Abstract: The main objective of this paper is a comparative
investigate in enhancement of damping power system oscillation via
coordinated design of the power system stabilizer (PSS) and static
synchronous series compensator (SSSC) and static synchronous
compensator (STATCOM). The design problem of FACTS-based
stabilizers is formulated as a GA based optimization problem. In this
paper eigenvalue analysis method is used on small signal stability of
single machine infinite bus (SMIB) system installed with SSSC and
STATCOM. The generator is equipped with a PSS. The proposed
stabilizers are tested on a weakly connected power system with
different disturbances and loading conditions. This aim is to enhance
both rotor angle and power system stability. The eigenvalue analysis
and non-linear simulation results are presented to show the effects of
these FACTS-based stabilizers and reveal that SSSC exhibits the best
effectiveness on damping power system oscillation.
Abstract: Voltage collapse is instability of heavily loaded electric
power systems that cause to declining voltages and blackout. Power
systems are predicated to become more heavily loaded in the future
decade as the demand for electric power rises while economic and
environmental concerns limit the construction of new transmission
and generation capacity. Heavily loaded power systems are closer to
their stability limits and voltage collapse blackouts will occur if
suitable monitoring and control measures are not taken. To control
transmission lines, it can be used from FACTS devices.
In this paper Harmony search algorithm (HSA) and Genetic
Algorithm (GA) have applied to determine optimal location of
FACTS devices in a power system to improve power system stability.
Three types of FACTS devices (TCPAT, UPFS, and SVC) have been
introduced. Bus under voltage has been solved by controlling reactive
power of shunt compensator. Also a combined series-shunt
compensators has been also used to control transmission power flow
and bus voltage simultaneously.
Different scenarios have been considered. First TCPAT, UPFS, and
SVC are placed solely in transmission lines and indices have been
calculated. Then two types of above controller try to improve
parameters randomly. The last scenario tries to make better voltage
stability index and losses by implementation of three types controller
simultaneously. These scenarios are executed on typical 34-bus test
system and yields efficiency in improvement of voltage profile and
reduction of power losses; it also may permit an increase in power
transfer capacity, maximum loading, and voltage stability margin.
Abstract: Distance protection of transmission lines including advanced flexible AC transmission system (FACTS) devices has been a very challenging task. FACTS devices of interest in this paper are static synchronous series compensators (SSSC) and unified power flow controller (UPFC). In this paper, a new algorithm is proposed to detect and classify the fault and identify the fault position in a transmission line with respect to a FACTS device placed in the midpoint of the transmission line. Discrete wavelet transformation and wavelet entropy calculations are used to analyze during fault current and voltage signals of the compensated transmission line. The proposed algorithm is very simple and accurate in fault detection and classification. A variety of fault cases and simulation results are introduced to show the effectiveness of such algorithm.