Abstract: Fossil fuel-firing power plants dominate electric
power generation in Taiwan, which are also the major contributor to
Green House gases (GHG). CO2 is the most important greenhouse
gas that cause global warming. This paper penetrates the relationship
between carbon trading for GHG reduction and power generation
expansion planning (GEP) problem for the electrical utility. The
Particle Swarm Optimization (PSO) Algorithm is presented to deal
with the generation expansion planning strategy of the utility with
independent power providers (IPPs). The utility has to take both the
IPPs- participation and environment impact into account when a new
generation unit is considering expanded from view of supply side.
Abstract: Single-pole switching scheme is widely used in the
Extra High Voltage system. However, the substantial negativesequence
current injected to the turbine-generators imposes the
electromagnetic (E/M) torque of double system- frequency
components during the dead time (between single-pole clearing and
line reclosing). This would induce supersynchronous resonance
(SPSR) torque amplifications on low pressure turbine generator
blades and even lead to fatigue damage. This paper proposes the
design of a mechanical filter (MF) with natural frequency close to
double-system frequency. From the simulation results, it is found that
such a filter not only successfully damps the resonant effect, but also
has the characteristics of feasibility and compact.