Abstract: This paper addresses the problems encountered by conventional distance relays when protecting double-circuit transmission lines. The problems arise principally as a result of the mutual coupling between the two circuits under different fault conditions; this mutual coupling is highly nonlinear in nature. An adaptive protection scheme is proposed for such lines based on application of artificial neural network (ANN). ANN has the ability to classify the nonlinear relationship between measured signals by identifying different patterns of the associated signals. One of the key points of the present work is that only current signals measured at local end have been used to detect and classify the faults in the double circuit transmission line with double end infeed. The adaptive protection scheme is tested under a specific fault type, but varying fault location, fault resistance, fault inception angle and with remote end infeed. An improved performance is experienced once the neural network is trained adequately, which performs precisely when faced with different system parameters and conditions. The entire test results clearly show that the fault is detected and classified within a quarter cycle; thus the proposed adaptive protection technique is well suited for double circuit transmission line fault detection & classification. Results of performance studies show that the proposed neural network-based module can improve the performance of conventional fault selection algorithms.
Abstract: This paper presents the development of adaptive
distance relay for protection of parallel transmission line with mutual
coupling. The proposed adaptive relay, automatically adjusts its
operation based on the acquisition of the data from distance relay of
adjacent line and status of adjacent line from line circuit breaker IED
(Intelligent Electronic Device). The zero sequence current of the
adjacent parallel transmission line is used to compute zero sequence
current ratio and the mutual coupling effect is fully compensated.
The relay adapts to changing circumstances, like failure in
communication from other relays and non - availability of adjacent
transmission line. The performance of the proposed adaptive relay is
tested using steady state and dynamic test procedures. The fault
transients are obtained by simulating a realistic parallel transmission
line system with mutual coupling effect in PSCAD. The evaluation
test results show the efficacy of adaptive distance relay over the
conventional distance relay.
Abstract: Pairwise testing, which requires that every
combination of valid values of each pair of system factors be covered
by at lease one test case, plays an important role in software testing
since many faults are caused by unexpected 2-way interactions among
system factors. Although meta-heuristic strategies like simulated
annealing can generally discover smaller pairwise test suite, they may
cost more time to perform search, compared with greedy algorithms.
We propose a new method, improved Extremal Optimization (EO)
based on the Bak-Sneppen (BS) model of biological evolution, for
constructing pairwise test suites and define fitness function according
to the requirement of improved EO. Experimental results show that
improved EO gives similar size of resulting pairwise test suite and
yields an 85% reduction in solution time over SA.
Abstract: Natural disasters, including earthquake, kill many people around the world every year. Society rescue actions, which start after the earthquake and are called LAST in abbreviation, include locating, access, stabilization and transportation. In the present article, we have studied the process of local accessibility to the injured and transporting them to health care centers. With regard the heavy traffic load due to earthquake, the destruction of connecting roads and bridges and the heavy debris in alleys and street, which put the lives of the injured and the people buried under the debris in danger, accelerating the rescue actions and facilitating the accessibilities are of great importance, obviously. Tehran, the capital of Iran, is among the crowded cities in the world and is the center of extensive economic, political, cultural and social activities. Tehran has a population of about 9.5 millions and because of the immigration of people from the surrounding cities. Furthermore, considering the fact that Tehran is located on two important and large faults, a 6 Richter magnitude earthquake in this city could lead to the greatest catastrophe during the entire human history. The present study is a kind of review and a major part of the required information for it, has been obtained from libraries all of the rescue vehicles around the world, including rescue helicopters, ambulances, fire fighting vehicles and rescue boats, and their applied technology, and also the robots specifically designed for the rescue system and the advantages and disadvantages of them, have been investigated. The studies show that there is a significant relationship between the rescue team-s arrival time at the incident zone and the number of saved people; so that, if the duration of burial under debris 30 minutes, the probability of survival is %99.3, after a day is %81, after 2days is %19 and after 5days is %7.4. The exiting transport systems all have some defects. If these defects are removed, more people could be saved each hour and the preparedness against natural disasters is increased. In this study, transport system has been designed for the rescue team and the injured; which could carry the rescue team to the incident zone and the injured to the health care centers. In addition, this system is able to fly in the air and move on the earth as well; so that the destruction of roads and the heavy traffic load could not prevent the rescue team from arriving early at the incident zone. The system also has the equipment required firebird for debris removing, optimum transport of the injured and first aid.
