Abstract: The experimental results on combustion of rice husk
in a conical fluidized bed combustor (referred to as the conical FBC)
using silica sand as the bed material are presented in this paper. The
effects of excess combustion air and combustor loading as well as the
sand bed height on the combustion pattern in FBC were investigated.
Temperatures and gas concentrations (CO and NO) along over the
combustor height as well as in the flue gas downstream from the ash
collecting cyclone were measured. The results showed that the axial
temperature profiles in FBC were explicitly affected by the
combustor loading whereas the excess air and bed height were found
to have minor influences on the temperature pattern. Meanwhile, the
combustor loading and the excess air significantly affected the axial
CO and NO concentration profiles; however, these profiles were
almost independent of the bed height. The combustion and thermal
efficiencies for this FBC were quantified for different operating
conditions.
Abstract: This paper presents the results of the experimental
tests of the cooling performance of a 12,000-Btu/h modified air
conditioner (referred to as M-AC) that use the ground as a heat sink
of a condenser. In the tests, cooling capacity of M-AC with an
optimal length of a condensing coil as well as life expectancy of
copper coil buried underground were investigated. The lengths of
copper coil fabricated and used as condenser coil of M-AC were set
at 67, 50, 40 and 30 m whereas that of a 12,000-Btu/h conventional
split-type air conditioner (referred to as C-AC) was about 22 m. The
results showed that the ground can absorb heat rejected from a
condenser of M-AC. The coefficient of performance (COP) of C-AC
was about 2.5 whereas those of M-AC were found to be higher. It
was found that the values of COP of M-AC with condensing coils of
67, 50 and 40 m long were about 6.9, 5.5 and 3.3, respectively, while
that of 30-m-long one was found to be about 2.1. The electrical
consumptions of M-AC were found lower than that of C-AC in the
range of 11.5 – 15.5%. Additionally, life expectancy of underground
condensing coil of M-AC was found to be over 7 years.