Abstract: In research on natural ventilation, and passive cooling
with forced convection, is essential to know how heat flows in a solid
object and the pattern of temperature distribution on their surfaces,
and eventually how air flows through and convects heat from the
surfaces of steel under roof. This paper presents some results from
running the computational fluid dynamic program (CFD) by
comparison between natural ventilation and forced convection within
roof attic that is received directly from solar radiation. The CFD
program for modeling air flow inside roof attic has been modified to
allow as two cases. First case, the analysis under natural ventilation,
is closed area in roof attic and second case, the analysis under forced
convection, is opened area in roof attic. These extend of all cases to
available predictions of variations such as temperature, pressure, and
mass flow rate distributions in each case within roof attic. The
comparison shows that this CFD program is an effective model for
predicting air flow of temperature and heat transfer coefficient
distribution within roof attic. The result shows that forced convection
can help to reduce heat transfer through roof attic and an around area
of steel core has temperature inner zone lower than natural
ventilation type. The different temperature on the steel core of roof
attic of two cases was 10-15 oK.
Abstract: The Platform Screen Doors improve Indoor Air Quality
(IAQ) in the subway station; however, and the air quality is degraded
in the subway tunnel. CO2 concentration and indoor particulate matter
value are high in the tunnel. The IAQ level in subway tunnel degrades
by increasing the train movements. Air-curtain installation reduces
dusts, particles and moving toxic smokes and permits traffic by
generating virtual wall. The ventilation systems of the subway tunnel
need improvements to have better air-quality. Numerical analyses
might be effective tools analyze the flowfield inside the air-curtain
installed subway tunnel. The ANSYS CFX software is used for steady
computations of the airflow inside the tunnel. The single-track subway
tunnel has the natural shaft, the mechanical shaft, and the PSDs
installed stations. The height and width of the tunnel are 6.0 m and 4.0
m respectively. The tunnel is 400 m long and the air-curtain is installed
at the top of the tunnel. The thickness and the width of the air-curtain
are 0.08 m and 4 m respectively. The velocity of the air-curtain
changes between 20 - 30 m/s. Three cases are analyzed depending on
the installing location of the air-curtain. The discharged-air through
the natural shafts increases as the velocity of the air-curtain increases
when the air-curtain is installed between the mechanical and the
natural shafts. The pollutant-air is exhausted by the mechanical and the
natural shafts and remained air is pushed toward tunnel end. The
discharged-air through the natural shaft is low when the air-curtain
installed before the natural shaft. The mass flow rate decreases in the
tunnel after the mechanical shaft as the air-curtain velocity increases.
The computational results of the air-curtain installed tunnel become
basis for the optimum design study. The air-curtain installing location
is chosen between the mechanical and the natural shafts. The velocity
of the air-curtain is fixed as 25 m/s. The thickness and the blowing
angles of the air-curtain are the design variables for the optimum
design study. The object function of the design optimization is
maximizing the discharged air through the natural shaft.
Abstract: The presented article deals with the description of a
numerical model of a corridor at a Central Interim Spent Fuel Storage
Facility (hereinafter CISFSF). The model takes into account the
effect of air flows on the temperature of stored waste. The
computational model was implemented in the ANSYS/CFX
programming environment in the form of a CFD task solution, which
was compared with an approximate analytical calculation. The article
includes a categorization of the individual alternatives for the
ventilation of such underground systems. The aim was to evaluate a
ventilation system for a CISFSF with regard to its stability and
capacity to provide sufficient ventilation for the removal of heat
produced by stored casks with spent nuclear fuel.
Abstract: To study the impact of the inter-module ventilation (IMV) on the space station, the Computational Fluid Dynamic (CFD) model under the influence of IMV, the mathematical model, boundary conditions and calculation method are established and determined to analyze the influence of IMV on cabin air flow characteristics and velocity distribution firstly; and then an integrated overall thermal mathematical model of the space station is used to consider the impact of IMV on thermal management. The results show that: the IMV has a significant influence on the cabin air flow, the flowrate of IMV within a certain range can effectively improve the air velocity distribution in cabin, if too much may lead to its deterioration; IMV can affect the heat deployment of the different modules in space station, thus affecting its thermal management, the use of IMV can effectively maintain the temperature levels of the different modules and help the space station to dissipate the waste heat.
Abstract: Natural ventilation has played an important role for
many low energy-building designs. It has been also noticed as a
essential subject to persistently bring the fresh cool air from the
outside into a building. This study carried out the computational fluid
dynamics (CFD)-based simulations to examine the natural ventilation
development of a work area in a public building. The simulated results
can be useful to better understand the indoor microclimate and the
interaction of wind with buildings. Besides, this CFD simulation
procedure can serve as an effective analysis tool to characterize the
airing performance, and thereby optimize the building ventilation for
strengthening the architects, planners and other decision makers on
improving the natural ventilation design of public buildings.
Abstract: This paper reports an experimental study on a sleeping
thermal manikin in a room equipped with a mixing ventilation
system. In the experimental work, heat loss from the sleeping thermal
manikin was measured under different conditions. The supply air
temperature was in a range of 17°C to 27°C. Apart from the heat loss
of the sleeping thermal manikin, the velocity distributions and
temperature distributions were also measured in the experiments for
subsequent analysis.
Abstract: Auckland has a temperate climate with comfortable warm, dry summers and mild, wet winters. Auckland house design not only focus on winter thermal performance and indoor thermal condition, but also indoor moisture control, which is closely related to indirect health effects such as dust mites, fungi, etc. Most Auckland houses are designed to use temporary heating for winter indoor thermal comfort. Based on field study data of indoor microclimate conditions of two Auckland townhouses with a whole home mechanical ventilation system or a passive wind directional skylight vent, this study is to evaluate and compare indoor moisture conditions of two insulated townhouses only using temporary heating with different ventilation systems.
Abstract: In July 2012, an indoor/outdoor monitoring
programme was undertaken in two university sports facilities: a
fronton and a gymnasium. Comfort parameters (temperature, relative
humidity, CO and CO2) and total volatile organic compounds
(VOCs) were continuously monitored. Concentrations of NO2,
carbonyl compounds and individual VOCs were obtained. Low
volume samplers were used to collect particulate matter (PM10). The
minimum ventilation rates stipulated for acceptable indoor air quality
were observed in both sports facilities. It was found that cleaning
activities may have a large influence on the VOC levels. Acrolein
was one of the most abundant carbonyl compounds, showing
concentrations above the recommended limit. Formaldehyde was
detected at levels lower than those commonly reported for other
indoor environments. The PM10 concentrations obtained during the
occupancy periods ranged between 38 and 43μgm-3 in the fronton and
from 154 to 198μgm-3 in the gymnasium.