Abstract: A Comparison and evaluation of the different
condition monitoring (CM) techniques was applied experimentally
on RC e.g. Dynamic cylinder pressure and crankshaft Instantaneous
Angular Speed (IAS), for the detection and diagnosis of valve faults
in a two - stage reciprocating compressor for a programme of
condition monitoring which can successfully detect and diagnose a
fault in machine. Leakage in the valve plate was introduced
experimentally into a two-stage reciprocating compressor. The effect
of the faults on compressor performance was monitored and the
differences with the normal, healthy performance noted as a fault
signature been used for the detection and diagnosis of faults.
The paper concludes with what is considered to be a unique
approach to condition monitoring. First, each of the two most useful
techniques is used to produce a Truth Table which details the
circumstances in which each method can be used to detect and
diagnose a fault. The two Truth Tables are then combined into a
single Decision Table to provide a unique and reliable method of
detection and diagnosis of each of the individual faults introduced
into the compressor. This gives accurate diagnosis of compressor
faults.
Abstract: The purpose of this paper is to solve the problem of protecting aerial lines from high impedance faults (HIFs) in distribution systems. This investigation successfully applies 3I0 zero sequence current to solve HIF problems. The feature extraction system based on discrete wavelet transform (DWT) and the feature identification technique found on statistical confidence are then applied to discriminate effectively between the HIFs and the switch operations. Based on continuous wavelet transform (CWT) pattern recognition of HIFs is proposed, also. Staged fault testing results demonstrate that the proposed wavelet based algorithm is feasible performance well.
Abstract: In this paper the behavior of fixed series compensated
extra high voltage transmission lines during faults is simulated. Many
over-voltage protection schemes for series capacitors are limited in
terms of size and performance, and are easily affected by
environmental conditions. While the need for more compact and
environmentally robust equipment is required. use of series
capacitors for compensating part of the inductive reactance of long
transmission lines increases the power transmission capacity.
Emphasis is given on the impact of modern capacitor protection
techniques (MOV protection). The simulation study is performed
using MATLAB/SIMULINK®and results are given for a three phase
and a single phase to ground fault.
Abstract: The group mutual exclusion (GME) problem is a
variant of the mutual exclusion problem. In the present paper a
token-based group mutual exclusion algorithm, capable of handling
transient faults, is proposed. The algorithm uses the concept of
dynamic request sets. A time out mechanism is used to detect the
token loss; also, a distributed scheme is used to regenerate the token.
The worst case message complexity of the algorithm is n+1. The
maximum concurrency and forum switch complexity of the
algorithm are n and min (n, m) respectively, where n is the number of
processes and m is the number of groups. The algorithm also satisfies
another desirable property called smooth admission. The scheme can
also be adapted to handle the extended group mutual exclusion
problem.
Abstract: In this paper, we propose a hardware and software
design method for automotive Electronic Control Units (ECU)
considering the functional safety. The proposed ECU is considered for
the application to Electro-Mechanical Actuator systems and the
validity of the design method is shown by the application to the
Electro-Mechanical Brake (EMB) control system which is used as a
brake actuator in Brake-By-Wire (BBW) systems. The importance of a
functional safety-based design approach to EMB ECU design has been
emphasized because of its safety-critical functions, which are executed
with the aid of many electric actuators, sensors, and application
software. Based on hazard analysis and risk assessment according to
ISO26262, the EMB system should be ASIL-D-compliant, the highest
ASIL level. To this end, an external signature watchdog and an
Infineon 32-bit microcontroller TriCore are used to reduce risks
considering common-cause hardware failure. Moreover, a software
design method is introduced for implementing functional
safety-oriented monitoring functions based on an asymmetric dual
core architecture considering redundancy and diversity. The validity
of the proposed ECU design approach is verified by using the EMB
Hardware-In-the-Loop (HILS) system, which consists of the EMB
assembly, actuator ECU, a host PC, and a few debugging devices.
Furthermore, it is shown that the existing sensor fault tolerant control
system can be used more effectively for mitigating the effects of
hardware and software faults by applying the proposed ECU design
method.
