Abstract: Clean air in subway station is important to passengers. The Platform Screen Doors (PSDs) can improve indoor air quality in the subway station; however the air quality in the subway tunnel is degraded. The subway tunnel has high CO2 concentration and indoor particulate matter (PM) value. The Indoor Air Quality (IAQ) level in subway environment degrades by increasing the frequency of the train operation and the number of the train. The ventilation systems of the subway tunnel need improvements to have better air-quality. Numerical analyses might be effective tools to analyze the performance of subway twin-track tunnel ventilation systems. An existing subway twin-track tunnel in the metropolitan Seoul subway system is chosen for the numerical simulations. The ANSYS CFX software is used for unsteady computations of the airflow inside the twin-track tunnel when the train moves. The airflow inside the tunnel is simulated when one train runs and two trains run at the same time in the tunnel. The piston-effect inside the tunnel is analyzed when all shafts function as the natural ventilation shaft. The supplied air through the shafts is mixed with the pollutant air in the tunnel. The pollutant air is exhausted by the mechanical ventilation shafts. The supplied and discharged airs are balanced when only one train runs in the twin-track tunnel. The pollutant air in the tunnel is high when two trains run simultaneously in opposite direction and all shafts functioned as the natural shaft cases when there are no electrical power supplies in the shafts. The remained pollutant air inside the tunnel enters into the station platform when the doors are opened.
Abstract: The Platform Screen Doors improve Indoor Air Quality
(IAQ) in the subway station; however, and the air quality is degraded
in the subway tunnel. CO2 concentration and indoor particulate matter
value are high in the tunnel. The IAQ level in subway tunnel degrades
by increasing the train movements. Air-curtain installation reduces
dusts, particles and moving toxic smokes and permits traffic by
generating virtual wall. The ventilation systems of the subway tunnel
need improvements to have better air-quality. Numerical analyses
might be effective tools analyze the flowfield inside the air-curtain
installed subway tunnel. The ANSYS CFX software is used for steady
computations of the airflow inside the tunnel. The single-track subway
tunnel has the natural shaft, the mechanical shaft, and the PSDs
installed stations. The height and width of the tunnel are 6.0 m and 4.0
m respectively. The tunnel is 400 m long and the air-curtain is installed
at the top of the tunnel. The thickness and the width of the air-curtain
are 0.08 m and 4 m respectively. The velocity of the air-curtain
changes between 20 - 30 m/s. Three cases are analyzed depending on
the installing location of the air-curtain. The discharged-air through
the natural shafts increases as the velocity of the air-curtain increases
when the air-curtain is installed between the mechanical and the
natural shafts. The pollutant-air is exhausted by the mechanical and the
natural shafts and remained air is pushed toward tunnel end. The
discharged-air through the natural shaft is low when the air-curtain
installed before the natural shaft. The mass flow rate decreases in the
tunnel after the mechanical shaft as the air-curtain velocity increases.
The computational results of the air-curtain installed tunnel become
basis for the optimum design study. The air-curtain installing location
is chosen between the mechanical and the natural shafts. The velocity
of the air-curtain is fixed as 25 m/s. The thickness and the blowing
angles of the air-curtain are the design variables for the optimum
design study. The object function of the design optimization is
maximizing the discharged air through the natural shaft.