The Comprehensive Study Based on Ultrasonic and X-ray Visual Technology for GIS Equipment Detection

For lack of the visualization of the ultrasonic detection method of partial discharge (PD), the ultrasonic detection technology combined with the X-ray visual detection method (UXV) is proposed. The method can conduct qualitative analysis accurately and conduct reliable positioning diagnosis to the internal insulation defects of GIS, and while it could make up the blindness of the X-ray visual detection method and improve the detection rate. In this paper, an experimental model of GIS is used as the trial platform, a variety of insulation defects are set inside the GIS cavity. With the proposed method, the ultrasonic method is used to conduct the preliminary detection, and then the X-ray visual detection is used to locate and diagnose precisely. Therefore, the proposed UXV technology is feasible and practical.




References:
[1] LI Da-jian, LIANG Ji-zhong, BU Ke-wei, YANG Jing-gang, LI
Yan-ming. Ultrasonic Detection of Partial Discharge on Typical Defects
in GIS. High Voltage Apparatus, Vol.45, No.1, Feb. 2009: 72-74
[2] Yang Yuan, Li Cheng-rong. Study on Ultrasonic Characteristics of
Typical Partial Discharge of GIS. Modern Electric Power. Vol. 26, No.5,
Oct. 2009: 18-23
[3] YAN Bin, HE Xi-mei, WANG Zhi-hui, LI Sheng-ping. Application of
X-ray Digital Imaging Defect Detection System in GIS Equipment. High
Voltage Apparatus, Vol.46, No.11, Nov. 2010: 89-91
[4] S. Rizzeto, N. Fujimoto and G. C. Stone. A System for the Detection and
Location of Partial Discharge Using X-Rays. Conference Record of the
1988 IEEE International Symposium on Electrical Insulation, Boston,
MA, June 5-8, 1988, pp: 262-266
[5] CHEN Min, Koji Urano, LI You-Cheng, and Atsuhide Jinno.
Application of Combined PD Sensor for GIS PD Detection and
Condition Monitoring. 2008 International Conference on Condition
Monitoring and Diagnosis, Beijing, China, April 21-24, 2008
[6] FANG Qing, LIU Wei-Dong, DENG Wei, TANG Xin. A new
Ultrasonic Diagnosis Technology for Internal Default of GIS
Equipment. High Voltage Apparatus. Vol.44, No.6, Dec. 2008: 589-595
[7] K. Raja and T. Floribert. Comparative Investigations on UHF and
Acoustic PD Detection Sensitivity in Transformers. Conference Record
of the 2002 IEEE International Symposium on Electrical Insulation, MA
USA, April 7-10 2002, pp: 150-153
[8] YAN Bin, HE Xi-mei, WU Tong-sheng, WANG Zhi-hui, LI Sheng-ping.
X-ray visualization detection technology for GIS equipment. Electric
Power. Vol. 43, No. 7, Jul. 2010: 44-47