Abstract: The most important parameter in transformers life
expectancy is the hot-spot temperature level which accelerates the
rate of aging of the insulation. The aim of this paper is to present
thermal models for transformers loaded at prefabricated MV/LV
transformer substations and outdoor situations. The hot-spot
temperature of transformers is studied using their top-oil temperature
rise models. The thermal models proposed for hot-spot and top-oil
temperatures of different operating situations are compared. Since the
thermal transfer is different for indoor and outdoor transformers
considering their operating conditions, their hot-spot thermal models
differ from each other. The proposed thermal models are verified by
the results obtained from the experiments carried out on a typical
1600 kVA, 30 /0.4 kV, ONAN transformer for both indoor and
outdoor situations.
Abstract: In gas lifted oil fields, the lift gas should be distributed optimally among the wells which share gas from a common source to maximize total oil production. One of the objectives of the paper is to show that a linear MPC consisting of a control objective and an economic objective can be used both as an optimizer and a controller for gas lifted systems. The MPC is based on linearized model of the oil field developed from first principles modeling. Simulation results show that the total oil production is increased by 3.4%. Difficulties in accurately measuring the bottom hole pressure using sensors in harsh operating conditions can be resolved by using an Unscented Kalman Filter (UKF) for estimation. In oil fields where input disturbance (total supply of gas) is not measured, UKF can also be used for disturbance estimation. Increased total oil production due to optimization leads to increased profit.