Abstract: The increasing demand of electric power is giving an
emphasis on the need for the maximum utilization of renewable
energy sources. On the other hand maintaining power quality to
satisfaction of utility is an essential requirement. In this paper the
design aspects of a Unified Power Quality Conditioner integrated
with photovoltaic system in a distributed generation is presented. The
proposed system consist of series inverter, shunt inverter are
connected back to back on the dc side and share a common dc-link
capacitor with Distributed Generation through a boost converter. The
primary task of UPQC is to minimize grid voltage and load current
disturbances along with reactive and harmonic power compensation.
In addition to primary tasks of UPQC, other functionalities such as
compensation of voltage interruption and active power transfer to the
load and grid in both islanding and interconnected mode have been
addressed. The simulation model is design in MATLAB/ Simulation
environment and the results are in good agreement with the published
work.
Abstract: Voltage flicker problems have long existed in several
of the distribution areas served by the Taiwan Power Company. In
the past, those research results indicating that the estimated ΔV10
value based on the conventional method is significantly smaller than
the survey value. This paper is used to study the relationship between
the voltage flicker problems and harmonic power variation for the
power system with electric arc furnaces. This investigation discussed
thought the effect of harmonic power fluctuation with flicker
estimate value. The method of field measurement, statistics and
simulation is used. The survey results demonstrate that 10 ΔV
estimate must account for the effect of harmonic power variation.
Abstract: This paper presents the experimental results of
leakage current waveforms which appears on porcelain insulator
surface due to existence of artificial pollutants. The tests have been
done using the chemical compounds of NaCl, Na2SiO3, H2SO4, CaO,
Na2SO4, KCl, Al2SO4, MgSO4, FeCl3, and TiO2. The insulator
surface was coated with those compounds and dried. Then, it was
tested in the chamber where the high voltage was applied. Using
correspondence analysis, the result indicated that the fundamental
harmonic of leakage current was very close to the applied voltage
and third harmonic leakage current was close to the yielded leakage
current amplitude. The first harmonic power was correlated to first
harmonic amplitude of leakage current, and third harmonic power
was close to third harmonic one. The chemical compounds of H2SO4
and Na2SiO3 affected to the power factor of around 70%. Both are the
most conductive, due to the power factor drastically increase among
the chemical compounds.