Abstract: Since IEC61850 substation communication standard represents the trend to develop new generations of Substation Automation System (SAS), many IED manufacturers pursue this technique and apply for KEMA. In order to put on the market to meet customer demand as fast as possible, manufacturers often apply their products only for basic environment standard certification but claim to conform to IEC61850 certification. Since verification institutes generally perform verification tests only on specific IEDs of the manufacturers, the interoperability between all certified IEDs cannot be guaranteed. Therefore the interoperability between IEDs from different manufacturers needs to be tested. Based upon the above reasons, this study applies the definitions of the information models, communication service, GOOSE functionality and Substation Configuration Language (SCL) of the IEC61850 to build the concept of communication protocols, and build the test environment. The procedures of the test of the data collection and exchange of the P2P communication mode and Client / Server communication mode in IEC61850 are outlined as follows. First, test the IED GOOSE messages communication capability from different manufacturers. Second, collect IED data from each IED with SCADA system and use HMI to display the SCADA platform. Finally, problems generally encountered in the test procedure are summarized.
Abstract: This study adopted previous fault patterns, results of
detection analysis, historical records and data, and experts-
experiences to establish fuzzy principles and estimate the failure
probability index of components of a power transformer. Considering
that actual parameters and limiting conditions of parameters may
differ, this study used the standard data of IEC, IEEE, and CIGRE as
condition parameters. According to the characteristics of each
condition parameter, relative degradation was introduced to reflect the
degree of influence of the factors on the transformer condition. The
method of fuzzy mathematics was adopted to determine the
subordinate function of the transformer condition. The calculation
used the Matlab Fuzzy Tool Box to select the condition parameters of
coil winding, iron core, bushing, OLTC, insulating oil and other
auxiliary components and factors (e.g., load records, performance
history, and maintenance records) of the transformer to establish the
fuzzy principles. Examples were presented to support the rationality
and effectiveness of the evaluation method of power transformer
performance conditions, as based on fuzzy comprehensive evaluation.