Abstract: The most common cause of power transformer failures
is mechanical defect brought about by excessive vibration, which is
formed by the combination of multiples of a frequency of 120 Hz. In
this paper, the types of mechanical exciting forces applied to the
power transformer were classified, and the mechanical damage
mechanism of the power transformer was identified using the
vibration transfer route to the machine or structure. The general
effects of 120 Hz-vibration on the enclosure, bushing, Buchholz
relay, pressure release valve and tap changer of the transformer were
also examined.
Abstract: In this paper, the construction of a detailed spine
model is presented using the LifeMOD Biomechanics Modeler. The
detailed spine model is obtained by refining spine segments in
cervical, thoracic and lumbar regions into individual vertebra
segments, using bushing elements representing the intervertebral
discs, and building various ligamentous soft tissues between
vertebrae. In the sagittal plane of the spine, constant force will be
applied from the posterior to anterior during simulation to determine
dynamic characteristics of the spine. The force magnitude is
gradually increased in subsequent simulations. Based on these
recorded dynamic properties, graphs of displacement-force
relationships will be established in terms of polynomial functions by
using the least-squares method and imported into a haptic integrated
graphic environment. A thoracolumbar spine model with complex
geometry of vertebrae, which is digitized from a resin spine
prototype, will be utilized in this environment. By using the haptic
technique, surgeons can touch as well as apply forces to the spine
model through haptic devices to observe the locomotion of the spine
which is computed from the displacement-force relationship graphs.
This current study provides a preliminary picture of our ongoing
work towards building and simulating bio-fidelity scoliotic spine
models in a haptic integrated graphic environment whose dynamic
properties are obtained from LifeMOD. These models can be helpful
for surgeons to examine kinematic behaviors of scoliotic spines and
to propose possible surgical plans before spine correction operations.
Abstract: At present, the tendency to implement the conditionbased
maintenance (CBM), which allows the optimization of the
expenses for equipment monitoring, is more and more evident; also,
the transformer substations with remote monitoring are increasingly
used. This paper reviews all the advantages of the on-line monitoring
and presents an equipment for on-line monitoring of bushings, which
is the own contribution of specialists who are the authors of this
paper. The paper presents a study of the temperature field, using the
finite element method. For carrying out this study, the 3D modelling
of the above mentioned bushing was performed. The analysis study is
done taking into account the extreme thermal stresses, focusing at the
level of the first cooling wing section of the ceramic insulator. This
fact enables to justify the tanĪ“ variation in time, depending on the
transformer loading and the environmental conditions. With a view
to reducing the variation of dielectric losses in bushing insulation, the
use of ferrofuids instead of mineral oils is proposed.
Abstract: This paper presents the results of a comprehensive
investigation of five blackouts that occurred on 28 August to 8
September 2011 due to bushing failures of the 132/33 kV, 125 MVA
transformers at JBB Ali Grid station. The investigation aims to
explore the root causes of the bushing failures and come up with
recommendations that help in rectifying the problem and avoiding the
reoccurrence of similar type of incidents. The incident reports about
the failed bushings and the SCADA reports at this grid station were
examined and analyzed. Moreover, comprehensive power quality
field measurements at ten 33/11 kV substations (S/Ss) in JBB Ali
area were conducted, and frequency scans were performed to verify
any harmonic resonance frequencies due to power factor correction
capacitors. Furthermore, the daily operations of the on-load tap
changers (OLTCs) of both the 125 MVA and 20 MVA transformers
at JBB Ali Grid station have been analyzed. The investigation
showed that the five bushing failures were due to a local problem, i.e.
internal degradation of the bushing insulation. This has been
confirmed by analyzing the time interval between successive OLTC
operations of the faulty grid transformers. It was also found that
monitoring the number of OLTC operations can help in predicting
bushing failure.
Abstract: The state of melt viscosity in injection process is significantly influenced by the setting parameters due to that the shear rate of injection process is higher than other processes. How to determine plastic melt viscosity during injection process is important to understand the influence of setting parameters on the melt viscosity. An apparatus named as pressure sensor bushing (PSB) module that is used to evaluate the melt viscosity during injection process is developed in this work. The formulations to coupling melt viscosity with fill time and injection pressure are derived and then the melt viscosity is determined. A test mold is prepared to evaluate the accuracy on viscosity calculations between the PSB module and the conventional approaches. The influence of melt viscosity on the tensile strength of molded part is proposed to study the consistency of injection quality.
Abstract: This paper proposes a robot able to climb Columns.
This robot is not dependent on the diameter and material of the
columns. Some climbing robots have been designed up to now but
Koala robot was designed and fabricated for climbing columns
exclusively. Simple kinematics of climbing in the nature inspired us
to design this robot. We used two linear mechanisms to grip the
column. The gripper consists of a DC motor and a power screw
mechanism with a linear bushing as a guide. This mechanism
provides enough force to grip the column. In addition we needed an
actuator for climbing the column; hence, two pneumatic jacks were
used. All the mechanical parts were designed according to the
exerted forces and operational condition. The prototype can be
simply installed and controlled on the column by an inexperienced
operator. This robot is intended for inspection and surveillance of
pipes in oil industries and power poles in electric industries.
Abstract: This study adopted previous fault patterns, results of
detection analysis, historical records and data, and experts-
experiences to establish fuzzy principles and estimate the failure
probability index of components of a power transformer. Considering
that actual parameters and limiting conditions of parameters may
differ, this study used the standard data of IEC, IEEE, and CIGRE as
condition parameters. According to the characteristics of each
condition parameter, relative degradation was introduced to reflect the
degree of influence of the factors on the transformer condition. The
method of fuzzy mathematics was adopted to determine the
subordinate function of the transformer condition. The calculation
used the Matlab Fuzzy Tool Box to select the condition parameters of
coil winding, iron core, bushing, OLTC, insulating oil and other
auxiliary components and factors (e.g., load records, performance
history, and maintenance records) of the transformer to establish the
fuzzy principles. Examples were presented to support the rationality
and effectiveness of the evaluation method of power transformer
performance conditions, as based on fuzzy comprehensive evaluation.