Abstract: This paper presents the experimental results on role of
ionic solutions affect water treeing propagation in cross-linked
polyethylene insulation for high voltage cable. To study the water
treeing expansion due to the ionic solutions, discs of 4mm thickness
and 4cm diameter were taken from 115 kV XLPE insulation cable
and were used as test specimen in this study. Ionic solutions
composed of CuSO4, FeSO4, Na2SO4 and K2SO4 were used. Each
specimen was immersed in 0.1 mole ionic solutions and was tested
for 120 hrs. under a voltage stress at 7 kV AC rms, 1000 Hz. The
results show that Na2SO4 and CuSO4solutions play an important role
in the expansion of water treeing and cause degradation of the crosslinked
polyethylene (XLPE) in the presence of the applied electric
field.
Abstract: This paper presents the experimental results on space charge distribution in cross-linked polyethylene (XLPE) insulating material for 22 kV power distribution system cable by using pulse electroacoustic measurement technique (PEA). Numbers of XLPE insulating material ribbon having thickness 60 μm taken from unused 22 kV high voltage cable were used as specimen in this study. DC electric field stress was applied to test specimen at room temperature (25°C). Four levels of electric field stress, 25 kV/mm, 50 kV/mm, 75 kV/mm and 100 kV/mm, were used. In order to investigate space charge distribution characteristic, space charge distribution characteristics were measured after applying electric field stress 15 min, 30 min and 60 min, respectively. The results show that applied time and magnitude of dc electric field stress play an important role to the formation of space charge.
Abstract: An acoustic emission (AE) technique is useful for
detection of partial discharges (PDs) at a joint and a terminal section of
a cross-linked polyethylene (XLPE) cable. For AE technique, it is not
difficult to detect a PD using AE sensors. However, it is difficult to
grasp whether the detected AE signal is owing to a single discharge or
not. Additionally, when an AE technique is applied at a terminal
section of a XLPE cable in salt pollution district, for example, there is
possibility of detection of AE signals owing to creeping discharges on
the surface of electric power apparatus. In this study, we evaluated AE
signals in order to grasp what kind of information we can get from
detected AE signals. The results showed that envelop detection of AE
signal and a period which some AE signals were continuously detected
were good indexes for estimating state-of-discharge.
Abstract: This paper presents the experimental results on effect of applied voltage stress frequency to the occurrence of electrical treeing in 22 kV cross linked polyethylene (XLPE) insulated cable.Hallow disk of XLPE insulating material with thickness 5 mm taken from unused high voltage cable was used as the specimen in this study. Stainless steel needle was inserted gradually into the specimen to give a tip to earth plane electrode separation of 2.50.2 mm at elevated temperature 105-110°C. The specimen was then annealed for 5 minute to minimize any mechanical stress build up around the needle-plane region before it was cooled down to room temperature. Each specimen were subjected to the same applied voltage stress level at 8 kV AC rms, with various frequency, 50, 100, 500, 1000 and 2000 Hz. Initiation time, propagation speed and pattern of electrical treeing were examined in order to study the effect of applied voltage stress frequency. By the experimental results, initial time of visible treeing decreases with increasing in applied voltage frequency. Also, obviously, propagation speed of electrical treeing increases with increasing in applied voltage frequency.Furthermore, two types of electrical treeing, bush-like and branch-like treeing were observed.The experimental results confirmed the effect of voltage stress frequency as well.