Air Quality in Sports Venues with Distinct Characteristics

In July 2012, an indoor/outdoor monitoring programme was undertaken in two university sports facilities: a fronton and a gymnasium. Comfort parameters (temperature, relative humidity, CO and CO2) and total volatile organic compounds (VOCs) were continuously monitored. Concentrations of NO2, carbonyl compounds and individual VOCs were obtained. Low volume samplers were used to collect particulate matter (PM10). The minimum ventilation rates stipulated for acceptable indoor air quality were observed in both sports facilities. It was found that cleaning activities may have a large influence on the VOC levels. Acrolein was one of the most abundant carbonyl compounds, showing concentrations above the recommended limit. Formaldehyde was detected at levels lower than those commonly reported for other indoor environments. The PM10 concentrations obtained during the occupancy periods ranged between 38 and 43μgm-3 in the fronton and from 154 to 198μgm-3 in the gymnasium.