Abstract: The aim of this research is to design a LHP with low thermal resistance and low condenser temperature. A Self-designed cascade LHP was tested by using biomaterial, sintered copper powder, and aluminum screen mesh as the wick. Using pure water as the working fluid for the first level of the LHP and 96% alcohol as the working fluid for the second level of LHP, the experiments were run with 10W, 20W, and 30W heat input. Experimental result shows that the usage of biomaterial as wick could reduce more temperature at evaporator than by using sintered copper powder and screen mesh up to 22.63% and 37.41% respectively. The lowest thermal resistance occurred during the usage of biomaterial as wick of heat pipe, which is 2.06 oC/W. The usage of cascade system could be applied to LHP to reduce the temperature at condenser and reduced thermal resistance up to 17.6%.
Abstract: We investigate the performance of an integrated cascade (IC) refrigeration system which uses environment friendly zeotropic mixtures. Computational calculation has been carried out by varying pressure level at the evaporator and the condenser of the system. Effects of mass flow rate of the refrigerant on the coefficient of performance (COP) are presented. We show that the integrated cascade system produces ultra-low temperatures in the evaporator by using environment friendly zeotropic mixture.
Abstract: Cascade refrigeration systems employ series of single stage vapor compression units which are thermally coupled with evaporator/condenser cascades. Different refrigerants are used in each of the circuit depending on the optimum characteristics shown by the refrigerant for a particular application. In the present research study, a steady state thermodynamic model is developed which simulates the working of an actual cascade system. The model provides COP and all other system parameters e.g. total compressor work, temperature, pressure, enthalpy and entropy at different state points. The working fluid in low temperature circuit (LTC) is CO2 (R744) while Ammonia (R717), Propane (R290), Propylene (R1270), R404A and R12 are the refrigerants in high temperature circuit (HTC). The performance curves of Ammonia, Propane, Propylene, and R404A are compared with R12 to find its nearest substitute. Results show that Ammonia is the best substitute of R12.
Abstract: Capacity and efficiency of any refrigerating system
diminish rapidly as the difference between the evaporating and
condensing temperature is increased by reduction in the evaporator
temperature. The single stage vapour compression refrigeration
system is limited to an evaporator temperature of -40 0C. Below
temperature of -40 0C the either cascade refrigeration system or multi
stage vapour compression system is employed. Present work
describes thermal design of main three heat exchangers namely
condenser (HTS), cascade condenser and evaporator (LTS) of
R404A-R508B and R410A-R23 cascade refrigeration system. Heat
transfer area of condenser (HTS), cascade condenser and evaporator
(LTS) for both systems have been compared and the effect of
condensing and evaporating temperature on heat-transfer area for
both systems have been studied under same operating condition. The
results shows that the required heat-transfer area of condenser and
cascade condenser for R410A-R23 cascade system is lower than the
R404A-R508B cascade system but heat transfer area of evaporator is
similar for both the system. The heat transfer area of condenser and
cascade condenser decreases with increase in condensing temperature
(Tc), whereas the heat transfer area of cascade condenser and
evaporator increases with increase in evaporating temperature (Te).
Abstract: Capacity and efficiency of any refrigerating system
diminish rapidly as the difference between the evaporating and
condensing temperature is increased by a reduction in the evaporator
temperature. The single stage vapour compression refrigeration
system using various refrigerants are limited to an evaporator
temperature of -40 0C. Below temperature of -40 0C the either
cascade refrigeration system or multi stage vapour compression
system is employed. Present work describes thermal design of
condenser (HTS), cascade condenser and evaporator (LTS) of
R404A-R508B and R410A-R23 cascade refrigeration system. Heat
transfer area of condenser, cascade condenser and evaporator for
both systems are compared and the effect of condenser and
evaporator temperature on heat-transfer area for both systems is
studied under same operating condition. The results shows that the
required heat-transfer area of condenser and cascade condenser for
R410A-R23 cascade system is lower than the R404A-R508B cascade
system but heat transfer area of evaporator is similar for both the
system. The heat transfer area of condenser and cascade condenser
decreases with increase in condenser temperature (Tc), whereas the
heat transfer area of cascade condenser and evaporator increases with
increase in evaporator temperature (Te).