Abstract: The intermittent connectivity modifies the “always
on" network assumption made by all the distributed query processing
systems. In modern- day systems, the absence of network
connectivity is considered as a fault. Since the last upload, it might
not be feasible to transmit all the data accumulated right away over
the available connection. It is possible that vital information may be
delayed excessively when the less important information takes place
of the vital information. Owing to the restricted and uneven
bandwidth, it is vital that the mobile nodes make the most
advantageous use of the connectivity when it arrives. Hence, in order
to select the data that needs to be transmitted first, some sort of data
prioritization is essential. A continuous query processing system for
intermittently connected mobile networks that comprises of a delaytolerant
continuous query processor distributed across the mobile
hosts has been proposed in this paper. In addition, a mechanism for
prioritizing query results has been designed that guarantees enhanced
accuracy and reduced delay. It is illustrated that our architecture
reduces the client power consumption, increases query efficiency by
the extensive simulation results.
Abstract: This paper describes a methodology for remote
performance monitoring of retail refrigeration systems. The proposed
framework starts with monitoring of the whole refrigeration circuit
which allows detecting deviations from expected behavior caused by
various faults and degradations. The subsequent diagnostics methods
drill down deeper in the equipment hierarchy to more specifically
determine root causes. An important feature of the proposed concept
is that it does not require any additional sensors, and thus, the
performance monitoring solution can be deployed at a low
installation cost. Moreover only a minimum of contextual
information is required, which also substantially reduces time and
cost of the deployment process.
Abstract: This paper focuses on PSS/E modeling of wind farms
of Doubly-fed Induction Generator (DFIG) type and their impact on
issues of power system operation. Since Wind Turbine Generators
(WTG) don-t have the same characteristics as synchronous
generators, the appropriate modeling of wind farms is essential for
transmission system operators to analyze the best options of
transmission grid reinforcements as well as to evaluate the wind
power impact on reliability and security of supply. With the high
excepted penetration of wind power into the power system a
simultaneous loss of Wind Farm generation will put at risk power
system security and reliability. Therefore, the main wind grid code
requirements concern the fault ride through capability and frequency
operation range of wind turbines. In case of grid faults wind turbines
have to supply a definite reactive power depending on the
instantaneous voltage and to return quickly to normal operation.
Abstract: The new idea of this research is application of a new fault detection and isolation (FDI) technique for supervision of sensor networks in transportation system. In measurement systems, it is necessary to detect all types of faults and failures, based on predefined algorithm. Last improvements in artificial neural network studies (ANN) led to using them for some FDI purposes. In this paper, application of new probabilistic neural network features for data approximation and data classification are considered for plausibility check in temperature measurement. For this purpose, two-phase FDI mechanism was considered for residual generation and evaluation.
Abstract: This paper presents the concept and realisation of an
e-learning tool that provides predefined or automatically generated
exercises concerning logistics cost accounting. Students may practise
where and whenever they like to via the Internet. Their solutions are
marked automatically by the tool while considering consecutive
faults and without any intervention of lecturers.
Abstract: Modern manufacturing facilities are large scale,
highly complex, and operate with large number of variables under
closed loop control. Early and accurate fault detection and diagnosis
for these plants can minimise down time, increase the safety of plant
operations, and reduce manufacturing costs. Fault detection and
isolation is more complex particularly in the case of the faulty analog
control systems. Analog control systems are not equipped with
monitoring function where the process parameters are continually
visualised. In this situation, It is very difficult to find the relationship
between the fault importance and its consequences on the product
failure. We consider in this paper an approach to fault detection and
analysis of its effect on the production quality using an adaptive
centring and scaling in the pickling process in cold rolling. The fault
appeared on one of the power unit driving a rotary machine, this
machine can not track a reference speed given by another machine.
The length of metal loop is then in continuous oscillation, this affects
the product quality. Using a computerised data acquisition system,
the main machine parameters have been monitored. The fault has
been detected and isolated on basis of analysis of monitored data.
Normal and faulty situation have been obtained by an artificial neural
network (ANN) model which is implemented to simulate the normal
and faulty status of rotary machine. Correlation between the product
quality defined by an index and the residual is used to quality
classification.
