Abstract: This paper compares the energy and exergy efficiency of a vapour compression refrigeration system using refrigerants of different groups. In this study, five different refrigerants including R507A, R134a, R114, R22 and R717 have been studied. EES Program is used to solve the thermodynamic equations. The results of this analysis are shown graphically. Based on the results, energy and exergy efficiencies for R717 are higher than the other refrigerants. Also, the energy and exergy efficiencies will be decreased with increasing the condensing temperature and decreasing the evaporating temperature.
Abstract: The present work deals with optimization of cascade refrigeration system using eco friendly refrigerants pair R507A and R23. R507A is azeotropic mixture composed of HFC refrigerants R125/R143a (50%/50% by wt.). R23 is a single component HFC refrigerant used as replacement to CFC refrigerant R13 in low temperature applications. These refrigerants have zero ozone depletion potential and are non-flammable. Optimization of R507AR23 cascade refrigeration system performance parameters such as minimum work required, refrigeration effect, coefficient of performance and exergetic efficiency was carried out in terms of eight operating parameters- combinations using Genetic Algorithm tool. The eight operating parameters include (1) low side evaporator temperature (2) high side condenser temperature (3) temperature difference in the cascade heat exchanger (4) low side condenser temperature (5) low side degree of subcooling (6) high side degree of subcooling (7) low side degree of superheating (8) high side degree of superheating. Results show that for minimum work system should operate at high temperature in low side evaporator, low temperature in high side condenser, low temperature difference in cascade condenser, high temperature in low side condenser and low degree of subcooling and superheating in both side. For maximum refrigeration effect system should operate at high temperature in low side evaporator, high temperature in high side condenser, high temperature difference in cascade condenser, low temperature in low side condenser and higher degree of subcooling in LT and HT side. For maximum coefficient of performance and exergetic efficiency, system should operate at high temperature in low side evaporator, low temperature in high side condenser, low temperature difference in cascade condenser, high temperature in low side condenser and higher degree of subcooling and superheating in low side of the system.
Abstract: The present work deals with thermodynamic analysis
of cascade refrigeration system using ozone friendly refrigerants pair
R507A and R23. R507A is azeotropic mixture composed of HFC
refrigerants R125/R143a (50%/50% wt.). R23 is a single component
HFC refrigerant used as replacement to CFC refrigerant R13 in low
temperature applications. These refrigerants have zero ozone
depletion potential and are non-flammable and as R507A an
azeotropic mixture there is no problem of temperature glide. This
study thermodynamically analyzed R507A-R23 cascade refrigeration
system to optimize the design and operating parameters of the
system. The design and operating parameters include: Condensing,
evaporating, subcooling and superheating temperatures in the high
temperature circuit, temperature difference in the cascade heat
exchanger, Condensing, evaporating, subcooling and superheating
temperatures in the low temperature circuit.