Abstract: This paper presents the experimental results and the related modeling of a thermal energy storage (TES) facility, ideated and realized by ENEA and realizing the thermocline with an innovative geometry. Firstly, the thermal energy exchange model of an equivalent shell & tube heat exchanger is described and tested to reproduce the performance of the spiral exchanger installed in the TES. Through the regression of the experimental data, a first-order thermocline model was also validated to provide an analytical function of the thermocline, useful for the performance evaluation and the comparison with other systems and implementation in simulations of integrated systems (e.g. power plants). The experimental data obtained from the plant start-up and the short-cut modeling of the system can be useful for the process analysis, for the scale-up of the thermal storage system and to investigate the feasibility of its implementation in actual case-studies.
Abstract: In countries with hot climates, air-conditioning forms
a large proportion of annual peak electrical demand, requiring
expansion of power plants to meet the peak demand, which goes
unused most of the time. Use of well-designed cool storage can offset
the peak demand to a large extent. In this study, an air conditioning
system with naturally stratified storage tank was designed,
constructed and tested. A new type of diffuser was designed and used
in this study. Factors that influence the performance of chilled water
storage tanks were investigated. The results indicated that stratified
storage tank consistently stratified well without any physical barrier.
Investigation also showed that storage efficiency decreased with
increasing flow rate due to increased mixing of warm and chilled
water. Diffuser design and layout primarily affected the mixing near
the inlet diffuser and the extent of this mixing had primary influence
on the shape of the thermocline. The heat conduction through tank
walls and through the thermocline caused widening of mixed volume.
Thermal efficiency of stratified storage tanks was as high as 90
percent, which indicates that stratified tanks can effectively be used
as a load management technique.
Abstract: This paper reports on the results of experimental
investigations of flash evaporation from superheated jet issues
vertically upward from a round straight nozzle of 81.3 mm diameter.
For the investigated range of jet superheat degree and velocity, it was
shown that flash evaporation enhances with initial temperature
increase. Due to the increase of jet inertia and subsequently the delay
of jet shattering, increase of jet velocity was found to result in
increase of evaporation "delay period". An empirical equation
predicts the jet evaporation completion height was developed, this
equation is thought to be useful in designing the flash evaporation
chamber. In attempts for enhancement of flash evaporation, use of
steel wire mesh located at short distance downstream was found
effective with no consequent pressure drop.