A Concept of Rational Water Management at Local Utilities – The Use of RO for Water Supply and Wastewater Treatment/Reuse

Local utilities often face problems of local industrial
wastes, storm water disposal due to existing strict regulations. For
many local industries, the problem of wastewater treatment and
discharge into surface reservoirs can’t be solved through the use of
conventional biological treatment techniques. Current discharge
standards require very strict removal of a number of impurities such
as ammonia, nitrates, phosphate, etc. To reach this level of removal,
expensive reagents and sorbents are used.
The modern concept of rational water resources management
requires the development of new efficient techniques that provide
wastewater treatment and reuse.
As RO membranes simultaneously reject all dissolved impurities
such as BOD, TDS, ammonia, phosphates etc., they become very
attractive for the direct treatment of wastewater without biological
stage. To treat wastewater, specially designed membrane "open
channel" modules are used that do not possess "dead areas" that cause
fouling or require pretreatment. A solution to RO concentrate
disposal problem is presented that consists of reducing of initial
wastewater volume by 100 times. Concentrate is withdrawn from
membrane unit as sludge moisture. The efficient use of membrane
RO techniques is connected with a salt balance in water system.
Thus, to provide high ecological efficiency of developed techniques,
all components of water supply and wastewater discharge systems
should be accounted for.





References:
[1] J. Losier, A. Fernandez, Using a membrane bioreactor/reverse osmosis
system for indirect potable reuse, Proc. of the conf. on Membranes,
Paris, October 2000, Desalination publications, L'Aquila, Italy. Vol. 2,
297-311.
[2] O. Duin, P. Wessels et al., Direct nanofiltration or ultrafiltration at
WWTP effluent. Proc. of the conf. on Membranes, Paris, October 2000,
Desalination publications, L'Aquila, Italy. Vol. 2, 105-112.
[3] M. Abdel-Javad, S. Ebrahimet. al., Advanced technologies for municipal
wastewater purification: technical and economic assessment,
Desalination, 124 (1999), 251-261.
[4] Pervov A. Scale formation prognosis and cleaning procedure schedules
in reverse osmosis operation, Desalination (1991), 83, 77-118.
[5] Pervov A., Andrianov A. Application of membranes to treat wastewater
for its recycling and reuse: new considerations to reduce fouling and
increase recovery up to 99 per cent, Desalination and water treatment
(2011) 35, 2-9.
[6] R.A. Riddle. Open channel ultrafiltration for reverse osmosis
pretreatment. IDA World Conference on Desalination and Water Reuse.
August 25-29, 1991, Washington DC. Pretreatment and Fouling.
[7] R. Bian, K. Yamamoto,Y. Watahabe. The effect of shear rate on
controlling the concentration polarization and membrane fouling.
Proceedings of the Conf. on Membranes in Drinking and Industrial
Water Production, Paris, France, 3-6 October 2000, v.1, p. 421-432.
[8] ITT PCI Membranes - Membrane Technology- tubular membranes -
micro-, ultra-, nanofiltration, reverse osmosis, http: //
www.pcimembranes.eu/ (accessed 7 November 2010).
[9] H. Futselaar, H. Schoneville, W.Meer. Direct capillary nanofiltration for
surface water. Desalination, 157 (2003), 135-136.
[10] N. Matveev,A. Pervov. Use of reverse osmosis to treat domestic
wastewater for local utilities and in small industries. Tianjin ida world
congress 2013 on desalination and water reuse. IDAWC REF: TIAN13-
217. 20-25 october, China, 2013.
[11] A. Pervov, N. Matveev. Applications of Open Channel Membrane
Modules to Treat and Reuse Wastewater. Journal of Membrane and
Separation Technology | Volume 3 Number 1, 2014, 11-28. DOI:
http://dx.doi.org/10.6000/1929-6037.2014.03.01.2