Abstract: Power Regeneration in Refrigeration Plant concept
has been analyzed and has been shown to be capable of saving about
25% power in Cryogenic Plants with the Power Regeneration System
(PRS) running under nominal conditions. The innovative component
Compressor Expander Group (CEG) based on turbomachinery has
been designed and built modifying CETT compressor and expander,
both selected for optimum plant performance. Experiments have
shown the good response of the turbomachines to run with R404a as
working fluid. Power saving up to 12% under PRS derated conditions
(50% loading) has been demonstrated. Such experiments allowed
predicting a power saving up to 25% under CEG full load.
Abstract: The Montreal protocol and Kyoto protocol underlined the need of substitution of CFC’s and HCFC’s due to their adverse impact on atmospheric ozone layer which protects earth from U.V rays. The CFCs have been entirely ruled out since 1995 and a long-term basis HCFCs must be replaced by 2020. All this events motivated HFC refrigerants which are harmless to ozone layer. In this paper thermodynamic analysis of cascade refrigeration system has been done using three different refrigerant pairs R13-R12, R290-R23, and R404A-R23. Effect of various operating parameters i.e. evaporator temperature, condenser temperature, temperature difference in cascade condenser and low temperature cycle condenser temperature on performance parameters viz. COP, exergetic efficiency and refrigerant mass flow ratio have been studied. Thermodynamic analysis shows that out of three refrigerant pairs R12-R13, R290-R23 and R404A-R23 the COP of R290-R23 refrigerant pair is highest.
Abstract: Cascade refrigeration systems employ series of single stage vapor compression units which are thermally coupled with evaporator/condenser cascades. Different refrigerants are used in each of the circuit depending on the optimum characteristics shown by the refrigerant for a particular application. In the present research study, a steady state thermodynamic model is developed which simulates the working of an actual cascade system. The model provides COP and all other system parameters e.g. total compressor work, temperature, pressure, enthalpy and entropy at different state points. The working fluid in low temperature circuit (LTC) is CO2 (R744) while Ammonia (R717), Propane (R290), Propylene (R1270), R404A and R12 are the refrigerants in high temperature circuit (HTC). The performance curves of Ammonia, Propane, Propylene, and R404A are compared with R12 to find its nearest substitute. Results show that Ammonia is the best substitute of R12.
Abstract: Capacity and efficiency of any refrigerating system
diminish rapidly as the difference between the evaporating and
condensing temperature is increased by reduction in the evaporator
temperature. The single stage vapour compression refrigeration
system is limited to an evaporator temperature of -40 0C. Below
temperature of -40 0C the either cascade refrigeration system or multi
stage vapour compression system is employed. Present work
describes thermal design of main three heat exchangers namely
condenser (HTS), cascade condenser and evaporator (LTS) of
R404A-R508B and R410A-R23 cascade refrigeration system. Heat
transfer area of condenser (HTS), cascade condenser and evaporator
(LTS) for both systems have been compared and the effect of
condensing and evaporating temperature on heat-transfer area for
both systems have been studied under same operating condition. The
results shows that the required heat-transfer area of condenser and
cascade condenser for R410A-R23 cascade system is lower than the
R404A-R508B cascade system but heat transfer area of evaporator is
similar for both the system. The heat transfer area of condenser and
cascade condenser decreases with increase in condensing temperature
(Tc), whereas the heat transfer area of cascade condenser and
evaporator increases with increase in evaporating temperature (Te).
Abstract: Capacity and efficiency of any refrigerating system
diminish rapidly as the difference between the evaporating and
condensing temperature is increased by a reduction in the evaporator
temperature. The single stage vapour compression refrigeration
system using various refrigerants are limited to an evaporator
temperature of -40 0C. Below temperature of -40 0C the either
cascade refrigeration system or multi stage vapour compression
system is employed. Present work describes thermal design of
condenser (HTS), cascade condenser and evaporator (LTS) of
R404A-R508B and R410A-R23 cascade refrigeration system. Heat
transfer area of condenser, cascade condenser and evaporator for
both systems are compared and the effect of condenser and
evaporator temperature on heat-transfer area for both systems is
studied under same operating condition. The results shows that the
required heat-transfer area of condenser and cascade condenser for
R410A-R23 cascade system is lower than the R404A-R508B cascade
system but heat transfer area of evaporator is similar for both the
system. The heat transfer area of condenser and cascade condenser
decreases with increase in condenser temperature (Tc), whereas the
heat transfer area of cascade condenser and evaporator increases with
increase in evaporator temperature (Te).