Abstract: This paper deals with a novel approach of power
transformers diagnostics. This approach identifies the exact location
and the range of a fault in the transformer and helps to reduce
operation costs related to handling of the faulty transformer, its
disassembly and repair. The advantage of the approach is a
possibility to simulate healthy transformer and also all faults, which
can occur in transformer during its operation without its
disassembling, which is very expensive in practice. The approach is
based on creating frequency dependent impedance of the transformer
by sweep frequency response analysis measurements and by 3D FE
parametrical modeling of the fault in the transformer. The parameters
of the 3D FE model are the position and the range of the axial short
circuit. Then, by comparing the frequency dependent impedances of
the parametrical models with the measured ones, the location and the
range of the fault is identified. The approach was tested on a real
transformer and showed high coincidence between the real fault and
the simulated one.
Abstract: Analytical seismic response of multi-story building
supported on base isolation system is investigated under real
earthquake motion. The superstructure is idealized as a shear type
flexible building with lateral degree-of-freedom at each floor. The
force-deformation behaviour of the isolation system is modelled by
the bi-linear behaviour which can be effectively used to model all
isolation systems in practice. The governing equations of motion of
the isolated structural system are derived. The response of the system
is obtained numerically by step-by-method under three real recorded
earthquake motions and pulse motions associated in the near-fault
earthquake motion. The variation of the top floor acceleration, interstory
drift, base shear and bearing displacement of the isolated
building is studied under different initial stiffness of the bi-linear
isolation system. It was observed that the high initial stiffness of the
isolation system excites higher modes in base-isolated structure and
generate floor accelerations and story drift. Such behaviour of the
base-isolated building especially supported on sliding type of
isolation systems can be detrimental to sensitive equipment installed
in the building. On the other hand, the bearing displacement and base
shear found to reduce marginally with the increase of the initial
stiffness of the initial stiffness of the isolation system. Further, the
above behaviour of the base-isolated building was observed for
different parameters of the bearing (i.e. post-yield stiffness and
characteristic strength) and earthquake motions (i.e. real time history
as well as pulse type motion).
Abstract: Self-sensing estimates the air gap within an electro
magnetic path by analyzing the bearing coil current and/or voltage
waveform. The self-sensing concept presented in this paper has been
developed within the research project “Active Magnetic Bearings
with Supreme Reliability" and is used for position sensor fault
detection.
Within this new concept gap calculation is carried out by an alldigital
analysis of the digitized coil current and voltage waveform.
For analysis those time periods within the PWM period are used,
which give the best results. Additionally, the concept allows the
digital compensation of nonlinearities, for example magnetic
saturation, without degrading signal quality. This increases the
accuracy and robustness of the air gap estimation and additionally
reduces phase delays.
Beneath an overview about the developed concept first
measurement results are presented which show the potential of this
all-digital self-sensing concept.
Abstract: This paper presents modern vibration signalprocessing
techniques for vehicle gearbox fault diagnosis, via the
wavelet analysis and the Squared Envelope (SE) technique. The
wavelet analysis is regarded as a powerful tool for the detection of
sudden changes in non-stationary signals. The Squared Envelope
(SE) technique has been extensively used for rolling bearing
diagnostics. In the present work a scheme of using the Squared
Envelope technique for early detection of gear tooth pit. The pitting
defect is manufactured on the tooth side of a fifth speed gear on the
intermediate shaft of a vehicle gearbox. The objective is to
supplement the current techniques of gearbox fault diagnosis based
on using the raw vibration and ordered signals. The test stand is
equipped with three dynamometers; the input dynamometer serves as
the internal combustion engine, the output dynamometers introduce
the load on the flanges of output joint shafts. The gearbox used for
experimental measurements is the type most commonly used in
modern small to mid-sized passenger cars with transversely mounted
powertrain and front wheel drive; a five-speed gearbox with final
drive gear and front wheel differential. The results show that the
approaches methods are effective for detecting and diagnosing
localized gear faults in early stage under different operation
conditions, and are more sensitive and robust than current gear
diagnostic techniques.
Abstract: Preliminary studies on Kuwait high voltage
transmission system show significant increase in the short circuit
level at some of the grid substations and some generating stations.
This increase results from the growth in the power transmission
systems in size and complexity. New generating stations are expected
to be added to the system within the next few years. This paper
describes the study analysis performed to evaluate the available and
potential solutions to control SC levels in Kuwait power system. It
also presents a modified planning of the transmission network in
order to fulfill this task.