmonic Power Fluctuation for Estimating Flicker

Voltage flicker problems have long existed in several of the distribution areas served by the Taiwan Power Company. In the past, those research results indicating that the estimated ΔV10 value based on the conventional method is significantly smaller than the survey value. This paper is used to study the relationship between the voltage flicker problems and harmonic power variation for the power system with electric arc furnaces. This investigation discussed thought the effect of harmonic power fluctuation with flicker estimate value. The method of field measurement, statistics and simulation is used. The survey results demonstrate that 10 ΔV estimate must account for the effect of harmonic power variation.

A New Design of Mobile Thermoelectric Power Generation System

This paper presents a compact thermoelectric power generator system based on temperature difference across the element. The system can transfer the burning heat energy to electric energy directly. The proposed system has a thermoelectric generator and a power control box. In the generator, there are 4 thermoelectric modules (TEMs), each of which uses 2 thermoelectric chips (TEs) and 2 cold sinks, 1 thermal absorber, and 1 thermal conduction flat board. In the power control box, there are 1 storing energy device, 1 converter, and 1 inverter. The total net generating power is about 11W. This system uses commercial portable gas stoves or burns timber or the coal as the heat source, which is easily obtained. It adopts solid-state thermoelectric chips as heat inverter parts. The system has the advantages of being light-weight, quite, and mobile, requiring no maintenance, and havng easily-supplied heat source. The system can be used a as long as burning is allowed. This system works well for highly-mobilized outdoors situations by providing a power for illumination, entertainment equipment or the wireless equipment at refuge. Under heavy storms such as typhoon, when the solar panels become ineffective and the wind-powered machines malfunction, the thermoelectric power generator can continue providing the vital power.

A New Design of Temperature-Controlled Chamber for OLED Panels

This paper presents an inexpensive and effective temperature-controlled chamber for temperature environment tests of Organic Light Emitting Diode (OLED) panels. The proposed chamber is a compact warmer and cooler with an exact temperature control system. In the temperature-controlled space of the chamber, thermoelectric modules (TEMs) are utilized to cool or to heat OLED panels, novel fixtures are designed to flexibly clamp the OLED panels of different size, and special connectors for wiring between the OLED panels and the test instrument are supplied. The proposed chamber has the following features. (1) The TEMs are solid semi-conductive devices, so they operate without noise and without pollution. (2) The volume of the temperature-controlled space of the chamber about 160mm*160mm*120mm, so the chamber are compact and easy to move. (3) The range of the controlled temperatures is from -10 oC to +80 oC, and the precision is ?0.5 oC. (4) The test instrument can conveniently and easily measure the OLED panels via the novel fixtures and special connectors. In addition to a constant temperature being maintained in the chamber, a temperature shock experiments can run for a long time. Therefore, the chamber will be convenient and useful for temperature environment tests of OLED panels.