Harmonic Comparison between Fluorescent and WOLED (White Organic LED) Lamps

Fluorescent and WOLED are widely used because it consumes less energy. However, both lamps cause a harmonics because it has semiconductors components. Harmonic is a distorted sinusoidal electric wave and cause excess heat. This study compares the amount of harmonics generated by both lamps. The test shows that both lamps have THDv(Total Harmonics Distortion of Voltage) almost the same with average 2.5% while the average of WOLED's THDi(Total Harmonics Distortion of Current) is lower than fluorescent has. The average WOLED's THDi is 29.10 % and fluorescent's 'THDi is 87. 23 %.




References:
[1] Weir, Bernie. (2012, March). Driving 21st Century's Lights. ieee
Spectrum 3.12 , pp. 42-47.
[2] Rasjid, Harun. (2006). Kajian Pnggunaan Filter Pasif Sebagai Pereduksi
Efek Harmonisa. ELTEK , 46-53.
[3] http://karyailmiah.tarumanagara.ac.id/index.php/S1TE/article/view/2221
/0 (11-04- 2012 - 22.40).
[4] http://www.onceinnovations.com/downloads/perf_diff.pdf . (26-05-2012
- 12. 05).
[5] Ellis, Robert G. Power System HArmonic, A Reference Guide to
Causes, Effects and Corrective Measures. Canada: Rockwell
International Corporation, 2001.
[6] Wijaya, F.Danang, Avrin Nur Widiastuti, and Zuhdan Febri Wibowo.
"Pengaruh Beban Harmonik Terhadap Putaran Piringan KWh Meter
Induksi." CITEE. Indonesia: Department Of Electrical Engineering and
Information Tech.,UGM, 2011. 124.
[7] IEEE Recommended Practices and Requirements for Harmonic Control
in Electrical Power Systems, ANSI/IEEE Std. 519-1992.