Abstract: This paper is focused on the reference current
calculation in the compensation mode of the active DC traction
substations. The so-called p-q theory of the instantaneous reactive
power is used as theoretical foundation. The compensation goal of
total compensation is taken into consideration for the operation under
both sinusoidal and nonsinusoidal voltage conditions, through the
two objectives of unity power factor and perfect harmonic
cancelation. Four blocks of reference current generation implement
the conceived algorithms and they are included in a specific Simulink
library, which is useful in a DSP dSPACE-based platform working
under Matlab/Simulink. The simulation results validate the
correctness of the implementation and fulfillment of the
compensation tasks.
Abstract: The aim of this paper is to identify an optimum
control strategy of three-phase shunt active filters to minimize the total harmonic distortion factor of the supply current. A classical PIPI cascade control solution of the output current of the active filterand the voltage across the DC capacitor based on Modulus–Optimum
criterion is taken into consideration. The control system operation
has been simulated using Matlab-Simulink environment and the results agree with the theoretical expectation. It is shown that there is
an optimum value of the DC-bus voltage which minimizes the supply current harmonic distortion factor. It corresponds to the equality of the apparent power at the output of the active filter and the apparent power across the capacitor. Finally, predicted results are verified experimentally on a MaxSine active power filter.
Abstract: This paper deals with the current space-vector
decomposition in three-phase, three-wire systems on the basis of
some case studies. We propose four components of the current spacevector
in terms of DC and AC components of the instantaneous
active and reactive powers. The term of supplementary useless
current vector is also pointed out. The analysis shows that the current
decomposition which respects the definition of the instantaneous
apparent power vector is useful for compensation reasons only if the
supply voltages are sinusoidal. A modified definition of the
components of the current is proposed for the operation under
nonsinusoidal voltage conditions.
Abstract: The proper selection of the AC-side passive filter
interconnecting the voltage source converter to the power supply is
essential to obtain satisfactory performances of an active power filter
system. The use of the LCL-type filter has the advantage of
eliminating the high frequency switching harmonics in the current
injected into the power supply. This paper is mainly focused on
analyzing the influence of the interface filter parameters on the active
filtering performances. Some design aspects are pointed out. Thus,
the design of the AC interface filter starts from transfer functions by
imposing the filter performance which refers to the significant current
attenuation of the switching harmonics without affecting the
harmonics to be compensated. A Matlab/Simulink model of the entire
active filtering system including a concrete nonlinear load has been
developed to examine the system performances. It is shown that a
gamma LC filter could accomplish the attenuation requirement of the
current provided by converter. Moreover, the existence of an optimal
value of the grid-side inductance which minimizes the total harmonic
distortion factor of the power supply current is pointed out.
Nevertheless, a small converter-side inductance and a damping
resistance in series with the filter capacitance are absolutely needed
in order to keep the ripple and oscillations of the current at the
converter side within acceptable limits. The effect of change in the
LCL-filter parameters is evaluated. It is concluded that good active
filtering performances can be achieved with small values of the
capacitance and converter-side inductance.