Abstract: Interior brick-infill partitions are usually considered as
non-structural components, and only their weight is accounted for in
practical structural design. In this study, the brick-infill panels are
simulated by compression struts to clarify their effect on the
progressive collapse potential of an earthquake-resistant RC building.
Three-dimensional finite element models are constructed for the RC
building subjected to sudden column loss. Linear static analyses are
conducted to investigate the variation of demand-to-capacity ratio
(DCR) of beam-end moment and the axial force variation of the beams
adjacent to the removed column. Study results indicate that the
brick-infill effect depends on their location with respect to the
removed column. As they are filled in a structural bay with a shorter
span adjacent to the column-removed line, more significant reduction
of DCR may be achieved. However, under certain conditions, the
brick infill may increase the axial tension of the two-span beam
bridging the removed column.
Abstract: Interior brick-infill partitions are usually considered as
non-structural components and only their weight is accounted for in
practical structural design. In this study, their effect on the progressive
collapse resistance of an RC building subjected to sudden column loss
is investigated. Three notional column loss conditions with four
different brick-infill locations are considered. Column-loss response
analyses of the RC building with and without brick infills are carried
out. Analysis results indicate that the collapse resistance is only
slightly influenced by the brick infills due to their brittle failure
characteristic. Even so, they may help to reduce the inelastic
displacement response under column loss. For practical engineering, it
is reasonably conservative to only consider the weight of brick-infill
partitions in the structural analysis.