Study of Tower Grounding Resistance Effected Back Flashover to 500 kV Transmission Line in Thailand by using ATP/EMTP

This study describes analysis of tower grounding resistance effected the back flashover voltage across insulator string in a transmission system. This paper studies the 500 kV transmission lines from Mae Moh, Lampang to Nong Chok, Bangkok, Thailand, which is double circuit in the same steel tower with two overhead ground wires. The factor of this study includes magnitude of lightning stroke, and front time of lightning stroke. Steel tower uses multistory tower model. The assumption of studies based on the return stroke current ranged 1-200 kA, front time of lightning stroke between 1 μs to 3 μs. The simulations study the effect of varying tower grounding resistance that affect the lightning current. Simulation results are analyzed lightning over voltage that causes back flashover at insulator strings. This study helps to know causes of problems of back flashover the transmission line system, and also be as a guideline solving the problem for 500 kV transmission line systems, as well.




References:
[1] K. Ngamsanroaj and W. Tayati, "An Analysis Of Switching
Overvoltages in the EGAT 500 kV Transmission System", Large
Engineering Systems Conference on Power Engineering, 7-9 May 2003,
pp. 149 - 153.
[2] C. Y. Yu, N. Petcharaks and C. Panprommin, "The Statistical
Calculation of Energization Overvoltages, Case of EGAT 500 kV
Lines", IEEE Power Engineering Society Winter Meeting , Vol. 4, 23-
27 Jan. 2000, pp. 2705 - 2709.
[3] C. Jaipradidtham, " Electromagnetic Field Analysis on Surge Response
of 500 kV EHV Single Circuit Transmission Tower in Lightning
Protection System using Neural Networks", Proc. of Int. Conf. on
Control, Automation and System, KINTEX, Gyeonggi-Do, Korea, 2-5
June 2005.
[4] N. Petcharaks, C. Y. Yu and C. Panprommin, " A Study of Ferranti and
Energization Overvoltages case of 500 kV Line in Thailand", 11th Int.
Sym. on High Voltage Engineering, Vol. 1, Conf. Publ. No. 467, 1999,
pp. 291-294.
[5] P. Yadee and S. Premrudeepreechacharn, "Analysis of Tower Footing
Resistance Effected Back Flashover Across Insulator in a Transmission
System", Proc. of Int. Conf. on Power Systems Transients (IPST-07) ,
Lyon, France, June 4-7, 2007.
[6] Report of flashover voltage in Northern Region Operation Division
1996-2003, EGAT, Thailand. (in Thai)
[7] A. R. Hileman, Insulation Coordination for Power Systems, Marcel
Dekker, New York, USA, 1989.
[8] L. V. Bewley, Traveling Waves on Transmission Systems. Dover
Publications, New York, N.Y., USA,1951.
[9] M. Ishii, T. Kawamura, T. Kouno, E. Ohsaki, K. Shiokawa, K. Murotani
and T. Higuchi, "Multistory Transmission Tower Model for Lightning
Surge Analysis", IEEE Trans. on Power Delivery, Vol. 6, No. 3, July
1991, pp. 1327 - 1335.
[10] T. Yamada, A. Mochizuki, J. Sawada, E. Zaima, T. Kawamura, A.
Ametani, M. Ishii and S. Kato, "Experimental evaluation of a UHV
tower model for lightning surge analysis", IEEE Trans. on Power
Delivery, Vol. 10, No. 1, January 1995, pp. 393 - 402.
[11] A. Ametani, N. Nagaoka, T. Funabashi and N. Inoue, "Tower
Structure Effect on a Back-Flashover Phase", Proc. of Int. Conf. on
Power Systems Transients (IPST-05), Paper No. IPST05 - 190,
Montreal, Canada, June 19-23, 2005.
[12] R. B. Anderson and A. J. Erikson, "Lightning Parameters for
Engineering Applications", ELECTRA 69, March 1980, pp. 65 - 102.