Abstract: Terms set in power purchase agreements (PPA) challenge power utility companies in balancing between the returns (from maximizing power production) and securing long term supply contracts at capped production. The production limitation set in the PPA has driven efforts to maximize profits through efficient and economic power production. In this paper, a combined industrial-scale gas turbine (GT) - absorption chiller (AC) system is considered to cool the GT air intake for reducing the plant’s heat rate (HR). This GT-AC system is optimized while considering power output limitations imposed by the PPA. In addition, the proposed formulation accounts for uncertainties in the ambient temperature using Type-2 fuzzy programming. Using the enhanced chaotic differential evolution (CEDE), the Pareto frontier was constructed and the optimization results are analyzed in detail.
Abstract: Gas turbine air inlet cooling is a useful method for
increasing output for regions where significant power demand and
highest electricity prices occur during the warm months. Inlet air
cooling increases the power output by taking advantage of the gas
turbine-s feature of higher mass flow rate when the compressor inlet
temperature decreases. Different methods are available for reducing
gas turbine inlet temperature. There are two basic systems currently
available for inlet cooling. The first and most cost-effective system is
evaporative cooling. Evaporative coolers make use of the evaporation
of water to reduce the gas turbine-s inlet air temperature. The second
system employs various ways to chill the inlet air. In this method, the
cooling medium flows through a heat exchanger located in the inlet
duct to remove heat from the inlet air. However, the evaporative
cooling is limited by wet-bulb temperature while the chilling can cool
the inlet air to temperatures that are lower than the wet bulb
temperature. In the present work, a thermodynamic model of a gas
turbine is built to calculate heat rate, power output and thermal
efficiency at different inlet air temperature conditions. Computational
results are compared with ISO conditions herein called "base-case".
Therefore, the two cooling methods are implemented and solved for
different inlet conditions (inlet temperature and relative humidity).
Evaporative cooler and absorption chiller systems results show that
when the ambient temperature is extremely high with low relative
humidity (requiring a large temperature reduction) the chiller is the
more suitable cooling solution. The net increment in the power output
as a function of the temperature decrease for each cooling method is
also obtained.