Abstract: This paper addresses the problems encountered by conventional distance relays when protecting double-circuit transmission lines. The problems arise principally as a result of the mutual coupling between the two circuits under different fault conditions; this mutual coupling is highly nonlinear in nature. An adaptive protection scheme is proposed for such lines based on application of artificial neural network (ANN). ANN has the ability to classify the nonlinear relationship between measured signals by identifying different patterns of the associated signals. One of the key points of the present work is that only current signals measured at local end have been used to detect and classify the faults in the double circuit transmission line with double end infeed. The adaptive protection scheme is tested under a specific fault type, but varying fault location, fault resistance, fault inception angle and with remote end infeed. An improved performance is experienced once the neural network is trained adequately, which performs precisely when faced with different system parameters and conditions. The entire test results clearly show that the fault is detected and classified within a quarter cycle; thus the proposed adaptive protection technique is well suited for double circuit transmission line fault detection & classification. Results of performance studies show that the proposed neural network-based module can improve the performance of conventional fault selection algorithms.
Abstract: The new idea of this research is application of a new fault detection and isolation (FDI) technique for supervision of sensor networks in transportation system. In measurement systems, it is necessary to detect all types of faults and failures, based on predefined algorithm. Last improvements in artificial neural network studies (ANN) led to using them for some FDI purposes. In this paper, application of new probabilistic neural network features for data approximation and data classification are considered for plausibility check in temperature measurement. For this purpose, two-phase FDI mechanism was considered for residual generation and evaluation.
Abstract: Modern manufacturing facilities are large scale,
highly complex, and operate with large number of variables under
closed loop control. Early and accurate fault detection and diagnosis
for these plants can minimise down time, increase the safety of plant
operations, and reduce manufacturing costs. Fault detection and
isolation is more complex particularly in the case of the faulty analog
control systems. Analog control systems are not equipped with
monitoring function where the process parameters are continually
visualised. In this situation, It is very difficult to find the relationship
between the fault importance and its consequences on the product
failure. We consider in this paper an approach to fault detection and
analysis of its effect on the production quality using an adaptive
centring and scaling in the pickling process in cold rolling. The fault
appeared on one of the power unit driving a rotary machine, this
machine can not track a reference speed given by another machine.
The length of metal loop is then in continuous oscillation, this affects
the product quality. Using a computerised data acquisition system,
the main machine parameters have been monitored. The fault has
been detected and isolated on basis of analysis of monitored data.
Normal and faulty situation have been obtained by an artificial neural
network (ANN) model which is implemented to simulate the normal
and faulty status of rotary machine. Correlation between the product
quality defined by an index and the residual is used to quality
classification.
Abstract: Self-sensing estimates the air gap within an electro
magnetic path by analyzing the bearing coil current and/or voltage
waveform. The self-sensing concept presented in this paper has been
developed within the research project “Active Magnetic Bearings
with Supreme Reliability" and is used for position sensor fault
detection.
Within this new concept gap calculation is carried out by an alldigital
analysis of the digitized coil current and voltage waveform.
For analysis those time periods within the PWM period are used,
which give the best results. Additionally, the concept allows the
digital compensation of nonlinearities, for example magnetic
saturation, without degrading signal quality. This increases the
accuracy and robustness of the air gap estimation and additionally
reduces phase delays.
Beneath an overview about the developed concept first
measurement results are presented which show the potential of this
all-digital self-sensing concept.
Abstract: The effect of the rotational speed and axial torque on
the diagnostics of tapered rolling element bearing defects was
investigated. The accelerometer was mounted on the bearing housing
and connected to Sound and Vibration Analyzer (SVAN 958) and
was used to measure the accelerations from the bearing housing. The
data obtained from the bearing was processed to detect damage of the
bearing using statistical tools and the results were subsequently
analyzed to see if bearing damage had been captured. From this study
it can be seen that damage is more evident when the bearing is
loaded. Also, at the incipient stage of damage the crest factor and
kurtosis values are high but as time progresses the crest factors and
kurtosis values decrease whereas the peak and RMS values are low at
the incipient stage but increase with damage.